ProSoft Technology, Inc.
Home > Products > for Rockwell Automation > Platform > ControlLogix > MVI56-AFC
Printable Page
 

Search | Clear


Gas & Liquid Flow Computer for ControlLogix

MVI56-AFC

The MVI56 Liquid & Gas Flow Computer Module is a ControlLogix backplane compatible module that allows ControlLogix processors to easily support flow applications performing measurement of hydrocarbon gases or liquids using AGA 3, 7, 8 and API MPMS Chapters 11 and 12 measurement standards.

The module calculates flow rates, accumulated volumes, accumulated mass and accumulated energy (heating value). The calculation results are transferred back to the Processor memory for use in the application ladder program or for transfer back to a SCADA host.

The MVI56-AFC Liquid and Gas Flow Computer product has been approved by Industry Canada Measurement for complying with Provisional Specifications and Procedures for the approval of Correction Devices and Linearization Functions Incorporated in Meters and Flow Computers.

Features and Benefits

Certified Custody Transfer

  • Gas measurement is accurate to the degree that it is Industry Canada Certified for custody transfer
  • Assurance to users the flow computer's values can be used in the transfer of ownership applications

Licensed Backplane Technology

  • Manufactured under license from Rockwell Automation
  • High-speed data transfer between MVI56 module and ControlLogix processor

Automatic Flow Computer

  • 16 meter runs with four streams per run
  • Monitor each meter run (flow rates, accumulator values and other calculation results). All alarm data is displayed on the screen
  • Download and view the archives and events
  • Audit scan shows the process input variables and calculation results as "snapshots," allowing verification of the calculations
  • Access Modbus Slave data (130,000 registers) and Virtual Modbus Slave data (20,000 registers)
  • Remap Modbus data to optimize the data polling

Includes AFC Manager Configuration Software

  • Configure, monitor, archive and view status from your desktop PC
  • Modbus Master port can send Modbus commands to connected devices
  • Precise configuration of meter types, streams, fluids and gases, component analysis

Backed by ProSoft Technology

  • 20-year history of delivering high-quality, reliable solutions designed with you in mind
  • Free, unlimited, worldwide Technical Support by phone anytime for pre-sale, set-up, or troubleshooting support help you get going sooner and stay running longer
  • Three-Year Warranty ensures reliability and protects against equipment failures

Configuration

The AFC Manager is an easy-to-use Windows 98/NT/2000/XP based configuration, reporting, and monitoring tool provided with the AFC modules. Project configurations may be uploaded, downloaded and saved to the PC under user selectable file names.

General Specifications

  • Single-slot - 1756 backplane compatible
  • Local or remote rack
  • The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
  • Ladder Logic is used for data transfer between module and processor.
  • Configuration data obtained through user-defined ladder. Sample ladder file included

AFC

The AFC module operates as a powerful flow computer module, augmenting the operation of the ControlLogix processor by providing a dedicated and accurate set of flow calculations. The calculated results are available to process monitoring and control applications through the ControlLogix processor memory or directly from the module Modbus port.

The module is configurable (see PSW-AFC), allowing each of the meter runs to be individually set up to meet the specific requirements of an application.

  • Gas analysis concentrations for any or all 21 components
  • Physical data for all meter runs including orifice and pipe diameters, selection of type of taps and tap location
  • Reference pressure, temperature and local atmospheric conditions
  • Default process and operating parameters including DP threshold for flow cutoff
  • Metric or imperial units
  • Number of meter channels: 16 differential (AGA3) or linear (AGA7) Gas; API MPMS Chapters 11 and 12 Liquids
  • Number of streams per meter channel: 4 streams
  • Product measurement: hydrocarbon gases and liquids

Functional Specifications

Data Exchange

Seamless data exchange between processor and Flow Computer with backplane compatibility

  • Supports 16 meter runs with 4 streams per meter run for the measurement of hydrocarbon gases and liquids using currently accepted industry measurement standards
  • Measurement standards supported: AGA 3, 7, 8 and API MPMS Chapters 11 and 12
  • Calculates flow rates, accumulated volumes, accumulated mass and accumulated energy
  • Calculation results are transferred back to the processor memory or to a SCADA host
  • Can be used in local or remote rack
  • User configurable allowing each of the meter runs to be individually set up to meet the specific requirements of an application

Configurable options

  • User selectable units for totalizers and flow rates on a per channel basis
  • Resettable and/or non-resettable totalizers for every meter channel
  • Process I/O: analog inputs (pressure, temperature, diff pressure) from analog modules and pulse inputs from pulse/frequency input modules in ControlLogix I/O rack
  • Calculation methods: AGA3-1992, AGA 7, AGA8-1992 (detail characterization method), API MPMS Chapters 11 and 12
  • Meter scan time under 1 second for all 16 channels
  • Data archiving: For each meter run, hourly for two days (48 records) and daily for one month (35 records) under default configuration, with optional extended archives up to 1440 hourly (60 days) and 1440 daily. Archive size and contents are fully configurable. All archived data is available in the onboard Modbus memory.
  • Event log report for all security sensitive configuration data (for example, orifice diameter) are date and time stamped and mapped to the local Modbus memory map. This data can be imported into any spreadsheet program and saved to disk or printed as hard copy

