EtherNet/IP Interface Module

MVI71-DFNT

The MVI71 EtherNet/IP (DF1 for Ethernet) Client/Server Communication Module is a PLC backplane compatible module that allows PLC processors to interface easily with EtherNet/IP protocol (Explicit Messaging) compatible devices and hosts. Devices commonly supporting the protocol include Rockwell Automation PLCs, and host HMI systems.

Features and Benefits

The MVI71-DFNT module is a single slot solution that provides a powerful connection between Rockwell Automation's PLC processor and EtherNet/IP (DF1 for Ethernet) network applications.

The module can send read or write commands to remote devices on the EtherNet/IP network. The MVI71-DFNT also has 20 servers that allows the module to receive commands from remote devices. The MVI71-DFNT Pass-Through server allows the user to edit and transfer the PLC ladder logic using an Ethernet connection. Up to 100 commands can be configured by the user.

General Specifications

  • Single Slot - 1771 backplane compatible
  • The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
  • Ladder Logic is used for data transfer between module and processor. Sample ladder file included.
  • Configuration data obtained from configuration text file downloaded to module. Sample configuration file included.

EtherNet/IP (Explicit Messaging) Compatible Devices

List of Rockwell Automation material that support EPIC:

  • PLC5/E rev C/N, D/E, E/D
  • SLC5/05 series A, OS503 frn4
  • 1785-ENET Series A, rev D
  • Interchange V6.2
  • MicroLogix 1100/1400/ANY via 1761-NET-ENI
  • CompactLogix 1768-L43/L45 via 1768-ENBT
  • CompactLogix 1769-L32E/L35E/ANY via 1761-NET-ENI
  • RSLinx Gateway V1.7+
  • ControlLogix 1756-ENET/ENBT/EN2T

Functional Specifications

  • PLC processor in-chassis EtherNet/IP bridge to optimize data throughput while communicating with HMI or SCADA and other control platforms without losing valuable process control bandwidth
  • Support of up to 4000 PLC registers user data files
  • User-definable module memory usage
  • 10/100 MB Ethernet compatible interface
  • Functions as a server or a client
  • Configurable parameters for the client include:
    • A minimum response delay of 0 to 65535 mSec
    • A response timeout of 1 to 65535 mSec
    • A retry count of 0 to 20
  • Status data available in ladder logic

Support for PLC processor programming over Ethernet using a TCP/IP service and a serial port on the module connected to channel 0 of the processor. The module's third port emulates Channel 0 of the processor to pass through messages from the port to the processor

Server Specifications

  • Supports EtherNet/IP explicit, connected, and unconnected class messaging
  • Twenty independent server connections permit remote clients to interact with all data contained in the module
  • Data can be derived from other clients on the network, through the client on the module, or from the PLC processor

Client Specifications

  • Actively issues connected, explicit messages to other nodes on the network
  • Supports 100 user-defined commands from a single client
  • Allows command control from ladder logic
  • Pass-through services
  • Permits remote programming of the PLC processor on the Ethernet network via a pass-through
  • TCP/IP service and a serial communication port (pass-through port) on the module
  • The third port on the module can emulate the Channel 0 port on the PLC, This allows a DF1 master device attached to the emulated (Channel 0) port to monitor and control data in the PLC.

Hardware Specifications

Form Factor

Single Slot - 1771 chassis compatible

 

BTR/BTW data transfer

 

Local or remote rack

Backplane Current Load

800 mA @ 5V

Operating Temperature

0 to 60 deg C (32 to 140 deg F)

Storage Temperature

-40 to 85 deg C (-40 to 185 deg F)

Shock

30g operational

 

50g non-operational

Vibration

5g from 10 - 10150 Hz

Relative Humidity

5 to 95% (w/o condensation)

LED Indicators

Module status

 

Backplane transfer status

 

Application status

 

Error LED status

 

Link and Activity LED

Configuration Port (CFG)

DB-9M PC compatible

 

RS-232

 

Hardware handshaking

Ethernet Port

RJ45 connector

Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration

Shipped with unit

RJ45 connector

 

RJ45 to DB-9M cable

 

6-foot RS-232 configuration cable

Ordering Information

MVI71-DFNT EtherNet/IP Interface Module
   
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

 

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

 

Image Gallery



ProSoft Technology, Inc. Copyright © 2003 - 2008

Return to Non-Printable Page