6104-WA-PDPM
6105-WA-PDPS

Product Description

The ProLinx High Speed Wireless PROFIBUS Solution creates a powerful wireless connection between Master and/or Slave devices on a PROFIBUS DP network. The modules are stand-alone DIN-rail mounted wireless protocol gateways providing an efficient and powerful over-the-air wireless protocol and a wired PROFIBUS Master or Slave interface port.

On the field device side, the PROFIBUS DP master protocol driver is configured as a Class 1 PROFIBUS DP Master to interface with and control your PROFIBUS DP slave devices. It provides access to both standard and extended diagnostic information and provides freeze/sync capability. Configuration of the PROFIBUS network is accomplished using the ProLinx SyCon Configuration software.

On the controller side, the PROFIBUS DP driver is configured to interface with your PDP master. It provides 200 bytes of read and 200 bytes write cyclic data. The module also provides common and extended diagnostic information and other important module status information.

The overall PROFIBUS network node capacity can be calculated based on the available number of cyclic bytes available in the PDPS slave unit. The slave gateway becomes hard wired to an existing PROFIBUS network controlled by a third party master. The available number of PDPS slave cyclic data is 244 bytes Input and 244 bytes Output data (maximum 400 I/O bytes). For example, if each remote PROFIBUS third party slave connected to the PDPM master gateway consumed 6 Input/Output bytes each a total of 40 slaves can be configured. The remote wireless PDPM master allows up to 512 bytes input and 512 bytes output cyclic data. Multiple PDPS slave units could be used to accommodate larger PROFIBUS networks.

The PROFIBUS DP Master (PDPM) protocol driver supports Master implementations of the protocol on either a Mono-Master or Multi-Master network.

The PROFIBUS DP Slave (PDPS) protocol interface supports the PROFIBUS V0 Slave implementation protocol, providing powerful data transfer capability between the ProLinx module and Siemens PLCs or other hosts. User configurable data mapping and DP port operation make the interface an easy to use and powerful data transfer tool.

Product Applications

The ProLinx 6000 series of wireless products will provide users more flexibility than ever before seen in wireless solutions. Users will be able to connect various field devices using different networks or protocols and share data between these devices over-the-air. This is accomplished by exchanging shared common database information wirelessly with ProSoft Technology's efficient but powerful wireless protocol, PWP. ProLinx is the first product line to benefit from this technology. With the growing usage of the PROFIBUS DP protocol in the industrial marketplace, this product has a wide variety of application uses. Industries that use this technology include:
  • Power and distribution applications
  • Petrochemical
  • Water and Gas Applications
  • SCADA and DCS applications
  • Manufacturing and Factory Automation Applications

Functional Specifications

Internal Database

The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.

The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.

Application Data Area

The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.

Status Data Area

This area is used to store error codes, counters, and port status information for each port.

Configuration Data Area

This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.

PROFIBUS DP Master Protocol Specifications

The PROFIBUS Master protocol driver exists as a single port implementation. The driver can be configured as a Class 1 PROFIBUS Master to interface with other PROFIBUS slave devices. The unit is also used for configuration of the nodes on the PROFIBUS network. It provides access to both standard as well as extended diagnostic information. The PROFIBUS master port can be used to continuously interface with PROFIBUS slave devices over a serial communication interface (RS-485).

General Parameters

Communication parameters

Baud Rate: 9.6 kbit/s - 12 Mbit/s

Slaves

Up to 125 Slaves

Data I/O

Up to 512 cyclic bytes (256 words) input and 512 bytes (256 words) output data

Command List

Read Diag

Global Cmd

Read Cntrs

Reset Cntrs

Node address

0 to 125 (software selectable)

Status Data

Error codes, counters and port status available per configured slave on the network.

