# DFNT.CFG # # This file contains the configuration for the MVIxx-DFNT communication # module. # # LOCATION : # DATE : # CONFIGURED BY : # MODIFIED : # # This section is used to define the configuration for the Module level # data. # [Module] Module Name : Test Example of MVI71-DFNT Communication Module Read Register Start : 0 #First register to transfer from module -> PLC Read Register Count : 120 #Number of registers to transfer to PLC Write Register Start : 200 #First register where to store data received from PLC Write Register Count : 120 #Number of registers to receive from PLC Failure Flag Count : -1 # Number of BP Errors to disable protocol comm Initialize Output Data : No #Initialize the database file on startup DFNT Server File Size : 100 #100 or 1000 as max file size for DFNT server # This section is used to define the DF1 pass-through server on Port 1 # (the second port) [DF1 Pass-Through Server Port 1] Enabled : Yes #Y=Use server, N=Do not use server Service Port Number : 15000 #TCP service port for this server Busy Timeout : 500 #Time to wait for not Busy (100-65535 mSec) Baud Rate : 19200 #Baud rate for port 110-19200 Parity : N #N=None,O=Odd,E=Even,M=Mark,S=Space Data Bits : 8 #5, 6, 7 or 8 Stop Bits : 1 #1 or 2 # This section is used to define the configuration for the DF1 pass-through # port on Port 2 (the third port) # [DF1 Pass-Through Port] Enabled : Y #Y=Use port, N=Do not use port Local Station ID : 1 #DF1 node address Protocol : H #F=Full-Duplex, H=Half-Duplex Termination Type : CRC #B=BCC, C=CRC Baud Rate : 38400 #Baud rate for port 1200-38400 Parity : None #N=None,O=Odd,E=Even,M=Mark,S=Space Data Bits : 8 #5, 6, 7 or 8 Stop Bits : 1 #1 or 2 RTS On : 0 #0-65536 mSec before message RTS Off : 0 #0-65536 mSec after message Use CTS Line : N #Use CTS modem control line (Y/N) Retry Count : 3 #Response failure retry count Request Timeout : 500 #Request messgage timeout (0-10000 mSec) Busy Timeout : 500 #Port Busy timeout (0-10000 mSec) ACK Timeout : 500 #DLE-ACK timeout (0-10000 mSec) # This section is used to define the configuration for the master device # simulated on network port # [DFNT Client 0] Minimum Command Delay : 30 #Minimum number of msec's between commands Response Timeout : 1000 #Response message timeout (0-5000 mSec) Retry Count : 3 #Response failure retry count [DFNT Client 0 Commands] # # The file contains examples for a ControlLogix processor with the N7 file # configured. This example uses SLC and PLC5 commands. # # LOCATION : # DATE : 04/05/2000 # CONFIGURED BY : RAR # MODIFIED : # # 1 2 3 4 5 6 7 8 9 10 11 12 # DB Poll Swap Func File File Elm Sub #Enab Addr Delay Count Code Node IP Address Slot Code Type # # Elm START 1 0 0 5 0 192.168.0.136 0 501 N 10 0 0 200 0 5 0 192.168.0.136 0 509 N 10 5 END