Weather Resistant RadioLinx Industrial Hotspot
RLX-IHW-66
The RadioLinx Industrial Hotspot (RLX-IHW-66) provides high speed industrial wireless Ethernet communications between Ethernet devices such as PLCs, I/O, and operator interfaces while serving as a repeater/bridge for other hotspots, and an access point for wireless clients such as laptops and PDAs.
Features and Benefits
Conforms to IEEE 802.11a/b/g
- Open standard protects wireless network investment
- High speed (54 Mbps), low latency communications
- Radio-based IGMP snooping/querying to filter multicast industrial Ethernet maximizing bandwidth
Rugged and Powerful
- IP-66 rated metal enclosure, industrial operating temperatures, vibration and shock resistant
- Certification for use in hazardous locations (ISA 12.12.01 Class 1 Div 2, ATEX Category 3 Zone 2)
- Transmit power and radio frequencies programmable for use globally
Data and Network Security
- Cryptographic strength security with WPA2/802.11i-128/192/256 bit AES encryption and CCM integrity check
- Limit access to approved device MAC IDs
- Monitors RF environment for approved/rogue radios
Flexible and Reliable
- Power over Ethernet (PoE) enables radio placement near antenna to reduce antenna cable costs and improve wireless network performance
- Single radio operates as an access point and repeater/bridge and client
- Automatic network configuration (can be prioritized or fixed) with self-healing network and master redundancy for reliable large networks (e.g. SCADA)
Easy to Configure and Monitor
- Built-in web server for browser-based configuration and remote diagnostics
- Included OPC Server for HMI-based RF network diagnostics
Backed by ProSoft Technology
- Industrial data communications experts who understand your protocols, devices, and applications
- Indoor/outdoor radio network design assistance – accessory selection, path studies, and site survey
- Three year standard warranty
Applications
Use the RLX-IHW-66 in applications where secure, high-speed, untethered Ethernet connectivity is required outdoors or in indoor environments requiring dust-tight or water-tight protection:
- Connect to moving or remote industrial devices while providing wireless coverage for mobile workers’ PDAs and laptops
-
Combine voice, video and data on a single, high speed industrial wireless network
Use for applications generating many packets per second or with high aggregate data requirements such as I/O messaging and client/server based HMI
Specifications
Radio
|
Frequency Band (Varies by Country)
|
802.11b/g:
2.412 to 2.462 GHz (FCC)
2.412 to 2.472 GHz (ETSI)
802.11a:
5.150 to 5.250 GHz (FCC/ETSI)
5.725 to 5.850 GHz (FCC)
|
|
Wireless Standards
|
802.11a, 802.11b, 802.11g, 802.11i
|
|
Transmit Power (Programmable)
|
Up to 50 mW without amplifier
Up to 500 mW with optional amplifier
|
|
Channel data rates (Modulation)
|
802.11b: 11, 5.5, 2, 1 Mbps (DSSS - BPSK, QPSK, CCK)
802.11g: 54, 48, 36, 24, 18, 12, 9, 6 Mbps (OFDM)
802.11a: 54, 48, 36, 24, 18, 12, 9, 6 Mbps (OFDM)
|
|
Receiver Sensitivity (Typical)
|
–95 dBm @ 1 Mbps
–90 dBm @ 11 Mbps
–82 dBm @ 24 Mbps
–75 dBm @ 54 Mbps
|
|
Channels Selection
|
1 to 13 (802.11b/g)
36, 40, 44, 48, 149, 153, 157, 161, 165 (802.11a)
|
|
Security
|
WPA2/802.11i with 128/192/256 bit AES-CCM
Legacy WPA TKIP, WEP support
MAC ID filter
Admin password
|
Physical
|
Enclosure
|
IP66 die-cast aluminum with pole mount hardware
|
|
Overall Dimensions
|
213 ´ 178 ´ 56 mm (W ´ H ´ D)
8.4 ´ 7.0 ´ 2.2 inches
|
|
Ethernet Ports
|
Water/Dust Tight M12 Connector
IEEE 802.3, 802.3u, 802.3x, 802.3af
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
|
|
Antenna Ports
|
(2) N-type female connectors
|
|
Weight
|
2.4 lb (1.1 kg)
|
Environmental
|
Operating Temperature
|
–30° C to +60° C
|
|
Humidity
|
To 90% RH, non-condensing
|
|
External Power
|
802.3af PoE
|
|
Average Power
|
<6W
|
Regulatory Approvals
Wireless Approvals
Visit our website www.prosoft-technology.com for current wireless approval information.
|
Hazardous Locations:
CSA/cCSAus
|
ISA 12.12.01 Class 1, Div. 2
C22.2 No. 213-1987
|
|
ATEX
|
Category 3, Zone 2
|
Ordering Information
| RLX-IHW-66 |
Weather Resistant RadioLinx Industrial Hotspot |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.
Sales and Support:
|
|