EtherNet/IP Interface Module

MVI71-DFNT

The MVI71 EtherNet/IP (DF1 for Ethernet) Client/Server Communication Module is a PLC backplane compatible module that allows PLC processors to interface easily with EtherNet/IP protocol (Explicit Messaging) compatible devices and hosts. Devices commonly supporting the protocol include Rockwell Automation PLCs, and host HMI systems.

Features and Benefits

The MVI71-DFNT module is a single slot solution that provides a powerful connection between Rockwell Automation's PLC processor and EtherNet/IP (DF1 for Ethernet) network applications.

The module can send read or write commands to remote devices on the EtherNet/IP network. The MVI71-DFNT also has 20 servers that allows the module to receive commands from remote devices. The MVI71-DFNT Pass-Through server allows the user to edit and transfer the PLC ladder logic using an Ethernet connection. Up to 100 commands can be configured by the user.

Configuration

ProSoft Configuration Builder (PCB) provides a PC-based software configuration solution for quick management of configuration files, as well as viewing communication and network diagnostics.
PCB is not only a powerful solution for new configuration files, but also allows you to import information from previously installed (known working) configurations into new projects.

General Specifications

  • Single Slot - 1771 backplane compatible
  • The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
  • Ladder Logic is used for data transfer between module and processor. Sample ladder file included.

EtherNet/IP (Explicit Messaging) Compatible Devices

Rockwell Automation equipment that supports EPIC:

  • PLC5/E rev C/N, D/E, E/D
  • SLC5/05 series A, OS503 frn4
  • 1785-ENET Series A, rev D
  • Interchange V6.2
  • MicroLogix 1100/1400/ANY via 1761-NET-ENI
  • CompactLogix 1768-L43/L45 via 1768-ENBT
  • CompactLogix 1769-L32E/L35E/ANY
  • CompactLogix L23E
  • RSLinx Gateway V1.7+
  • ControlLogix 1756-ENET/ENBT/EN2T/EN2TR

Functional Specifications

  • PLC processor in-chassis EtherNet/IP bridge to optimize data throughput while communicating with HMI or SCADA and other control platforms without losing valuable process control bandwidth
  • Support of up to 4000 PLC registers user data files
  • User-definable module memory usage
  • 10/100 MB Ethernet compatible interface
  • Functions as a server or a client
  • Configurable parameters for the client include:
    • A minimum response delay of 0 to 65535 mSec
    • A response timeout of 1 to 65535 mSec
    • A retry count of 0 to 20
  • Status data available in ladder logic

Support for PLC processor programming over Ethernet using a TCP/IP service and a serial port on the module connected to channel 0 of the processor. The module's third port emulates Channel 0 of the processor to pass through messages from the port to the processor

Server Specifications

  • Supports EtherNet/IP explicit, connected, and unconnected class messaging
  • Twenty independent server connections permit remote clients to interact with all data contained in the module
  • Data can be derived from other clients on the network, through the client on the module, or from the PLC processor

Client Specifications

  • Actively issues connected, explicit messages to other nodes on the network
  • Supports 100 user-defined commands from a single client
  • Allows command control from ladder logic
  • Pass-through services
  • Permits remote programming of the PLC processor on the Ethernet network via a pass-through
  • TCP/IP service and a serial communication port (pass-through port) on the module
  • The third port on the module can emulate the Channel 0 port on the PLC, This allows a DF1 master device attached to the emulated (Channel 0) port to monitor and control data in the PLC.

Hardware Specifications

Form Factor

Single Slot - 1771 chassis compatible

 

BTR/BTW data transfer

 

Local or remote rack

Backplane Current Load

800 mA @ 5V

Operating Temperature

32°F to 140°F (0°C to 60°C)

Storage Temperature

-40°F to 185°F(-40°C to 85°C)

Shock

30g operational

 

50g non-operational

Vibration

5g from 10 Hz to 150 Hz

Relative Humidity

5% to 95% RH, with no condensation

LED Indicators

Module status

 

Backplane transfer status

 

Application status

 

Error LED status

 

Link and Activity LED

Configuration Port (CFG)

DB-9M PC compatible

 

RS-232

 

Hardware handshaking

Ethernet Port

RJ45 connector

 

10/100 Mbit Ethernet support (auto-sensing)

 

Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 seconds, applied as specified in section 5.3.2 of IEC 60950: 1991

 

Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration

Shipped with unit

RJ45 to DB-9M adapter cable for configuration

 

6-foot RS-232 null-modem configuration cable

   

Ordering Information

MVI71-DFNT EtherNet/IP Interface Module
   
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

 

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe/Middle East/Africa
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

 

Related Information

ProSoft Configuration Builder

Home : Products : Support : Distributors : Services : News/Events : Contact : ProSoft Tested