EtherNet/IP Interface Module
MVI71-DFNT
The MVI71 EtherNet/IP (DF1 for Ethernet) Client/Server Communication Module is a PLC backplane compatible module that allows PLC processors to interface easily with EtherNet/IP protocol (Explicit Messaging) compatible devices and hosts. Devices commonly supporting the protocol include Rockwell Automation PLCs, and host HMI systems.
Features and Benefits
The MVI71-DFNT module is a single slot solution that provides a powerful connection between Rockwell Automation's PLC processor and EtherNet/IP (DF1 for Ethernet) network applications.
The module can send read or write commands to remote devices on the EtherNet/IP network. The MVI71-DFNT also has 20 servers that allows the module to receive commands from remote devices. The MVI71-DFNT Pass-Through server allows the user to edit and transfer the PLC ladder logic using an Ethernet connection. Up to 100 commands can be configured by the user.
General Specifications
- Single Slot - 1771 backplane compatible
- The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
- Ladder Logic is used for data transfer between module and processor. Sample ladder file included.
- Configuration data obtained from configuration text file downloaded to module. Sample configuration file included.
EtherNet/IP (Explicit Messaging) Compatible Devices
List of Rockwell Automation material that support EPIC:
- PLC5/E rev C/N, D/E, E/D
- SLC5/05 series A, OS503 frn4
- 1785-ENET Series A, rev D
- Interchange V6.2
- MicroLogix 1100/1400/ANY via 1761-NET-ENI
- CompactLogix 1768-L43/L45 via 1768-ENBT
- CompactLogix 1769-L32E/L35E/ANY via 1761-NET-ENI
- RSLinx Gateway V1.7+
- ControlLogix 1756-ENET/ENBT/EN2T
Functional Specifications
- PLC processor in-chassis EtherNet/IP bridge to optimize data throughput while communicating with HMI or SCADA and other control platforms without losing valuable process control bandwidth
- Support of up to 4000 PLC registers user data files
- User-definable module memory usage
- 10/100 MB Ethernet compatible interface
- Functions as a server or a client
- Configurable parameters for the client include:
- A minimum response delay of 0 to 65535 mSec
- A response timeout of 1 to 65535 mSec
- A retry count of 0 to 20
- Status data available in ladder logic
Support for PLC processor programming over Ethernet using a TCP/IP service and a serial port on the module connected to channel 0 of the processor. The module's third port emulates Channel 0 of the processor to pass through messages from the port to the processor
Server Specifications
- Supports EtherNet/IP explicit, connected, and unconnected class messaging
- Twenty independent server connections permit remote clients to interact with all data contained in the module
- Data can be derived from other clients on the network, through the client on the module, or from the PLC processor
Client Specifications
- Actively issues connected, explicit messages to other nodes on the network
- Supports 100 user-defined commands from a single client
- Allows command control from ladder logic
- Pass-through services
- Permits remote programming of the PLC processor on the Ethernet network via a pass-through
- TCP/IP service and a serial communication port (pass-through port) on the module
- The third port on the module can emulate the Channel 0 port on the PLC, This allows a DF1 master device attached to the emulated (Channel 0) port to monitor and control data in the PLC.
Hardware Specifications
|
Form Factor
|
Single Slot - 1771 chassis compatible
|
|
|
BTR/BTW data transfer
|
|
|
Local or remote rack
|
|
Backplane Current Load
|
800 mA @ 5V
|
|
Operating Temperature
|
0 to 60 deg C (32 to 140 deg F)
|
|
Storage Temperature
|
-40 to 85 deg C (-40 to 185 deg F)
|
|
Shock
|
30g operational
|
|
|
50g non-operational
|
|
Vibration
|
5g from 10 - 10150 Hz
|
|
Relative Humidity
|
5 to 95% (w/o condensation)
|
|
LED Indicators
|
Module status
|
|
|
Backplane transfer status
|
|
|
Application status
|
|
|
Error LED status
|
|
|
Link and Activity LED
|
|
Configuration Port (CFG)
|
DB-9M PC compatible
|
|
|
RS-232
|
|
|
Hardware handshaking
|
|
Ethernet Port
|
RJ45 connector
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
|
|
Shipped with unit
|
RJ45 connector
|
|
|
RJ45 to DB-9M cable
|
|
|
6-foot RS-232 configuration cable
|
Ordering Information
| MVI71-DFNT |
EtherNet/IP Interface Module |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.
Sales and Support:
|