PDPMV1 Compatibility Notice to PDPM Users

The PDPMV1 product is not backward compatible with the PDPM product due to new enhancements and command structure. The PDPMV1 DPV1 master gateway product provides enhanced features to the PDPM DPV0 gateway product as follows:

  1. Increased Cyclic IO. The DPPMV1 provides 768 Words of Input and 768 Words of Output.
  2. ProSoft Configuration Builder (PCB) complete support. The PCB provides module level configuration and integrated PROFIBUS master network configuration support.
  3. The PDPMV1 master supports DPV1 Class 1 or Class 2 DPV1 features such as: Acyclic communication with slaves for parameterization and other slave settings, Alarm handling, extended diagnostics.

PROFIBUS DP Slave Specifications

The PROFIBUS DP Slave driver gives access to the ProLinx unit's internal database via 200 bytes of Input data and 200 bytes of Output data. These Input and Output data blocks are mapped by the user within the ProLinx module's data memory allowing the user maximum flexibility and data transfer with other protocols.

General Parameters

GSD File

PRLX05A5.GSD
Downloadable from ftp site

PROFIBUS Specifications

Communication parameters

Baud Rate: 9.6 kbit/s - 12 Mbit/s

Supported I/O length

200 bytes Input data
200 bytes Output data

Supported PROFIBUS DP features

PROFIBUS V0 Slave using Siemens SPC3 chipset
Freeze Mode
Sync Mode
Auto Baud Setting

Configurable Parameters

- PROFIBUS Node Address: 1 to 125
- Data byte swapping
- Action on loss of PROFIBUS connection
- Comm Fail Timeout Multiplier
- Status Data location in Internal Database

Status Data

Status data is available through the debug menu. The status information includes diagnostic data, input and output counters and module state.

Important Note: The slave node address is set to 126 by default in the module configuration file. The default node address must be changed to a valid address between 1-125 by the user for the slave to function on the PROFIBUS network.

Hardware Specifications

Power Supply 24 VDC nominal
  18-32 VDC allowed
  Positive, Negative, GND Terminals
  2.5 mm screwdriver blade

Current Load

500 mA max@ 32 VDC max
Operating Temperature -20 to 50°C
  -4 to 122°F
Storage Temperature -40 to 85°C
  -40 to 185°F
Relative Humidity 5% to 95% (non-condensing)
Dimensions

Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD

LED Indicators

Power and Module Status

  Application Status
  Serial Port Activity LED
  Serial Activity and Error LED Status
  RF Link Status
  RF Data Status
Configuration Serial Port DB-9M RS-232 only
  No hardware handshaking
Ethernet Port
(Ethernet protocol gateways only)
10Base-T half duplex RJ45 Connector
  Link and Activity LED indicators
  Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991
  Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
Application Serial Ports (Serial protocol gateways only) RS-232/422/485
  RS232 handshaking configurable
  RS-422/485 DB-9 to Screw Terminal Adaptor
  Note: The number of serial application ports depends on the module type, and the combination of protocols.
Serial Port Isolation 2500V RMS port signal isolation per UL 1577
  3000V DC min. isolation port to ground and port to logic
Shipped with each unit Mini-DIN to DB-9M serial cables
  4 ft RS-232 configuration cable
  2.5mm screwdriver
  CD (docs and Configuration utility)
  RS-422/485 DB-9 to Screw Terminal Adaptor for each serial application port (serial protocols only)

PROFIBUS Connector

DB-9F Standard PROFIBUS connector

PROFIBUS LED Indicators

Tkn - Green

 

Err - Red

 

Rdy - Green

 

Run - Green

PROFIBUS Connector

DB-9F Standard PROFIBUS connector

PROFIBUS LED Indicators

Active - Green

 

Error - Red

Click here for dimensions diagram

Certifications

The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class I, Div 2

PNO Certified - PROFIBUS Test Center


Ordering Information

6104-WA-PDPM
6105-WA-PDPS

Wireless PROFIBUS DP Master Gateway
Wireless PROFIBUS DP Slave Gateway

To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe/Middle East/Africa
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

Image Gallery



Home : Products : Support : Distributors : Services : News/Events : Contact : ProSoft Tested