PDPS Protocol Specification
The PROFIBUS DP Slave protocol driver supports the PROFIBUS V0 Slave implementation, providing powerful data transfer capability between the ProLinx module and Siemens PLCs or other hosts. User configurable data mapping and DP port operation make the interface an easy to use and powerful data transfer tool.
The PROFIBUS DP Slave driver gives access to the ProLinx unit's internal database via 244 bytes of Input data and 244 bytes of Output data (maximum 400 bytes total). These Input and Output data blocks are mapped by the user within the ProLinx module's data memory allowing the user maximum flexibility and data transfer with other protocols.
General Parameters
GSD File
PRLX05A5.GSD
Downloadable from ProSoft Technology web site
PROFIBUS Specifications
Communication parameters
Baud Rate: 9.6 kbps to 12 Mbps
Supported I/O length
244 bytes Input data
244 bytes Output data
400 bytes total
Supported PROFIBUS DP features
PROFIBUS V0 Slave using Siemens SPC3 chipset
Freeze Mode
Sync Mode
Auto Baud Setting
Configurable Parameters
PROFIBUS Node Address: 1 to 125
Data byte swapping
Action on loss of PROFIBUS connection
Comm Fail Timeout Multiplier
Status Data location in Internal Database