Modbus Master/Slave to Honeywell DE Master Communication Module
5106-MCM-DEM
Product Description
The ProLinx family Modbus Master/Slave to Honeywell DE Master communications module (5106-MCM-DEM) creates a powerful connection between devices on a Honeywell DE network and Modbus devices. The module is a stand-alone DIN-rail mounted protocol gateway that provides one configurable serial port and one 8 channel DEM block.
The Modbus (MCM) protocol driver supports Master and Slave implementations of the protocol. All Modbus serial ports are individually configurable, providing a very powerful and flexible host or device interface solution.
The DEM protocol driver is designed to provide a tightly integrated communications interface between other protocols of the ProLinx platform and the Honeywell DE instruments. Compatible DE devices include a large array of field devices including pressure, temperature, metering, and many other instruments.
Product Applications
The MCM-DEM modules are the ideal solution for the many applications where DEM connectivity can be used to integrate Modbus serial devices into a system.
The Honeywell DE gateway is a powerful module designed with Server support, enabling easy connection to Rockwell Automation PLCs (CLX, SLC, PLC, CPLX, and similar devices). In combination with the Modbus device support, the module provides a very powerful interface to the many Modbus devices which are in use in the industrial marketplace today. Applications for the module are found in most industries, especially the Manufacturing, Oil and Gas, Electrical Power and Food Processing.
Functional Specifications
Internal Database
The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.
The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.
Application Data Area
The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.
Status Data Area
This area is used to store error codes, counters, and port status information for each port.
Configuration Data Area
This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.
Modbus Protocol Specifications
The Modbus driver provides access to an internal database of 4000 registers (words), with extensive support provided for both the Master and the Slave implementations of the protocol. The serial port(s) on the gateway can be individually configured to support the Modbus protocol (Master or Slave, RTU or ASCII, Baud Rate, etc).
|
General Parameters - Modbus Protocol
|
|
Type
|
Specifications
|
|
Communication parameters
|
Baud Rate: 110 to 115K baud
Stop Bits: 1 or 2
Data Size: 7 or 8 bits
Parity: None, Even, Odd
RTS Timing delays: 0 to 65535 ms
|
|
Error Checking
|
RTU mode (binary) with CRC-16 ASCII mode with LRC error checking
|
|
Floating Point
|
Floating point data movement supported, including configurable support for Enron implementation
|
|
Function Codes
|
1 : Read Output Status
2 : Read Input Status
3 : Read Multiple Data Registers
4 : Read Input Registers
5 : Write Single Bit
6 : Write Single Data Register
15 : Write Multiple Bits
16 : Write Multiple Data Register
|
|
Modbus Master
|
|
Type
|
Specifications
|
|
Command List
|
Up to 100 command per master port, each fully configurable for function, slave address, register to/from addressing and word/bit count
|
|
Status Data
|
Error codes are provided on an individual command basis, as well as a slave status list is maintained per active Modbus Master port.
|
|
Polling of command list
|
Configurable polling of command list, including continuous and on change of data, and dynamically user or automatic enabled.
|
|
Modbus Slave
|
|
Type
|
Specifications
|
|
Node address
|
1 to 247 - software selectable
|
|
Status Data
|
Error codes, counters and port status available per configured slave port. Status data is all pre-mapped in the module
|
Honeywell DE Master Protocol Specifications
The ProLinx DEM Protocol Driver is designed to interface with up to 8 DE devices. Data is exchanged between the DE instruments and the driver using the internal database contained in the DEM module.
|
DE Communications
|
- Built in accordance with the Honeywell DE specification
- Supports up to 8 single PV transmitters, 2 multivariable transmitters with 4 PVs each, or a mix of single and multivariable equaling 8 input channels
- Instrument database mismatch verification
- Interfaces directly to Honeywell Field Terminal Assembly (FTA) with ProSoft-supplied cable
- Supports redundant and non-redundant FTA implementations
- Single cable connection from DEM module to FTA
|
|
Physical Specifications
|
|
Type
|
Specifications
|
|
Power Source
|
External 24 VDC source connection on the front of the DEM module provides instrument loop power
|
|
LEDs for Visual Module Status
|
DE Active
DE Error
|
Hardware Specifications
| Power Supply |
24 VDC nominal |
| |
18-32 VDC allowed |
| |
Positive, Negative, GND Terminals |
| |
2.5 mm screwdriver blade |
Current Load
|
500 mA max@ 32 VDC max |
| Operating Temperature |
-20 to 50 Deg C |
| |
-4 to 122 Deg F |
|
Storage Temperature |
-40 to 85 Deg C |
| |
-40 to 185 Deg F |
| Relative Humidity |
5-95% (w/o condensation) |
| Dimensions |
Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD |
|
LED Indicators |
Power and Module Status |
| |
Application Status |
| |
Serial Port Activity LED |
| |
Serial Activity and Error LED Status |
| Configuration Serial Port |
Mini-DIN |
| |
RS-232 only |
| |
No hardware handshaking |
|
Ethernet Port |
10Base-T Connector |
| |
Link and Activity LED indicators |
| |
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 |
| |
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration |
|
Application Serial Ports |
Mini-DIN |
| |
RS-232/422/485 |
| |
RS232 handshaking configurable |
| |
RS422/485 screw termination included |
|
Port Isolation |
2500V Opto-Isolators |
| |
500V Power Supply Isolation |
|
Shipped with each unit |
Mini-DIN to DB-9M cables per serial port |
| |
4 ft RS-232 configuration cable |
| |
2.5mm screwdriver |
| |
CD (docs and Configuration utility) |
| |
RS-422/485 DB9 to Screw Terminal |
| |
Adaptor (1 or 4, depending on ports) |
|
Honeywell DE Connector
|
Honeywell non-redundant FTA module
|
|
|
DEM to FTA cable
|
|
|
2 pos screw-terminal plug (HRD126)
|
|
DE LED Indicators
|
Comm - Green
|
|
|
Err - Red
|
Click here for dimensions diagram Certifications
The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class 1, Div 2
Ordering Information
|
5106-MCM-DEM
|
Modbus Master/Slave to Honeywell DE Master
|
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.