Modbus Master/Slave Enhanced Communication Module

MVI56E-MCM, MVI56E-MCMXT

The MVI56E Enhanced Modbus Master/Slave Communication Modules allow Rockwell Automation ControlLogix processors to easily interface with devices using the Modbus RTU/ASCII serial communications protocol.

The MVI56E-MCM and MVI56E-MCMXT act as input/output modules on the ControlLogix backplane, making Modbus data appear as I/O data to the processor. Data transfer to and from the processor is asynchronous from the communications on the Modbus network. Two independently-configurable serial ports can operate on the same or different Modbus networks. Each port can be configured as a Modbus Master or Slave, sharing the same user-controlled 5000-word database.

The two modules are functionally the same. The MVI56E-MCM is designed for standard process applications. The MVI56E-MCMXT is designed for the Logix-XT control platform, allowing it to operate in extreme environments, at higher operating temperatures, and has a conformal coating to protect it from harsh or caustic conditions.

Features

Benefits

Backward Compatibility

  • All MVI56E products are backward-compatible with earlier MVI56 modules allowing direct replacement without the need to change existing controller programs
  • Enjoy Enhanced features and flexibility without incurring expensive reprogramming costs

RSLogix 5000 Integrated

  • Module configuration and communication is integrated within RSLogix 5000
  • No additional programming or configuration software is required
  • Add-On Instruction for RSLogix 5000 version 16 or higher cuts development time and costs

CIPconnect-enabled

  • ProSoft Configuration Builder software (PCB), with CIPconnect, facilitates remote user access across the ControlLogix backplane through Rockwell Automation's 1756-ENBT module
  • Configure, diagnose, and analyze process data and communications status
  • CIPconnect can bridge through multiple ENBT/CNBT links to connect to MVI56E-MCMs installed in remote chassis for configuration and diagnostics

4-digit LED Display

  • A scrolling display for easily-understood, plain English diagnostic and error information
  • See critical configuration and status information without having to hook up to the port

Ethernet Port with Built-in Web Server

  • Module Ethernet port provides a built-in web server for access to documentation, module status, firmware update software, and support software
  • Local and remote diagnostics access available through the Ethernet Port

Configuration

ProSoft Configuration Builder (PCB) provides a PC-based software configuration solution for quick and easy management of ProSoft Technology modules, as well as viewing module and network diagnostics. PCB provides an excellent diagnostic tool for the module when used with CIPconnect technology, providing communication over local and remote chassis. The Setup Guide and sample configuration provide a quick start up with step by step instructions on how to move data from the Modbus network to the controller.

General Specifications

  • Backward-compatible with previous MVI56-MCM version
  • Single Slot - 1756 ControlLogix backplane compatible
  • 10/100 MB Ethernet port for configuration with Auto Cable Crossover Detection
  • User-definable module data memory mapping of up to 5000 16-bit registers
  • CIPconnect-enabled network configuration and diagnostics monitoring using ControlLogix 1756-ENxT modules and EtherNet/IPpass-thru communications
  • Sample Ladder Logic or Add-On Instruction (AOI) used for data transfers between module and processor and for module configuration
  • Internal web page providing access to product documentation, module status, and firmware update software
  • 4-character, scrolling LED display of status and diagnostic data in plain English
  • ProSoft Discovery Service (PDS) software finds the module on the network and assigns a temporary IP address to facilitate module access

Functional Specifications

  • Adjustable Modbus floating point data support in Enron, Daniels and other formats
  • Powerful Modbus network analyzer diagnostics using ProSoft Configuration Builder
  • Optional ladder logic functions, like Command Control, Event Commands, and Slave Disable/Enable functions, give users the option to place normally automatic Modbus polling under logic control for special situations.
  • Error codes, network error counters, and port status data available in pre-defined controller tag arrays or may be stored in user data memory

