EtherNet/IP to Modbus TCP/IP Communication Module
5201-DFNT-MNET
Product Description
The ProLinx family EtherNet/IP to Modbus TCP/IP communications module (5201-DFNT-MNET) creates a powerful connection between Modbus TCP/IP and EtherNet/IP networks. The module is a stand-alone DIN-rail mounted protocol gateway that provides one Ethernet port.
The Modbus TCP/IP (MNET) driver can be used to interface many different protocols into the Schneider Electric Quantum family of processors as well other software solutions supporting the protocol. The MNET driver supports Client connections as well as Server connections.
The Ethernet/IP (DFNT) protocol driver supports the Explicit Messaging implementation of the protocol. User-configurable as both a Client and a Server, the EtherNet/IP port is a very powerful data transfer tool.
Product Applications
The DFNT-MNET modules are the ideal solution for joining EtherNet/IP and Modbus TCP/IP networks.
This Ethernet to Ethernet gateway is a powerful module designed with both Client and Server support for each protocol, enabling easy connections between the dissimilar network types. The module utilizes a shared database so that the two protocols can quickly and easily transfer data between themselves. Applications for the module are found in most industries, especially the Manufacturing, Oil and Gas, Electrical Power and Food Processing
.
Functional Specifications
Internal Database
The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.
The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.
Application Data Area
The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.
Status Data Area
This area is used to store error codes, counters, and port status information for each port.
Configuration File
This file contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, the module.
Modbus TCP/IP Protocol Specifications
The Ethernet driver interfaces with a common internal database in the module. This permits the sharing of data across many different protocols and networks.
Modbus TCP/IP Port Specifications
Server
The MNET module supports server functionality using the reserved Modbus TCP/IP service port 502, as well as service port 2000 to support the TCP/IP encapsulated Modbus protocol that is supported by several HMI manufacturers. Services supported in the module permit client applications (i.e., HMI software packages, Quantum processors, etc.) to read from and write to the module's database.
Data in the module's internal database is accessible for read and write operations by any node on the network supporting the MBAP (service port 502) or MNET (service ports 2000/2001) TCP/IP protocols.
There is no configuration of the MNET module required to implement Server functionality other than setting up the network and database parameters in the user configuration file.
|
Modbus TCP/IP Server
|
|
Type
|
Specification
|
|
General
|
The server driver supports connections to Modbus TCP/IP clients supporting Service Port 502 using the standard MBAP protocol, and clients supporting Modbus on Service Port 2000. - Supports up to five (5) independent server connections for Service Port 502
- Supports up to five (5) independent server connections for Service Port 2000
|
|
Configurable Parameters
|
Module IP Address Modbus address offsetting
|
|
Modbus Commands supported
|
1 : Read Output Status
2 : Read Input Status
3 : Read Multiple Data Registers
4 : Read Input Registers
5 : Write Single Bit
6 : Write Single Data Register
15 : Write Multiple Bits 16 : Write Multiple Data Register
|
Client
The module supports a client connection on the TCP/IP network to interface with processors (and other server based devices) using a user constructed command list of up to 100 entries.
|
Modbus TCP/IP Client
|
|
Type
|
Specification
|
|
General
|
The client driver supports the active reading and writing of data with Modbus TCP/IP compatible devices.
- One client connection available (connect up to 100 servers/devices with 100 commands)
|
|
Configurable parameters
|
Number of active commands (Up to 100 for client)
Min Command Delay
Response Timeout
Retry Count Command Error Pointer
|
|
Modbus Commands supported
|
1 : Read Output Status
2 : Read Input Status
3 : Read Multiple Data Registers
4 : Read Input Registers
5 : Write Single Bit
6 : Write Single Data Register
15 : Write Multiple Bits 16 : Write Multiple Data Register
|
|
Command List
|
Up to 100 commands on the Client port, each fully configurable for function, Server IP address, Service Port, register to/from addressing and word/bit count
|
|
Status Data
|
Error codes available on an individual command basis.
