# 94MCMM.CFG # # Example file for use with the MVI94-MCM communication module with a # Modbus Master port on PRT2. # # DATE : 08/01/2002 # LOCATION : Example shipped with MVI94-MCM communication module # DESCRIPTION : MVI94-MCM Master Version 1.07 # MODIFIED : [Module] # Settings required by both Master and Slave Module Name : MVI94-MCM Modbus Master Module Maximum Register : 3996 #Maximum number of Modbus registers in #virtual database Error/Status Block Pointer : -1 #Offset in virtual database to the start #of the module status list Error/Status Frequency : 1000 #Update frequency of status list (mSec) BT Read Start Register : 0 #Starting register in virtual database to #write to processor BT Read Register Count : 96 #Number of registers to write to processor BT Write Start Register : 600 #Starting register in virtual database to #read from processor BT Write Register Count : 96 #Number of registers to read from processor Backplane Fail Count : 10 #Number of consecutive backplane transfer #failures before halting communications [Port] # Settings required by both Master and Slave Type : 0 #Port type 0=Master, 1=Slave, #3=Slave (Pass-through, data swapped), #4=Slave (Pass-through) Float Flag : N #Use floating data type Y=Yes, N=No Float Start : 7000 #Starting register to be considered as #a floating-point number Float Offset : 2000 #Offset in virtual database for floating- #point numbers Protocol : 0 #Modbus Protocol 0=RTU, 1=ASCII Baud Rate : 9600 #Baud rate for port Parity : 0 #0=None,1=Odd, 2=Even, 3=Mark, 4=Space Data Bits : 8 #5 to 8 data bits Stop Bits : 1 #1 or 2 stop bits RTS On : 0 #Delay after RTS set before message sent (mSec) RTS Off : 0 #Delay after message before RTS dropped(mSec) Minimum Response Delay : 10 #Number of mSec to delay before respose Use CTS Line : N #Monitor CTS modem line (Y/N) [Modbus Master] # Settings required for Master Driver Command Count : 2 #Command list count for port Minimum Command Delay : 1000 #mSec delay between commands Command Error Pointer : 90 #Internal database location of cmd err list data Response Timeout : 1000 #mSec for response timeout of command Retry Count : 3 #retry count for failed requests Error Delay Count : 10 #0-65535 delay for slave after comm error [Commands] # Internal Poll Reg Swap Node Modbus MB Address # Enable Address Interval Count Code Address Func in Device START 1 0 1 10 0 1 3 600 0 600 1 10 0 1 16 400 END