Modbus General Specifications

Communication parameters

Baud Rate: 110 baud to 115.2 kbps
Stop Bits: 1 or 2
Data Size: 7 or 8 bits
Parity: None, Even, Odd
RTS Timing delays: 0 to 65535 milliseconds

Modbus Modes

RTU mode (binary) with CRC-16
ASCII mode with LRC error checking

Floating Point Data

Floating point data movement supported, including configurable support for Enron and Daniel implementations

Modbus Function Codes

1: Read Coils Status
2: Read Input Status
3: Read Holding Registers
4: Read Input Registers
5: Force (Write) Single Coil
6: Preset (Write) Single Register
8: Diagnostics
15: Force (Write) Multiple Coils
16: Preset (Write) Multiple Data Registers
17: Report Slave ID
22: Mask Write 4x Register
23: Read/Write 4x Registers

Modbus Master Specifications

Command List

Up to 100 commands per Master port, each fully configurable for function code, slave address, register to/from addressing and word/bit count.

Optimized Polling

Configuration options allow Master ports and commands to be optimized to poll slaves with communication problems less frequently.

Command Status/Error Monitoring

Command Status or Error codes are generated for each command as it executes, allowing careful monitoring of communication health between the Master and its Slaves.

Slave Polling Control

Master Port maintains a Slave Status list of all network Slaves. Polling of each Slave may be disabled and enabled using this list.

Modbus Slave Specifications

Full Memory Access

A port configured as a Modbus Slave permits a remote Master to read from or write to any of the 5000 registers that make up the user memory database.

Multi-source Slave data

Data presented at the Slave port can be derived from other Modbus Slave devices on a different network through the module's Master port or from the processor tag database.

Node address

1 to 247 (software selectable)

Status Data

Slave port error codes, counters and statuses are available separately for each port when configured as a Slave

Hardware Specifications

General

Specification

Description

Backplane Current Load

800 mA @ 5 V DC
3 mA @ 24V DC

Operating Temperature

0° to 60°C (32 to 140°F) - MVI56E-MCM

-25° to 70°C (-13° to 158°F) - MVI56E-MCMXT

Storage Temperature

-40° to 85°C (-40 to 185°F)

Extreme/Harsh Environment

MVI56E-MCMXT comes with conformal coating

Shock

30g Operational
50g non-operational
Vibration: 5 g from 10 to 150 Hz

Relative Humidity

5% to 95% (non-condensing)

LED Indicators

Battery Status (ERR)
Application Status (APP)
Module Status (OK)

4-Character, Scrolling, Alpha-Numeric LED Display

Shows Module, Version, IP, Port Master/Slave Setting, Port Status, and Error Information

Debug/Configuration Ethernet port (E1 - Config)

Ethernet Port

10/100 Base-T, RJ45 Connector, for CAT5 cable

Link and Activity LED indicators

Auto-crossover cable detection

Serial Application ports (P1 & P2)

Full hardware handshaking control, providing radio, modem, and multi-drop support

Software configurable communication parameters

Baud rate: 110 baud to 115.2 kbps
RS-232, 485 and 422
Parity: none, odd or even
Data bits: 5, 6, 7, or 8
Stop bits: 1 or 2
RTS on/off delay: 0 to 65535 milliseconds

App Ports (P1, P2)

RJ45 (DB-9M with supplied adapter cable)
Configurable RS-232 hardware handshaking
500V Optical isolation from backplane

RS-232, RS-422, RS-485 jumper-select, each port

RX (Receive) and TX (Transmit) LEDs, each port

Shipped with Unit

RJ45 to DB-9M cables for each serial port
5 foot Ethernet Straight-Thru Cable (Gray)

Ordering Information

MVI56E-MCM, MVI56E-MCMXT Modbus Master/Slave Enhanced Communication Module
   
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

 

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe/Middle East/Africa
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

 

Related Information

ProSoft Configuration Builder

Home : Products : Support : Distributors : Services : News/Events : Contact : ProSoft Tested