ProSoft Technology, Inc.
Home > Products > Stand-alone Gateways > Serial > Modbus Master/Slave > Modbus Master/Slave to PROFIBUS DP Slave Communication Module
Printable Page
 

Search | Clear


Modbus Master/Slave to PROFIBUS DP Slave Communication Module

5105-MCM-PDPS

Product Description

The ProLinx family Modbus Master/Slave to PROFIBUS DP Slave communications module (5105-MCM-PDPS) creates a powerful connection between devices on a Modbus network and PROFIBUS DP Slave devices. The module is a stand-alone DIN rail-mounted protocol gateway that provides one confgurable serial port and one DB9F PDPS port.

The Modbus (MCM) protocol driver supports Master and Slave implementations of the protocol. All Modbus serial ports are individually configurable, providing a very powerful and flexible host or device interface solution.

The PROFIBUS DP Slave (PDPS) protocol interface supports the PROFIBUS V0 Slave implementation protocol, providing powerful data transfer capability between the ProLinx module and Siemens PLCs or other hosts. User configurable data mapping and DP port operation make the interface an easy to use and powerful data transfer tool.

Product Applications

The PROFIBUS DP slave interface enables Siemens PLCs or a similar host supporting the PROFIBUS DP protocol to exchange data with other protocols. As such, possible applications of the PDPS product exist in nearly every sector of industry.

Functional Specifications

Internal Database

The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.

The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.

Application Data Area

The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.

Status Data Area

This area is used to store error codes, counters, and port status information for each port.

Configuration Data Area

This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.

Modbus Protocol Specifications

The Modbus driver provides access to an internal database of 4000 registers (words), with extensive support provided for both the Master and the Slave implementations of the protocol. The serial port(s) on the gateway can be individually configured to support the Modbus protocol (Master or Slave, RTU or ASCII, Baud Rate, etc).

General Parameters - Modbus Protocol

Type

Specifications

Communication parameters

Baud Rate: 110 to 115K baud

Stop Bits: 1 or 2

Data Size: 7 or 8 bits

Parity: None, Even, Odd

RTS Timing delays: 0 to 65535 ms

Error Checking

RTU mode (binary) with CRC-16
ASCII mode with LRC error checking

Floating Point

Floating point data movement supported, including configurable support for Enron implementation

Function Codes

1 : Read Output Status

2 : Read Input Status

3 : Read Multiple Data Registers

4 : Read Input Registers

5 : Write Single Bit

6 : Write Single Data Register

15 : Write Multiple Bits

16 : Write Multiple Data Register

Modbus Master

Type

Specifications

Command List

Up to 100 command per master port, each fully configurable for function, slave address, register to/from addressing and word/bit count

Status Data

Error codes are provided on an individual command basis, as well as a slave status list is maintained per active Modbus Master port.

Polling of command list

Configurable polling of command list, including continuous and on change of data, and dynamically user or automatic enabled.

Modbus Slave

Type

Specifications

Node address

1 to 247 - software selectable

Status Data

Error codes, counters and port status available per configured slave port. Status data is all pre-mapped in the module

PROFIBUS DP Slave Specifications

The PROFIBUS DP Slave driver gives access to the ProLinx unit's internal database via 200 bytes of Input data and 200 bytes of Output data. These Input and Output data blocks are mapped by the user within the ProLinx module's data memory allowing the user maximum flexibility and data transfer with other protocols.

General Parameters

GSD File

PRLX05A5.GSD
Downloadable from ftp site

PROFIBUS Specifications

Communication parameters

Baud Rate: 9.6 kbit/s - 12 Mbit/s

Supported I/O length

200 bytes Input data
200 bytes Output data

Supported PROFIBUS DP features

PROFIBUS V0 Slave using Siemens SPC3 chipset
Freeze Mode
Sync Mode
Auto Baud Setting

Configurable Parameters

- PROFIBUS Node Address: 1 to 125
- Data byte swapping
- Action on loss of PROFIBUS connection
- Comm Fail Timeout Multiplier
- Status Data location in Internal Database

Status Data

Status data is available through the debug menu. The status information includes diagnostic data, input and output counters and module state.

Important Note: The slave node address is set to 126 by default in the module configuration file. The default node address must be changed to a valid address between 1-125 by the user for the slave to function on the PROFIBUS network.

Hardware Specifications

Power Supply 24 VDC nominal
  18-32 VDC allowed
  Positive, Negative, GND Terminals
  2.5 mm screwdriver blade

Current Load

500 mA max@ 32 VDC max
Operating Temperature -20 to 50 Deg C
  -4 to 122 Deg F
Storage Temperature -40 to 85 Deg C
  -40 to 185 Deg F
Relative Humidity 5-95% (w/o condensation)
Dimensions

Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD

LED Indicators

Power and Module Status

  Application Status
  Serial Port Activity LED
  Serial Activity and Error LED Status
Configuration Serial Port Mini-DIN
  RS-232 only
  No hardware handshaking
Ethernet Port 10Base-T Connector
  Link and Activity LED indicators
  Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991
  Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
Application Serial Ports Mini-DIN
  RS-232/422/485
  RS232 handshaking configurable
  RS422/485 screw termination included
Port Isolation 2500V Opto-Isolators
  500V Power Supply Isolation
Shipped with each unit Mini-DIN to DB-9M cables per serial port
  4 ft RS-232 configuration cable
  2.5mm screwdriver
  CD (docs and Configuration utility)
  RS-422/485 DB9 to Screw Terminal
  Adaptor (1 or 4, depending on ports)

PROFIBUS Connector

DB-9F Standard PROFIBUS connector

PROFIBUS LED Indicators

Active - Green

 

Error - Red

Click here for dimensions diagram

Certifications

The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class 1, Div 2

PNO Certified - PROFIBUS Test Center


Ordering Information

5105-MCM-PDPS

Modbus Master/Slave to PROFIBUS DP Slave

To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

Home : Products : Support : Distributors : Services : News/Events : Contact Us : ProSoft Tested