IEC60870-5-101 Master Communications Module
MVI71-101M
The MVI71 IEC 60870-5-101 Master Communication Module allows Rockwell Automation PLC processors to interface easily with IEC 60870-5-101 slave (controlled unit) devices.
Features and Benefits
The MVI71-101M module interfaces up to 32 serial communication devices with the Rockwell Automation PLC processor. Two communication ports on the module act as controlling devices (masters) to interface with controlled devices on their own networks. Each port is individually configurable and can be set for balanced or unbalanced mode. Data is exchanged between the serial network and the Rockwell Automation processor using the internal database contained in the module and direct control by the controller's ladder logic.
General Specifications
- Single Slot - 1771 backplane compatible
- The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
- Ladder Logic is used for data transfer between module and processor. Sample ladder file included.
- Configuration data obtained from configuration text file downloaded to module. Sample configuration file included.
The MVI71-101M module is the ideal solution for many applications where IEC protocol connectivity must be added to a PLC system. The IEC solution is designed to address the expanding interest in the IEC protocol and the use of IEC compatible devices in industrial applications such as those in the water/wastewater power and oil & gas industries.
Compatible devices include relays, breakers, sub-station Communication Modules and other serial communication devices.
Functional Specifications
- Built in accordance to the approved international specification
- Two independent master ports completely user configurable
- Support for balanced and unbalanced mode
- Up to 32 sessions
- Up to five sectors (separate databases) for each session
- Individual database definition for each sector
- 1000 commands to control stations
- PLC processor can issue control commands directly to the module or a controlled device (10 at each scan)
- Pass-through of event messages from controlled device to processor for logging of time-tagged events
- Operation via simple ladder logic
- PLC processor can synchronize the module clock
- Supports clock synchronization from/to the PLC
- Receives events from the slave and sends them to the PLC processor
- Supports monitored data
- Single-point
- Double-point
- Step-point
- Measured-point
- Bitstring 32-bit
- Integrated total point
- Class 1 and Class 2 delay parameter in the configuration file
- Complete set up and monitoring of module through RSLogix 5 software and user constructed configuration file (IEC101M.CFG)
- All data related to the module is contained in user data files to ease in the monitoring and interfacing with the module
|
Application Serial ports (P1, P2)
|
|
|
|
Full hardware handshaking control, providing radio, modem, and multi-drop support
|
|
Software configurable communication parameter
|
Baud rate: 110 to 38,400 baud depending on protocol
Parity: None, Odd or Even
Data Bits: 5, 6, 7, or 8
Stop Bits: 1 or 2
RTS On/Off Delay: 0 to 65535 ms RS-232 handshaking configurable
|
|
App Ports (P1, P2)
|
RJ45 (DB-9M with supplied cable)
RS-232, 485, and 422 (jumper selectable) 500V optical isolation from backplane
|
|
CFG Port
|
RJ45 (DB-9M with supplied cable) RS-232 only
|
|
Shipped with unit
|
RJ45 to DB-9M adapter cable and 6-foot RS-232 configuration cable for the debug port
|
Hardware Specifications
|
Form Factor
|
Single Slot - 1771 chassis compatible
|
|
|
BTR/BTW data transfer
|
|
|
Local or remote rack
|
|
Backplane Current Load
|
800 mA @ 5V
|
|
Operating Temperature
|
0 to 60 deg C (32 to 140 deg F)
|
|
Storage Temperature
|
-40 to 85 deg C (-40 to 185 deg F)
|
|
Shock
|
30g operational
|
|
|
50g non-operational
|
|
Vibration
|
5g from 10 - 150 Hz
|
|
Relative Humidity
|
5 - 95% (w/o condensation)
|
|
LED Indicators
|
Module status
|
|
|
Backplane transfer status
|
|
|
Application status
|
|
|
Serial Activity and error LED status
|
|
Configuration Port (CFG)
|
DB-9M PC compatible
|
|
|
RS-232
|
|
|
Hardware handshaking
|
|
Application Serial Port (P2, P3)
|
(2) RJ45 RS-232/422/485
|
|
Shipped with unit
|
RJ45 to DB-9M cables for each port
|
|
|
6-foot RS-232 configuration cable
|
Ordering Information
| MVI71-101M |
IEC60870-5-101 Master Communications Module |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.
Sales and Support:
|