PROFIBUS DP-V1 Master Communication Module
MVI69-PDPMV1
The PROFIBUS DP-V1 Master module is a powerful communication interface for CompactLogix I/O compatible processors. The module incorporates proprietary backplane technology that enables powerful data exchange with CompactLogix I/O compatible processors.
Features and Benefits
The module supports complete Master specifications according to IEC 61158. Acyclic parameter data can be transferred with Class 1 or Class 2 DP-V1 services, allowing processors to easily communicate with slave devices supporting PROFIBUS DP-V0 or DP-V1 protocol.
The module acts as an input/output module between the PROFIBUS network and the CompactLogix or MicroLogix processors. Data transfer from the processor is asynchronous with the I/O data transfer on the PROFIBUS network. Databases are user-defined and stored in the module to hold the data required by the protocol.
Applications
With the growing usage of the PROFIBUS DP-V1 protocol in the industrial marketplace, this product has a wide variety of application uses. Industries that use this technology include:
- Power and distribution applications
- Petrochemical
- Water and Gas Applications
- SCADA and DCS applications
General Specifications
- Single-slot, 1769 backplane compatible
- The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
- Ladder Logic is used for data transfer between module and processor. Sample ladder file included.
- Configuration data obtained from ProSoft Configuration Builder Software, which defines the PROFIBUS network, and then downloads the configuration to the module using the serial port of the PC
- Supports all CompactLogix processors: L20/L30/L31/L32/L35 and L43 (L43 & L45 supported with RSLogix 5000 v16)
- Also supports MicroLogix 1500 LRP
Hardware Specifications
|
Specification
|
Description
|
|
Dimensions
|
Standard 1769 Single-slot module
|
|
Current Load
|
800 mA max@ 5 VDC
Power supply distance rating of 2 (first or second slot on the 1769 bus)
|
|
Operating Temp.
|
0 to 60° C (32 to 140° F)
|
|
Storage Temp.
|
-40 to 85° C (-40 to 185° F)
|
|
Relative Humidity
|
5% to 95% (non-condensing)
|
|
LED Indicators
|
Power and Module Status
Application Status
Serial Port Activity
Serial Activity and Error Status
|
|
CFG Port (CFG)
|
RJ45 (DB-9M with supplied cable)
RS-232 only
No hardware handshaking
|
|
Shipped with Unit
|
RJ45 to DB-9M cables for each port
6-foot RS-232 configuration Cable
|
Functional Specifications
The inRAx PDPMV1 PROFIBUS Master module acts as a PROFIBUS network scanner, transferring Input and Output data between PROFIBUS devices and processor data memory over the backplane.
- Master Busview configuration interface via included ProSoft Configuration Builder software (see PSW-PCB)
- Project-unique GSD file import library
- Monitoring and Modification of process data and DP-V1 acyclic data
- Multi-drop on a PROFIBUS DP-V1 network drop with other compatible devices
- Ability to be used with a third-party link coupler (not supplied) as a PROFIBUS Master with PROFIBUS PA slaves on the network
- Automatic project documentation
- Automatic Bus Parameter calculation
- Online slave diagnostics
- Supports all standardized baud rates, up to 12 Mbps
- Supports extended diagnostic data (DP-V1 devices only)
- Auto baud detection at all valid PROFIBUS DP-V1 rates
- Multiple modules can be placed in a single rack
- CRC checksum determination of slave configuration consistency to processor
- Master Status LED Indicators for Operations, Network Drop Communication, Master Token-Hold
- FDT/DTM PROFIBUS master transport communication DTM software included (see PSW-CDTM-PDPM)
PROFIBUS Master Specifications
- Up to 125 Slaves can be connected with a repeater
- Up to 1536 cyclic bytes input and 1536 bytes output data
- Supports Extended Diagnostic Data
- RS-485 optically isolated PROFIBUS Interface with on board DC-DC converter
- Acyclic communications (DP-V1 device only), Read and Write
- Alarm Handling (DP-V1 devices only)
- Supports Sync and Freeze commands
- Supports PROFIdrive 3.1 compliant parameter read and write operations
- Supports Multicast and Broadcast telegrams (DP-V1 devices only)
PROFIBUS Master Port
- DB-9F Optically Isolated RS-485
- Ready, Run, Error and Token LED Indicators
- PROFIBUS DP-V1 RS-485 interface with a 9-pin D shell female connector and isolated opto-couplers
Ordering Information
| MVI69-PDPMV1 |
PROFIBUS DP-V1 Master Communication Module |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.
Sales and Support:
|