Johnson Controls Metasys Slave

PTQ-N2

The PTQ Johnson Controls Metasys Slave Communication Module allows Schneider Electric Quantum compatible processors to interface easily with other Johnson Controls N2 master devices.

These modules are ideal for commercial building and energy management projects. Single or multiple processor applications will benefit through reduced installation costs and increased functionality.

Features and Benefits

Feature

Benefit

Communicates with Johnson Controls Metasys Master (NCM, N-30, NAE, NIE)

Enables SE Quantum control systems integration into existing Metasys master systems

Two configurable N2 application slave ports

Segmented and separate networks can justify better performance and control, or implement redundant connectivity

Easy to Configure and Monitor

ProSoft Configuration Builder software (included) allows you to customize module configuration files and view module diagnostics

Three Year Warranty

Low risk investment with great cost savings, backed up by a better than average equipment failure protection plan, from the industrial communications experts who know protocols, devices, and automation

Configuration

ProSoft Configuration Builder (PCB) provides a quick and easy way to manage module configuration files and view module and network diagnostics. PCB is not only a powerful solution for new configuration files, but also allows you to import information from previously installed (known working) configurations to new projects.

General Specifications

  • Single Slot - Quantum backplane compatible
  • The module is recognized as an Options module and has access to PLC memory for data transfer
  • Configuration data is stored in non-volatile memory in the ProTalk® module
  • Configuration software for Microsoft Windows XP, 2000 and NT is included with the module.
  • Up to six modules can be placed in a rack
  • Local rack - The module must be placed in the same rack as processor.
  • Compatible with common Quantum programming tools: UnityPro XL, Concept, ProWORX
  • Quantum data types supported: 3x, 4x
  • High speed data transfer across backplane provides quick data update times.
  • Sample ladder file available.

Functional Specifications

Specification

Description

N2 Objects

Binary Input:/Output Up to 960 points

Analog Input:/OutputUp to 255 points

Commands/
Sub-commands

0/4, 0/5, 0/9 Status

1/1, 1/2, 1/3, 1/4 Read Attributes

2/1, 2/2, 2/3, 2/4 Write Attributes

7/2/3, 7/2/4 Override Output

F: Identify Device Type

Configurable options

Slave Address (assignable individually for Port 1 and 2)

Analog Input/Output Object Count

Binary Input/Output Object Count

Other

Warning and Alarming functions performed on Analog Input and Binary Input data types

Change of State Response buffering

Communication status error codes and statistics returned per port

Communication parameter: Baud rate 9600 bps

Memory mapping is pre-assigned to optimize data access and to ease implementation

Hardware Specifications

Specification

Value

Backplane Current Load

800 mA @ 5 V

Operating Temperature

0 to 60°C (32 to 140°F)

Storage Temperature

-40 to 85°C (-40 to 185°F)

Relative Humidity

5% to 95% (non-condensing)

Vibration

Sine vibration 4-100 Hz in each of the 3 orthogonal axes

Shock

30G, 11 mSec. in each of the 3 orthogonal axes

LED Indicators

Module Status

Backplane Transfer Status

Serial Port Activity LED

Serial Activity and Error LED Status

Configuration Serial Port (Debug)

DB-9M PC Compatible

RS-232 only

No hardware handshaking

Application Serial Ports (PRT1, PRT2)

DB-9M PC Compatible

RS-232/422/485 jumper selectable

RS-422/485 screw termination included

RS-232 handshaking configurable

500V Optical isolation from backplane

Certifications

cULus, ATEX, CE

Hardware Specifications

Backplane Current Load

800 mA @ 5 V

Operating Temperature

0 to 60 Deg C (32 to 140 Deg F)

Storage Temperature

-40 to 85 Deg C (-40 to 185 Deg F)

Relative Humidity

5-95% (non-condensing)

Vibration

Sine vibration 4-100 Hz in each of the 3 orthogonal axes

Shock

30G, 11 mSec. in each of the 3 orthogonal axes

LED Indicators

Module Status
Backlane Transfer Status
Serial Port Activity LED
Serial Activity and Error LED Status

Configuration Serial Port
(PRT1)

DB-9M PC Compatible
RS-232 only
No hardware handshaking

Serial Ports

(PRT2, PRT3)
DB-9M PC Compatible
RS-232/422/485 jumper selectable
RS-422/485 screw termination included
RS-232 handshaking configurable
500 V Optical isolation from backplane

Ordering Information

PTQ-N2 Johnson Controls Metasys Slave
   
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

 

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

 