Home » Categories » Multiple Categories

Why am I getting: Download was successful but Module failed to reboot in 60 seconds

This error is indicative of a backplane issue between the prosoft card and the compact logix PLC.

With the MVI69E and MVI69L modbus modules, all of the configuration is stored on the PLC itself, not on the Prosoft card. This means that, unlike with some of our other modules, it is possible to perform a download while our card does not have a backplane connection to the PLC and have the download be successful. However, in order to actually get the new configuration into the module, a reboot notice must then be sent from the PLC to the card, as the card will load whatever configuration the PLC has on boot up. If we don't have a backplane connection, this will result in the "download was sucessful but module failed to reboot" error.

Common causes include:
1) Your Compact Logix is not in run mode.
2) Your Prosoft card's Add-On Instruction is either not installed, or the rung it is on is not being completed, scheduled, or jumped to.
3) You have not yet installed the right end cap.
4) There are more then 3 cards separating the Prosoft card and the nearest power supply.
5) Your Prosoft card's Add-On Instruction block is not aiming at the correct slot (for example, it's connection input is set to local:1:I:Data when we the card is located in slot 2).
6) You have a destructive rung of ladder (such as a copy, move, etc.) besides Prosoft's AOI putting data into the card's Local Controller Tag (for example, you are attempting to copy data directly to the cards associated local tag instead of to its WriteData tag array created by the Add-On Instruction Rung).

If none of these issues appear to be the cause of the error, please contact you're Tech Support department for your region for further assistance: http://www.prosoft-technology.com/SERVICES-SUPPORT/Customer-Support
Custom Fields
    Attachments (0) Attachments
    There are no attachments for this article.
    Comments Comments
    There are no comments for this article. Be the first to post a comment.
    Related Articles RSS Feed
    Which of your products support RS-485 serial protocols?
    Viewed 1 times since Wed, Feb 6, 2008
    What causes a conditional command to be issued?
    Viewed 1 times since Tue, Nov 28, 2006
    Which ProSoft products can communicate with a Honeywell DCS System?
    Viewed 1 times since Tue, Jan 22, 2008
    What does a -36 modbus error code indicate?
    Viewed 1 times since Thu, Aug 20, 2015
    How do I fix the Arithmetic Overflow Error
    Viewed 1 times since Tue, Jun 16, 2015
    What is Enron-Daniels mode?
    Viewed 1 times since Thu, May 5, 2016
    Using CIP Connect with the Lite (free) Version of RSLinx Classic
    Viewed 1 times since Mon, Jun 22, 2015
    How can I configure the module to store and initialize input values on reset or powerup?
    Viewed 1 times since Tue, Nov 28, 2006