MTS Level Plus Interface Communications Module
3100-MTS
The 3100-MTS product allows the user to easily communicate with up to 64 MTS Level Plus gauges. The 3100-MTS (PLC) Module is a single slot solution for the A-B 1771 platforms (firmware solutions also available). These products allow MTS Level Plus digital gauges and Level Plus Monitors to be interfaced directly to the Allen-Bradley environment.
Features
Simple to Use All module setup and operating control is performed over the backplane through simple ladder logic and data table configuration. The only software necessary is a standard ladder-programming package.
Port Configuration Configuring the two ports independently allows for optimum flexibility. Using both ports as RS-485 Masters to MTS gauges, or one port as a RS-485 Master to a set of MTS gauges and the other as a Modbus Slave connected via modem to a SCADA host is one example of this flexibility. Once configured through the processor data table the module will perform all protocol related functions on a stand-alone basis, returning level and temperature information to the processor.
Easy Hardware Installation The connection between the 3100-MTS and the MTS gauges is a direct one and needs no RS-232 to RS-485 converter. In order to connect the 3100-MTS product to the MTS digital gauges, plug the module into the Allen-Bradley rack and connect the RS-485 line from the MTS gauges to the module's port.
Installation, Set Up and Operation The ProSoft module installs in any slot in a local or a remote rack. The product's capabilities are enabled and controlled with simple ladder logic and data table initialization. The module operates in any one of the following configurations:
|
Mode
|
Port 1
|
Port 2
|
|
Master/Master
|
MTS Master
|
MTS Master
|
|
MTS Master
|
MTS Master
|
Modbus Slave
|
Functional Specifications
- Continuous polling sequence of up to 64 gauges, each fully configurable for port, gauge address, level resolution, and temperature resolution
- Support for the storage and transfer of up to 4000 registers to/from the PLC
- RS-485 interface in module (No converters needed)
- Communication and instrument error codes returned to ladder logic on a per command/slave basis
- Supported commands:
16: Output Level 1 and 2 at 0.1 inch resolution
17: Output Level 1 and 2 at 0.01 inch resolution
18: Output Level 1 and 2 at 0.001 inch resolution
31: Ave & Indiv RTD Temp at 1 Deg F resolution
32: Ave & Indiv RTD Temp at 0.2 Deg F resolution
33: Ave & Indiv RTD Temp at 0.02 Deg F resolution
- The following Modbus features have been implemented:
RTU mode (binary) with CRC-16
ASCII mode with LRC error checking
Broadcast commands
125 word reads and writes
1: Read output status
2: Read input status
3: Read multiple data registers
4: Read input registers
5: Force single coil (Write single bit)
6: Preset (Write) single data register
15: Force multiple coils (Write multiple bits)
16: Preset (Write) multiple data register
- Address
- parity
- stop bits
- baud rate
- Full radio, modem and multi-drop support
- Supports RS-232C, RS-422 and RS-485 interfaces
Hardware Specifications
- Backplane current load
-
3100 module for PLC
- 0.65 A
-
Operating temperature
- 0 to 60 deg C (32 to 140 deg F)
-
Storage temperature
-From -40 to 85 deg C (-40 to 185 deg F)
-
Relative humidity
- 5-95% (w/o condensation)
-
LED Indicators
- Module status
- Backplane transfer status
- Serial port TX/RX activity LED - Serial port error LED status
-
Application serial ports
- DB-25F - 3100 module
- RS232/422/485 jumper selectable
- RS422/485 screw termination included (two per module)
- RS-232 hardware handshaking (RTS/CTS, DTR) - 500V optical isolation from backplane
Ordering Information
| 3100-MTS |
MTS Level Plus Interface Communications Module |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.
Sales and Support:
|