Foxboro/Systronics Minimote RTU Slave Communications Module
3150-SYS
The 3150-SYS (SLC) Systronics slave module is a single slot solution for the A-B 1746 platforms. By providing configurable access to both ports, this product provides previously unavailable functionality and versatility. Support has been added to the product to support the report by exception capabilities associated with VSAT implementations of the protocol.
Features
Simple to Use
All module setup and operating controls are performed over the backplane through simple ladder logic and data table configuration. The only software necessary is a standard ladder-programming package.
Hands Off Operation
Once the SYS module has been setup for operation, the card provides transparent control and monitoring capabilities. The SYS module, integrated directly into the PLC/SLC rack, forms a tightly integrated and practical solution. Once configured, the module will perform all protocol related functions on a stand-alone basis.
Installation, Set Up and Operation
The ProSoft module installs in any slot in a local rack. The product's capabilities are enabled and controlled with simple ladder logic and data table initialization.
Applications
Applications involving the Foxboro/Systronics slave module can be found in many industrial sectors and in the following applications:
- Foreign device data concentrator
- Pipelines
- Offshore platforms
- Oil field lease
Functional Specifications
- Foxboro / Systronics Minimote RTU Protocol, with VSAT reporting support
- Full radio, modem and multi-drop support
- Supports RS-232C, RS-422 and RS-485 interfaces
- Communication error codes and counters returned to ladder logic (Slave port)
- Configurable character delay to support VSAT packetizing delays
- Configuration via simple ladder logic
- Supports broadcast commands from Master
- Supports write commands from host in both direct or indirect modes
- Setpoint select and operate
- Control point - continuous and momentary
- Supported file numbers
|
14h
|
Analog Data
|
|
19h
|
Status Data
|
|
37h
|
Accumulator Data - 32 bit
|
|
1Dh
|
Momentary Control Select
|
|
21h
|
Setpoint Select
|
|
23h
|
Execute Selected Control File
|
|
2Ch
|
Pulse Train Control File
|
|
30h
|
Multi-file Streaming Data Setup
|
|
3Fh
|
Multi-file Streaming Data
|
|
3Ch
|
VSAT Timer Setup
|
|
3Eh
|
20 msec Timer
|
|
41h
|
Analog Deviation Limits
|
|
44h
|
Accumulator Reset Commands
|
|
47h
|
32 bit Accumulator Current End of Batch
|
|
4Bh
|
Tank Levels
|
|
Filetype
|
File #'s
|
Valid Addresses
|
|
16 bit registers
|
14h
|
0 - 61
|
|
16 bit binary
|
19h
|
0 - 123
|
|
32 bit acc EOBatch
|
47h
|
0 - 15
|
|
32 bit accumulator
|
37h
|
0 - 31
|
|
Tank Levels
|
4Bh
|
0 - 31
|
|
Momentary Control
|
1Dh
|
Bit:0 - 255
|
|
|
|
Card 0 - 15
|
|
Setpoint Select
|
21h
|
Reg:0 - 4095
|
|
Accumulator Reset
|
44h
|
1 -2
|
|
Address
|
1 to 254 ( 127 is broadcast)
|
|
Parity
|
None, Odd, Even
|
|
Stop Bit
|
1 or 2
|
|
Baud rate
|
300 to 38.4K
|
|
RTS Delays
|
1 ms resolution on and off
|
Hardware Specifications
- Backplane current load
-
3150 module for SLC
- 5V @ 0.15 A - 24 V @ 0.040 A
-
Operating temperature
- From 0° C to 60° C (32° F to 140° F)
-
Storage temperature
-From -40° C to 85° C (-40° F to 185° F)
-
Relative humidity
- From 5% to 95% (without condensation)
-
LED indicators
- Module Status
- Backplane transfer status
- Serial port TX/RX activity LED - Serial port error LED status
-
Application Serial ports
- DB-25F - 3100 module
- DB-9M - 3150 module
- RS232/422/485 jumper selectable
- RS422/485 screw termination included (two per module)
- RS-232 hardware handshaking (RTS/CTS, DTR) - 500 V Optical isolation from backplane
Ordering Information
| 3150-SYS |
Foxboro/Systronics Minimote RTU Slave Communications Module |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.