DF1 Master/Slave
PTQ-DFCM
The DF1 Master/Slave Communication Module is a Quantum backplane compatible module that allows Modicon Quantum processors to interface easily with DF1 protocol compatible devices and hosts. Devices commonly supporting the protocol include Rockwell Automation PLCs and power monitoring equipment, as well as several other third party devices in the marketplace.
Features and Benefits
The module has two serial ports supporting the DF1 protocol, with each port user configurable to act as a Master or as a Slave. Data transfer between the module and the Quantum processor is asynchronous to the DF1 network, with the module's internal database being used to exchange data between the Quantum processor and the DF1 network.
The PTQ-DFCM module is a powerful communication interface for Quantum platform processors. Developed under license from Schneider Electric, the module incorporates proprietary backplane technology that enables powerful data access to the Quantum processor.
General Specifications
- Single Slot - Quantum backplane compatible
- The module is recognized as an Options module and has access to PLC memory for data transfer
- Configuration data is stored in non-volatile memory in the ProTalk module
- Configuration software for Microsoft Windows XP, 2000 and NT is included with the module.
- Up to six modules can be placed in a rack
- Local rack - The module must be placed in the same rack as processor.
- Compatible with common Quantum / Unity programming tools.
- Quantum data types supported: 0x, 1x, 3x, 4x
- High speed data transfer across backplane provides quick data update times.
- Sample function blocks available.
Applications
The PTQ-DFCM module is the ideal solution for many applications where DF1 Master/Slave protocol connectivity must be added to a Quantum system.
The DFCM solution is a powerful module designed with both Master and Slave support. This broad support enables the module to function as a SCADA sub-master, or to be a powerful slave on in a SCADA system. Applications for the module are found in most industries, especially the Water/Wastewater, Oil and Gas, Electrical Power and Food processing.
- Foreign device data concentrator
- SCADA system pipelines and offshore platforms
- Food processing
- Mining
- Pulp and paper
Functional Specifications
General Protocol specifications
|
Type
|
Specifications
|
|
Internal Database
|
4000 registers (words) available for transfer to and from Quantum processor
|
|
Communication parameters
|
Local Station ID: 0 to 254
Port 1&2 Baud Rate: 110 to 115K baud
Stop Bits: 1
Data Size: 8 bits
Parity: None, Even, Odd
RTS Timing delays:0 to 65535 ms
|
|
DF1 Modes
|
Full-Duplex
- Master and Slave, multidrop addressing
Half-Duplex
- Master-Slave polling by master
- Peer to Peer (Slave to Slave)
|
|
Error Checking
|
BCC and CRC
|
|
Miscellaneous
|
Full hardware handshaking control, providing radio, modem and Multidrop support
125 word read and write data lengths supported
Floating point data supported
|
DF1 Slave Protocol Specifications
The ports on the PTQ-DFCM module can be individually configured to support the Slave mode of the DF1 protocol. When in the Slave mode, the module can accepts DF1 commands from a Master to read/write data stored in the module's internal registers. This data is easily transferred to the Quantum processor's data registers.
|
DF1 Slave Driver
|
|
Configurable Parameter per slave port
|
Data Table File Start (File N[X] 0 to 999)
Data Table File Size (1-1000 words)
Data Table location in module (0 to 3999)
|
|
DF1 Commands supported
|
Basic Command Set
0x00: Protected Write
0x01: Unprotected Read
0x02: Protected Bit Write
0x05: Unprotected Bit Write
0x08: Unprotected Write
PLC-5 Command Set (0x0F)
0x00: Word Range Write (Binary Address)
0x01: Word Range Read (Binary Address)
0x00: Word Range Write (ASCII Address)
0x01: Word Range Read (ASCII Address)
SLC Command Set (0x0F)
0xA1: Prot Typed Read with 2 addr fields
0xA2: Prot Typed Read with 3 addr fields
0xA9: Prot Typed Write with 2 addr fields
0xAA: Prot Typed Write with 3 addr fields
|
DF1 Master Protocol Specifications
The ports on the PTQ-DFCM can individually be configured as master ports. When configured in the master mode the DFCM module is capable of reading and writing data to remote DF1 devices, enabling the Quantum platform to act as a SCADA sub-master.
|
DF1 Master Driver
|
|
General
|
Full-Duplex
Master
Half-Duplex
Master
Peer to Peer (Slave to Slave)
|
|
DF1 Commands supported
|
Basic Command Set
0x00: Protected Write
0x01: Unprotected Read
0x02: Protected Bit Write
0x05: Unprotected Bit Write
0x08: Unprotected Write
PLC-5 Command Set (0x0F)
0x00: Word Range Write (Binary Address)
0x01: Word Range Read (Binary Address)
0x26: Read-Modify-Write (Binary Address)
0x00: Word Range Write (ASCII Address)
0x01: Word Range Read (ASCII Address)
0x26: Read-Modify-Write (ASCII Address)
SLC Command Set (0x0F)
0xA1: Prot Typed Read with 2 addr fields
0xA2: Prot Typed Read with 3 addr fields
0xA9: Prot Typed Write with 2 addr fields
0xAA: Prot Typed Write with 3 addr fields
0xAB: Prot Typed Write with Mask 3 addr fields
|
|
Command List
|
Up to 100 command per master port, each fully configurable for function, slave address, register to/from addressing and word/bit count
|
|
Status Data
|
Error codes available on an individual command basis. In addition, a slave status list is maintained per active master port.
|
|
Polling of command list
|
User configurable polling of commands, including disabled, continuous and on change of data (write only)
|
Hardware Specifications
|
Backplane Current Load
|
800 mA @ 5 V
|
|
Operating Temperature
|
0 to 60 Deg C (32 to 140 Deg F)
|
|
Storage Temperature
|
-40 to 85 Deg C (-40 to 185 Deg F)
|
|
Relative Humidity
|
5-95% (non-condensing)
|
|
Vibration
|
Sine vibration 4-100 Hz in each of the 3 orthogonal axes
|
|
Shock
|
30G, 11 mSec. in each of the 3 orthogonal axes
|
|
LED Indicators
|
Module Status
Backlane Transfer Status
Serial Port Activity LED Serial Activity and Error LED Status
|
|
Configuration Serial Port (PRT1)
|
DB-9M PC Compatible
RS-232 only No hardware handshaking
|
|
Serial Ports
|
(PRT2, PRT3)
DB-9M PC Compatible
RS-232/422/485 jumper selectable
RS-422/485 screw termination included
RS-232 handshaking configurable 500 V Optical isolation from backplane
|
Ordering Information
| PTQ-DFCM |
DF1 Master/Slave |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.