Modbus Master/Slave to PROFIBUS DP Slave Communication Module
5105-MCM-PDPS
Product Description
The ProLinx family Modbus Master/Slave to PROFIBUS DP Slave communications module (5105-MCM-PDPS) creates a powerful connection between devices on a Modbus network and a PROFIBUS DP Master device. The module is a stand-alone DIN rail-mounted protocol gateway that provides one confgurable serial port and one DB9F PDPS port.
The Modbus (MCM) protocol driver supports Master and Slave implementations of the protocol. All Modbus serial ports are individually configurable, providing a very powerful and flexible host or device interface solution.
The PROFIBUS DP Slave (PDPS) protocol interface supports the PROFIBUS V0 Slave implementation protocol, providing powerful data transfer capability between the ProLinx module and Siemens PLCs or other hosts. User configurable data mapping and DP port operation make the interface an easy to use and powerful data transfer tool.
Product Applications
The PROFIBUS DP slave interface enables Siemens PLCs or a similar host supporting the PROFIBUS DP protocol to exchange data with other protocols. As such, possible applications of the PDPS product exist in nearly every sector of industry.
Functional Specifications
Internal Database
The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.
The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.
Application Data Area
The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.
Status Data Area
This area is used to store error codes, counters, and port status information for each port.
Configuration Data Area
This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.
Modbus Protocol Specifications
The Modbus driver provides access to an internal database of 4000 registers (words), with extensive support provided for both the Master and the Slave implementations of the protocol. The serial port(s) on the gateway can be individually configured to support the Modbus protocol (Master or Slave, RTU or ASCII, Baud Rate, etc).
|
General Parameters - Modbus Protocol
|
|
Type
|
Specifications
|
|
Communication parameters
|
Baud Rate: 110 to 115K baud
Stop Bits: 1 or 2
Data Size: 7 or 8 bits
Parity: None, Even, Odd
RTS Timing delays: 0 to 65535 ms
|
|
Error Checking
|
RTU mode (binary) with CRC-16 ASCII mode with LRC error checking
|
|
Floating Point
|
Floating point data movement supported, including configurable support for Enron implementation
|
|
Function Codes
|
1 : Read Output Status
2 : Read Input Status
3 : Read Multiple Data Registers
4 : Read Input Registers
5 : Write Single Bit
6 : Write Single Data Register
15 : Write Multiple Bits
16 : Write Multiple Data Register
|
|
Modbus Master
|
|
Type
|
Specifications
|
|
Command List
|
Up to 100 command per master port, each fully configurable for function, slave address, register to/from addressing and word/bit count
|
|
Status Data
|
Error codes are provided on an individual command basis, as well as a slave status list is maintained per active Modbus Master port.
|
|
Polling of command list
|
Configurable polling of command list, including continuous and on change of data, and dynamically user or automatic enabled.
|
|
Modbus Slave
|
|
Type
|
Specifications
|
|
Node address
|
1 to 247 - software selectable
|
|
Status Data
|
Error codes, counters and port status available per configured slave port. Status data is all pre-mapped in the module
|
PROFIBUS DP Slave Specifications
The PROFIBUS DP Slave driver gives access to the ProLinx unit's internal database via 200 bytes of Input data and 200 bytes of Output data. These Input and Output data blocks are mapped by the user within the ProLinx module's data memory allowing the user maximum flexibility and data transfer with other protocols.
|
General Parameters
|
|
GSD File
|
PRLX05A5.GSD Downloadable from ftp site
|
|
PROFIBUS Specifications
|
|
Communication parameters
|
Baud Rate: 9.6 kbit/s - 12 Mbit/s
|
|
Supported I/O length
|
200 bytes Input data 200 bytes Output data
|
|
Supported PROFIBUS DP features
|
PROFIBUS V0 Slave using Siemens SPC3 chipset
Freeze Mode
Sync Mode Auto Baud Setting
|
|
Configurable Parameters
|
- PROFIBUS Node Address: 1 to 125
- Data byte swapping
- Action on loss of PROFIBUS connection
- Comm Fail Timeout Multiplier - Status Data location in Internal Database
|
|
Status Data
|
Status data is available through the debug menu. The status information includes diagnostic data, input and output counters and module state.
|
Important Note: The slave node address is set to 126 by default in the module configuration file. The default node address must be changed to a valid address between 1-125 by the user for the slave to function on the PROFIBUS network.
Hardware Specifications
| Power Supply |
24 VDC nominal |
| |
18-32 VDC allowed |
| |
Positive, Negative, GND Terminals |
| |
2.5 mm screwdriver blade |
Current Load
|
500 mA max@ 32 VDC max |
| Operating Temperature |
-20 to 50 Deg C |
| |
-4 to 122 Deg F |
|
Storage Temperature |
-40 to 85 Deg C |
| |
-40 to 185 Deg F |
| Relative Humidity |
5-95% (w/o condensation) |
| Dimensions |
Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD |
|
LED Indicators |
Power and Module Status |
| |
Application Status |
| |
Serial Port Activity LED |
| |
Serial Activity and Error LED Status |
| Configuration Serial Port |
Mini-DIN |
| |
RS-232 only |
| |
No hardware handshaking |
|
Ethernet Port |
10Base-T Connector |
| |
Link and Activity LED indicators |
| |
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 |
| |
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration |
|
Application Serial Ports |
Mini-DIN |
| |
RS-232/422/485 |
| |
RS232 handshaking configurable |
| |
RS422/485 screw termination included |
|
Port Isolation |
2500V Opto-Isolators |
| |
500V Power Supply Isolation |
|
Shipped with each unit |
Mini-DIN to DB-9M cables per serial port |
| |
4 ft RS-232 configuration cable |
| |
2.5mm screwdriver |
| |
CD (docs and Configuration utility) |
| |
RS-422/485 DB9 to Screw Terminal |
| |
Adaptor (1 or 4, depending on ports) |
|
PROFIBUS Connector
|
DB-9F Standard PROFIBUS connector
|
|
PROFIBUS LED Indicators
|
Active - Green
|
|
|
Error - Red
|
Click here for dimensions diagram Certifications
The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class 1, Div 2
PNO Certified - PROFIBUS Test Center
Ordering Information
|
5105-MCM-PDPS
|
Modbus Master/Slave to PROFIBUS DP Slave
|
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.