Modbus interface

  • Two Modbus slave ports allow for SCADA communication and the Modbus client can be configured for RTU or ASCII mode
  • Modbus table may be re-mapped for user assigned contiguous register polling from a SCADA master (up to 20,000 registers)
  • Additional Port can be configured as a Modbus Master port to poll data from a remote chromatograph device

Archiving

  • Supports data archiving and event logging
  • Data archiving feature provides 35 regular daily, 48 regular hourly archives or a total of 1,440 daily and hourly extended archives per meter.
  • Event logging feature provides storage up to 1999 events station-wide.

Hardware Specifications

Application Serial ports
(P1, P2)

 
 

Full hardware handshaking control, providing radio, modem, and multi-drop support

Software configurable communication parameter

Baud rate: 110 to 115,200 baud depending on protocol
Parity: None, Odd or Even
Data Bits: 5, 6, 7, or 8
Stop Bits: 1 or 2
RTS On/Off Delay: 0 to 65535 ms
RS-232 handshaking configurable

App Ports (P1, P2)

RJ45 (DB-9M with supplied cable)
RS-232, 485, and 422 (jumper selectable)
500V optical isolation from backplane

CFG Port

RJ45 (DB-9M with supplied cable)
RS-232 only

Shipped with unit

RJ45 to DB-9M adapter cable and 6-foot RS-232 configuration cable for the debug port

Specification

Description

Backplane Current Load

800 mA @ 5 V

Operating Temperature

0 to 60° C (32 to 140° F)

Storage Temperature

-40 to 85° C (-40 to 185° F)

Shock:

30g Operational
50g non-operational
Vibration: 5 g from 10 to 150 Hz

Relative Humidity

5 to 95% (non-condensing)

LED Indicators:

Module Status
Backplane Transfer Status
Application Status
Serial Activity

Ordering Information

MVI56-AFC Gas & Liquid Flow Computer for ControlLogix
   
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

 

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe/Middle East/Africa
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

AFC Version 2.05 Update Notice

If your module measures liquids, please read this notice before upgrading from version 2.04 (or earlier) to 2.05 (or later).

For compliance with new measurement standards, the AFC version 2.05 has introduced several new liquid product groups. In particular, the two non-refined liquid product groups of version 2.04, which covered the entire density range of crudes and NGLs, have each been split into two separate product groups, one for the higher density range of crudes and the other for the lower density range of NGLs. If your module has meter channels configured for either "Crude, NGL" or "Oil-water emulsion", you should decide before upgrading the firmware the new product group (light or heavy) to which each such channel should be assigned. This assignment will be performed during the upgrade process and will preserve all other configuration and historical records including accumulator values and archives, in contrast to changing a product group after the upgrade which resets the meter configuration and erases all historical records. Meter channels configured for "Gas" or "Refined products" are not affected.

AFC Manager exhibits the same behavior when converting a project between versions 2.04 (or earlier) and 2.05 (or later).

The criterion for assigning the new product group depends on the density units and the Default Reference Density, as detailed in the following tables:

Density Units = kg/m3

Version 2.04 Product Group

Default Reference Density

Version 2.05 Product Group

Crude, NGL

= 0 OR >= 610.0

Crude oils, JP4

Crude, NGL

> 0 AND < 610.0

NGLs, LPGs

Oil Water Emulsion

= 0 OR >= 610.0

Oil-water emulsion (Crd)

Oil Water Emulsion

> 0 AND < 610.0

Oil-water emulsion (NGL)

Density Units = Rd/60

Version 2.04 Product Group

Default Reference Density

Version 2.05 Product Group

Crude, NGL

= 0 OR >= 0.6100

Crude oils, JP4

Crude, NGL

> 0 AND < 0.6100

NGLs, LPGs

Oil Water Emulsion

= 0 OR >= 0.6100

Oil-water emulsion (Crd)

Oil Water Emulsion

> 0 AND < 0.6100

Oil-water emulsion (NGL)

Due to roundoff error of numeric conversions, a Relative Density very close to the cutoff value of 0.6100 may cause the module to assign the new product group opposite to the one that was intended. Before upgrading, change the Default Reference Density to a number significantly different from 0.6100, such as 0.6110 (to target Crude) or 0.6090 (to target NGLs). You may change it back to the correct value after the upgrade

Density Units = API Gravity

Version 2.04 Product Group

Default Reference Density

Version 2.05 Product Group

Crude, NGL

= 0 OR <= 100.0

Crude oils, JP4

Crude, NGL

> 0 AND > 100.0

NGLs, LPGs

Oil Water Emulsion

= 0 OR <= 100.0

Oil-water emulsion (Crd)

Oil Water Emulsion

> 0 AND > 100.0

Oil-water emulsion (NGL)

 

Image Gallery