Harris 5000/5500/6000 RTU Slave Communications Module

3100-HAR

The ProSoft Harris Slave Module allows the user to easily configure one or both ports to be slaves to a Harris M9000 Host based system.

The 3100-HAR (PLC) Harris Slave Module is a single slot solution for the A-B 1771 and platforms. By providing configurable access to both ports, this product provides previously unavailable functionality and versatility.

Features

Simple to Use
All module setup and operating controls are performed over the backplane through simple ladder logic and data table configuration. The only software necessary is a standard ladder-programming package.

Hands Off Operation
Once the HAR module has been setup for operation, the card provides transparent control and monitoring capabilities. The HAR module, integrated directly into the PLC/SLC rack, forms a tightly integrated and practical solution. Once configured, the module will perform all protocol related functions on a stand-alone basis.

Installation, Set Up and Operation
The ProSoft module installs in any slot in a local rack. The product's capabilities are enabled and controlled with simple ladder logic and data table initialization.

Applications

The Harris 5000/5500/6000 Slave Module can be found in mainly in the power industry in the following applications:

  • Foreign device data concentrator
  • Power equipment monitoring
  • Dam operation

Functional Specifications

  • Harris 5000/5500/6000 implementation of the protocol
  • Full radio, modem and multi-drop support
  • Supports RS-232C, RS-422 and RS-485 interfaces
  • Communication error codes and counters returned to ladder logic(Slave port)
  • Configurable character delay to support VSAT packetizing delays
  • Configuration via simple ladder logic
  • Supported operational codes:

0

A/D and accumulator data dump

3

Status check

4

Status change dump

5

Status dump

6

Trip/close control arm

7

Trip/close control operate

8

AGC raise/lower

9

Set point control arm

10

Set point control operate

11

Power fail reset

12

Port on-line status scan

21

Time synchronization (SOE)

23

Time synchronization adjustment

27

Time synchronization (Non-SOE)

30

Set freeze interval

  • Supports broadcast commands from master register addressing
  • Up to 7 ports, each port with:

Status

Up to 63 words

Analog

Up to 63 words

  • Accumulator

12 bit

Up to 63 words

24 bit

Up to 34 values

32 bit

Up to 12 values

  • Communication parameters:

Address

1 to 63

Parity

None, odd, even

Stop bit

1 or 2

Baud rate

300 to 38.4K

RTS delays

1 ms resolution on and off

Hardware Specifications

  • Backplane current load
  • 3100 module for PLC
    - 0.65 A
  • Operating temperature
    - 0 to 60 deg C (32 to 140 deg F)
  • Storage temperature
    -From -40 to 85 deg C (-40 to 185 deg F)
  • Relative humidity
    - 5-95% (w/o condensation)
  • LED Indicators
    - Module status
    - Backplane transfer status
    - Serial port TX/RX activity LED
    - Serial port error LED status
  • Application serial ports
    - DB-25F - 3100 module
    - RS232/422/485 jumper selectable
    - RS422/485 screw termination included (two per module)
    - RS-232 hardware handshaking (RTS/CTS, DTR)
    - 500V optical isolation from backplane

Ordering Information

3100-HAR Harris 5000/5500/6000 RTU Slave Communications Module
   
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

 

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

 

Image Gallery



ProSoft Technology, Inc. Copyright © 2003 - 2008

Return to Non-Printable Page