FH Ethernet
RLX-FHE
The RadioLinx Frequency Hopping Ethernet radio is designed to operate in high-interference environments by combining advanced frequency hopping and digital signal processing technology with outstanding receiver sensitivity and antenna diversity. This combination results in exceptional noise and interference rejection.
The RLX-FHE is compatible with all protocols that run over standard IEEE 802.3 Ethernet including TCP/IP, UDP, IPX, NetBEUI, BootP, EtherNet/IP, and Modbus/TCP. The RLX-FHE simultaneously supports multiple 802.3 compliant protocols.
- Supports up to 1000 addressed devices with 2000 radios and 78 repeaters per network
- 64 user-selectable data channels for multiple network operation
- Active antenna diversity
- 2.4 GHz frequency hopping spread spectrum (FHSS) technology
- Secure wireless communications with data encryption, proprietary radio protocol, and 2.4 GHz FHSS physical layer
- Industrial temperature range
- 15+ (24 km) mile range with high-gain antennas (longer with repeaters)
- Remote diagnostics without interrupting data communications
- Over air user programmability (after initial configuration) using Windows-based software
- Three year standard warranty
Functional Specifications
|
Radio
|
|
Frequency
|
2400 to 24835.5 MHz (varies by country)
|
|
Compliance
|
IEEE 802.3, 802.3u, 802.3x
|
|
Protocols
|
All standard IEEE 802.3 protocols
|
|
Encryption
|
ARC4 (40 or 128 bit)
|
|
Network Topology
|
Peer-to-Peer, store and forward repeater
|
|
Hop Patterns
|
64 independent, non-interfacing networks
|
|
Error Detection
|
32-bit CRC and ARQ (Automatic Re-Send Query)
|
|
Radio Type
|
Frequency Hopping Spread Spectrum
|
|
Output power
|
1mW to 250mW, programmable (varies by country
|
|
Channel data rates
|
250 Kbps
|
|
Receiver sensitivity
|
-96 dBm @ 10-6 BER
|
|
Channels - user selectable
|
64 North America (varies by country)
|
|
Typical indoor range
|
500 to 1500 ft (150 to 450 meters)
|
|
Outdoor range
|
15 + miles line of sight with high-gain antennas
|
|
Security
|
ARC4 (40 or 128 bit)
|
|
Physical
|
|
Enclosure
|
Extruded aluminum with DIN and panel mount
|
|
Size
|
4.10" x 3.71" x 2.05" (104.1 mm x 94.23 mm x 52.07 mm)
|
|
Vibration Shock
|
IEC 60068-2-6 IEC 60068-2-27
|
|
Ethernet port
|
10/100 Base-T connector, shielded RJ45
IEEE 802.3, 802.3u, 802.3x
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
|
|
Weight
|
1 lbs /454g
|
|
Environmental
|
|
Operating temperature
|
-40°C to +70°C (-40° F to 158° F)
|
|
Humidity
|
To 90% RH, non-condensing
|
|
External power
|
10 to 24 VDC
|
|
Average power
|
<4W
|
Regulatory Approvals
|
Type Approvals
|
|
FCC
|
FCC Part 15.247
|
|
Industry Canada
|
RSS 210
|
|
Europe / CE
|
LVD EN 50850-2000
RF Safety EN 50364-2001
EMC EN 301 489-1, EN 301 489-17
Spectrum EN 300 328 v1.4.1
|
|
Mexico
|
Nom 121 SCT1 2 or 1
|
|
Australia
|
AS/NZS 4771
|
|
Brazil
|
365 / 2004 e
238 / 2000
|
|
Malaysia
|
SIRIM
|
|
Hazardous Locations
|
|
UL
|
UL 1604 Class I Division 2, Groups A, B, C, D Temp Code T4A
|
|
CSA/cUL
|
C22.2 No. 213-1987
|
|
ATEX Zone 2
|
ATEX II 3 G EEx nC IIC
|
Ordering Information
| RLX-FHE |
FH Ethernet |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.
Sales and Support:
|