Modbus TCP/IP Client/Server Communication Module

MVI46-MNET

The MVI46 Modbus TCP/IP Communication Module is designed to allow SLC processors to interface easily with other Modbus TCP/IP protocol-compatible devices using client and server functionality.

Compatible devices include not only Modicon processors (which support the Modbus TCP/IP protocol) but also a wide assortment of other clients and server devices.

Features and Benefits

The MVI46-MNET module is a single slot solution that provides a powerful connection between Rockwell Automation's SLC processor and Modbus TCP/IP network applications.

The TCP/IP Modbus network applications include those networks hosted by Modicon Quantum processors, networks controlled by operator interface software packages, and the growing number of manufactured devices that support this protocol. The module acts as an input/output module between the Modbus TCP/IP network and the Rockwell Automation backplane. The data transfer from the processor is asynchronous from the actions on the Modbus TCP/IP network. A 5000-word register space in the module exchanges data between the processor and the Modbus TCP/IP network.

  • Support for the storage and transfer of up to 5000 registers to/from the SLC processor using M0/M1 data file transfer
  • User-definable module memory usage
  • 10/100 MB Ethernet compatible interface
  • Configurable parameters for the client and server applications and floating point support

General Specifications

  • Single Slot - 1746 backplane compatible (Local or extended I/O rack only. Remote rack not supported)
  • The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module using M0/M1 files
  • Ladder Logic is used for data transfer between module and processor. Sample ladder file included
  • Configuration data obtained from configuration text file downloaded to module. Sample configuration file included

Applications

With the growing trend of Ethernet technology in the industrial marketplace, this product has a wide variety of application uses.

  • Food processing
  • Petrochemical
  • Pulp and paper
  • Automobile manufacturing
  • Water and Wastewater
  • Oil and Gas
  • Power and Electric

Functional Specifications

General Protocol specifications

Type

Specifications

Floating Point Data

Floating point data movement supported, including configurable support for Enron and Daniels floating poiont implementations

Supported Function Codes

Function Code Descriptions

FC 1

Read Coil Status (Bits)

FC 2

Read Input Status (Bits)

FC 3

Read Input Registers

FC 4

Read Holding Registers

FC 5

Write Single Coil (Bit)

FC 6

Write Single Holding Register

FC 15

Write Multiple Coils (Bits)

FC 16

Write Multiple Holding Registers

Modbus Server Protocol Specifications

The server driver supports up to ten (10) connections to Modbus TCP/IP Clients using Service Port 502 with the standard MBAP protocol, and up to an additional ten (10) Clients using an other service port for Encapsulated Modbus protocol.

Modbus TCP/IP Client

The Client driver supports the active reading and writing of data with Modbus TCP/IP compatible devices.
One Client with up to 100 total commands. (Allows connections to as many as 100 Servers)

Hardware Specifications

Ethernet and CFG Ports

 

Ethernet Port

RJ45 connection
10/100 Mbit Ethernet support (auto-sensing)
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 seconds, applied as specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration

CFG Port

RJ45 (DB-9M with supplied cable)
RS-232 only

Shipped with unit

RJ45 to DB-9M adapter cable and 6-foot RS-232 configuration cable for debug port

Specification

Description

Backplane Current Load

800 ma @ 5V (from backplane)

Operating Temperature

0 to 60° C (32 to 140° F)

Storage Temperature

-40 to 85° C (-40 to 185° F)

Shock

30g operational, 50g non-operational

Relative Humidity

5 to 95% (non-condensing)

Vibration

5g from 10 to 50 Hz

Processor

Compatible with Rockwell Automation SLC 5/02 M0/M1 capable processors or newer.

LED indicators

Module status, Backplane transfer status, Application status, Serial activity and error LED status

Ordering Information

MVI46-MNET Modbus TCP/IP Client/Server Communication Module
   
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

 

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe/Middle East/Africa
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

 

Related Information

ProSoft Configuration Builder

ProSoft Technology, Inc. Copyright © 2003 - 2010

Return to Non-Printable Page