Modbus TCP/IP to PROFIBUS DP Slave Communication Module
5205-MNET-PDPS
Product Description
The ProLinx family Modbus TCP/IP to PROFIBUS DP Slave communications module (5205-MNET-PDPS) creates a powerful connection between devices on a Modbus TCP/IP network and a PROFIBUS DP Master device. The module is a stand-alone DIN-rail mounted protocol gateway that provides a single Ethernet port and a single DB9F PROFIBUS port.
The Modbus TCP/IP (MNET) driver can be used to interface many different protocols into the Schneider Electric Quantum family of processors as well other software solutions supporting the protocol. The MNET driver supports Client connections as well as Server connections.
The PROFIBUS DP Slave (PDPS) protocol interface supports the PROFIBUS V0 Slave implementation protocol, providing powerful data transfer capability between the ProLinx module and Siemens PLCs or other hosts. User configurable data mapping and DP port operation make the interface an easy to use and powerful data transfer tool.
Product Applications
The MNET-PDPS modules are the ideal solution for the many applications where Modbus TCP/IP connectivity can be used to integrate a PROFIBUS DP Slave device into a system.
The Modbus TCP/IP gateway is a powerful module designed with both Client and Server support, enabling easy connection to other Modbus TCP/IP devices (Modicon processors and many others). In combination with the PROFIBUS DP device support, the module provides a very powerful interface to the many Modbus TCP/IP devices which are in use in the industrial marketplace today. Applications for the module are found in most industries, especially the Manufacturing, Oil and Gas, Electrical Power and Food Processing.
Functional Specifications
Internal Database
The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.
The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.
Application Data Area
The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.
Status Data Area
This area is used to store error codes, counters, and port status information for each port.
Configuration File
This file contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, the module.
Modbus TCP/IP Protocol Specifications
The Ethernet driver interfaces with a common internal database in the module. This permits the sharing of data across many different protocols and networks.
Modbus TCP/IP Port Specifications
Server
The MNET module supports server functionality using the reserved Modbus TCP/IP service port 502, as well as service port 2000 to support the TCP/IP encapsulated Modbus protocol that is supported by several HMI manufacturers. Services supported in the module permit client applications (i.e., HMI software packages, Quantum processors, etc.) to read from and write to the module's database.
Data in the module's internal database is accessible for read and write operations by any node on the network supporting the MBAP (service port 502) or MNET (service ports 2000/2001) TCP/IP protocols.
There is no configuration of the MNET module required to implement Server functionality other than setting up the network and database parameters in the user configuration file.
|
Modbus TCP/IP Server
|
|
Type
|
Specification
|
|
General
|
The server driver supports connections to Modbus TCP/IP clients supporting Service Port 502 using the standard MBAP protocol, and clients supporting Modbus on Service Port 2000. - Supports up to five (5) independent server connections for Service Port 502
- Supports up to five (5) independent server connections for Service Port 2000
|
|
Configurable Parameters
|
Module IP Address Modbus address offsetting
|
|
Modbus Commands supported
|
1 : Read Output Status
2 : Read Input Status
3 : Read Multiple Data Registers
4 : Read Input Registers
5 : Write Single Bit
6 : Write Single Data Register
15 : Write Multiple Bits 16 : Write Multiple Data Register
|
Client
The module supports a client connection on the TCP/IP network to interface with processors (and other server based devices) using a user constructed command list of up to 100 entries.
|
Modbus TCP/IP Client
|
|
Type
|
Specification
|
|
General
|
The client driver supports the active reading and writing of data with Modbus TCP/IP compatible devices.
- One client connection available (connect up to 100 servers/devices with 100 commands)
|
|
Configurable parameters
|
Number of active commands (Up to 100 for client)
Min Command Delay
Response Timeout
Retry Count Command Error Pointer
|
|
Modbus Commands supported
|
1 : Read Output Status
2 : Read Input Status
3 : Read Multiple Data Registers
4 : Read Input Registers
5 : Write Single Bit
6 : Write Single Data Register
15 : Write Multiple Bits 16 : Write Multiple Data Register
|
|
Command List
|
Up to 100 commands on the Client port, each fully configurable for function, Server IP address, Service Port, register to/from addressing and word/bit count
|
|
Status Data
|
Error codes available on an individual command basis.
|
|
Polling of command list
|
User configurable polling of commands, including disabled, continuous and on change of data (write only)
|
PROFIBUS DP Slave Specifications
The PROFIBUS DP Slave driver gives access to the ProLinx unit's internal database via 200 bytes of Input data and 200 bytes of Output data. These Input and Output data blocks are mapped by the user within the ProLinx module's data memory allowing the user maximum flexibility and data transfer with other protocols.
|
General Parameters
|
|
GSD File
|
PRLX05A5.GSD Downloadable from ftp site
|
|
PROFIBUS Specifications
|
|
Communication parameters
|
Baud Rate: 9.6 kbit/s - 12 Mbit/s
|
|
Supported I/O length
|
200 bytes Input data 200 bytes Output data
|
|
Supported PROFIBUS DP features
|
PROFIBUS V0 Slave using Siemens SPC3 chipset
Freeze Mode
Sync Mode Auto Baud Setting
|
|
Configurable Parameters
|
- PROFIBUS Node Address: 1 to 125
- Data byte swapping
- Action on loss of PROFIBUS connection
- Comm Fail Timeout Multiplier - Status Data location in Internal Database
|
|
Status Data
|
Status data is available through the debug menu. The status information includes diagnostic data, input and output counters and module state.
|
Important Note: The slave node address is set to 126 by default in the module configuration file. The default node address must be changed to a valid address between 1-125 by the user for the slave to function on the PROFIBUS network.
Hardware Specifications
| Power Supply |
24 VDC nominal |
| |
18-32 VDC allowed |
| |
Positive, Negative, GND Terminals |
| |
2.5 mm screwdriver blade |
Current Load
|
500 mA max@ 32 VDC max |
| Operating Temperature |
-20 to 50 Deg C |
| |
-4 to 122 Deg F |
|
Storage Temperature |
-40 to 85 Deg C |
| |
-40 to 185 Deg F |
| Relative Humidity |
5-95% (w/o condensation) |
| Dimensions |
Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD |
|
LED Indicators |
Power and Module Status |
| |
Application Status |
| |
Serial Port Activity LED |
| |
Serial Activity and Error LED Status |
| Configuration Serial Port |
Mini-DIN |
| |
RS-232 only |
| |
No hardware handshaking |
|
Ethernet Port |
10Base-T Connector |
| |
Link and Activity LED indicators |
| |
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 |
| |
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration |
|
Application Serial Ports |
Mini-DIN |
| |
RS-232/422/485 |
| |
RS232 handshaking configurable |
| |
RS422/485 screw termination included |
|
Port Isolation |
2500V Opto-Isolators |
| |
500V Power Supply Isolation |
|
Shipped with each unit |
Mini-DIN to DB-9M cables per serial port |
| |
4 ft RS-232 configuration cable |
| |
2.5mm screwdriver |
| |
CD (docs and Configuration utility) |
| |
RS-422/485 DB9 to Screw Terminal |
| |
Adaptor (1 or 4, depending on ports) |
|
PROFIBUS Connector
|
DB-9F Standard PROFIBUS connector
|
|
PROFIBUS LED Indicators
|
Active - Green
|
|
|
Error - Red
|
Click here for dimensions diagram Certifications
The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class 1, Div 2
PNO Certified - PROFIBUS Test Center
Ordering Information
|
5205-MNET-PDPS
|
Modbus TCP/IP to PROFIBUS DP Slave
|
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.