ProSoft Technology, Inc.
Home > Products > for Rockwell Automation > Platform > CompactLogix > MVI69-MCM
Printable Page
 

Search | Clear


Modbus Master/Slave Communication Module

MVI69-MCM

MVI69-MCM Interactive Tour

The MVI69 Modbus Communication Module allows Rockwell Automation CompactLogix processors to interface easily with other Modbus protocol compatible devices.

Compatible devices include not only Modicon PLCs (which all support the Modbus protocol) but also a wide assortment of end devices. The module acts as an input/output module between the Modbus network and the Rockwell Automation backplane. The data transfer from the processor is asynchronous from the actions on the Modbus network. A 5000-word register space in the module exchanges data between the processor and the Modbus network.

Features and Benefits

The inRAx Modbus Master/Slave Communications module (MVI69-MCM) is designed to allow CompactLogix processors to interface easily with Modbus protocol-compatible devices and hosts.

Many host SCADA packages support the Modbus protocol, while devices commonly supporting the protocol include several PLCs, as well as many other third party devices in the marketplace. (For a partial list of devices that speak Modbus, please visit the ProSoft Tested section of the ProSoft web site).

Applications

  • Applications using the Modbus Communication Module can be found in many industrial sectors and in the following applications
  • Foreign device data concentrator
  • Pipelines and offshore platforms
  • Food processing
  • Mining
  • Pulp and paper
  • SCADA communications
  • Supports Enron version of Modbus protocol for floating point data transactions.

Functional Specifications

Type

Specifications

Communication parameters (configurable)

Port 1: Baud Rate: 110 to 38.4K baud RS232

Port 2,3: Baud Rate: 110 to 115K baud RS232, 485, 422 (jumper selectable)

Stop Bits: 1 or 2

Data Size: 5 to 8 bits

Parity: None, Odd, Even

RTS Timing delays: 0 to 65535 ms

Modbus Modes

RTU Mode (binary) with CRC-16

ASCII mode with LRC error checking

Floating Point Data

Floating point data movement supported, including configurable support for Enron implementation

Modbus Slave Protocol Specifications

The ports on the MVI69-MCM module can be individually configured to support the slave mode of the Modbus protocol. When in slave mode, the module can accept Modbus commands from a master to read/write data stored in the module's internal registers. This data is easily transferred to the CompactLogix processor's data registers.

Modbus Slave Driver

Node Address

1 to 247 software selectable

Status Data

Error codes, counters, and port status available per configured slave port starting at memory register 4400

Modbus Function Codes

1: Read Output Status

2: Read Input Status

3: Read Multiple Data Registers

4: Read Input Registers

5: Write Single Bit

6: Write Single Data Register

15: Write Multiple Bits

16: Write Multiple Data Register

Modbus Master Protocol Specifications

The ports on the MVI69-MCM module can be individually configured as Master ports. When configured in master mode, the MCM module is capable of reading and writing data to remote Modbus devices, enabling the CompactLogix platform to act as a SCADA sub-master, or a device data concentrator.

Modbus Master Driver

Command List

Up to 100 commands per master port, each fully configurable for function, slave address, register to/from addressing and word/bit count

Status Data

Error codes available on an individual command basis. In addition, a slave status list is maintained per active Modbus master port

Polling of Command List

Configurable polling of command list, including continuous and on change of data

Modbus Function Codes

1: Read Output Status

2: Read Input Status

3: Read Multiple Data Registers

4: Read Input Registers

5: Write Single Bit

6: Write Single Data Register

15: Write Multiple Bits

16: Write Multiple Data Register

Hardware Specifications

Dimensions

Standard 1769 Single-slot module

Current Load

800 mA max@ 5 VDC (Serial)
Power supply distance rating of 2 (L43 and L45 installations on first 2 slots of 1769 bus)

Operating Temp.

0 to 60 Deg C

 

32 to 140 Deg F

Storage Temp.

-40 to 85 Deg C

 

-40 to 185 Deg F

Relative Humidity

5 - 95% (w/o condensation)

LED Indicators

Power and Module Status

 

Application Status

 

Serial Port Activity

 

Serial Activity and Error Status

CFG Port

RJ45 (DB-9M w/ supplied cable)

 

RS-232 only

 

No hardware handshaking

App Ports (P1, P2)

RJ45 (DB-9M w/supplied cable)

 

RS-232 handshaking configurable

 

500V Optical isolation from backplane

Shipped with Unit

RJ45 to DB-9M cables for each port

 

6-foot RS-232 configuration Cable

Ordering Information

MVI69-MCM Modbus Master/Slave Communication Module
   
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

 

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe/Middle East/Africa
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

 

Related Information

ProSoft Configuration Builder

Home : Products : Support : Distributors : Services : News/Events : Contact : ProSoft Tested