|
|
Polling of command list
|
User configurable polling of commands, including disabled, continuous and on change of data (write only)
|
EtherNet/IP Protocol Specifications
The EtherNet/IP protocol is one of the primary connectivity tools to the different Rockwell Automation platforms. The Explicit Messaging aspect of the protocol (only) has been implemented in the ProLinx units to provide the data transfer link between the ProLinx units and the Rockwell Automation hardware. (Implicit Messaging (I/O communications) is not supported)
|
General Protocol Information
|
|
Messaging
|
PCCC on CIP Explicit Messaging supported
|
|
Compatibility
|
Compatible devices include a wide assortment of other client/server devices such as:
- PLC5/E Rev. C/N, D/E, E/D or later
- SLC5/05 Series A, OS503 frn4 or later
- ControlLogix processor via 1756-ENET
- 1785-ENET Series A, Rev. D
- Interchange (release dependent) - RSLinx Gateway V1.7 or later
|
|
Miscellaneous
|
125 word read and write data lengths Floating point data supported
|
EtherNet/IP Server Specifications
When in the Server mode, the module accepts commands from one or more clients to read/write data stored in the module's internal registers.
The following table lists EtherNet/IP Server specifications:
|
EtherNet/IP Server Specifications
|
|
Connections
|
Five (5) independent TCP server sockets permit remote clients to interact with all data contained in the module.
|
|
Data File
|
Data Table File Start - Fixed at N10 Data Table File Size - 100 or 1000 words
|
|
PCCC on CIP
Commands supported
(DF1 commands)
|
Basic Command Set
0x00 Protected Write
0x01 Unprotected Read
0x02 Protected Bit Write
0x05 Unprotected Bit Write 0x08 Unprotected Write
PLC-5 Command Set (0x0F)
0x00 WordRange Write (Binary Address)
0x01 WordRange Read (Binary Address)
0x00 WordRange Write (ASCII Address) 0x01 WordRange Read (ASCII Address)
SLC Command Set (0x0F)
0xA1 Prot Typed Read w/ 2 addr fields
0xA2 Prot Typed Read w/ 3 addr fields
0xA9 Prot Typed Write w/ 2 addr fields 0xAA Prot Typed Write w/ 3 addr fields
|
|
CIP Services Supported
|
0x4C CIP Data Table Read 0x4D CIP Data Table Write
|
EtherNet/IP Client Specifications
When configured in Client mode, the module controls the read/write data transfer between the gateway and other Ethernet/IP devices. When configured in this mode, data transfer can be initiated and executed without any ladder programming being required in the Rockwell Automation hardware.
The following table provides Ethernet/IP Client specifications:
|
EtherNet/IP Client Specifications
|
|
General
|
One client
|
|
Command List
|
Support for 100 commands, each configurable for command, IP address, register to/from addressing and word/bit count
|
|
Polling of command list
|
User configurable polling of commands, including disabled, continuous and on change of data (write only)
|
|
PCCC on CIP
Commands Supported
(DF1 Commands)
|
Basic Command Set
0x00 Protected Write
0x01 Unprotected Read
0x02 Protected Bit Write
0x05 Unprotected Bit Write 0x08 Unprotected Write
PLC-5 Command Set (0x0F)
0x00 WordRange Write (Binary Address)
0x01 WordRange Read (Binary Address)
0x26 Read-Modify-Write (Binary Address)
0x00 WordRange Write (ASCII Address)
0x01 WordRange Read (ASCII Address) 0x26 Read-Modify-Write (ASCII Address)
SLC Command Set (0x0F)
0xA1 Prot Typed Read w/ 2 addr fields
0xA2 Prot Typed Read w/ 3 addr fields
0xA9 Prot Typed Write w/ 2 addr fields
0xAA Prot Typed Write w/ 3 addr fields 0xAB Prot Typed Write w/ Mask 3 addr fields
|
|
Status Data
|
Error codes available on an individual command basis.
|
EtherNet/IP (Explicit Messaging) Compatible Devices
List of Rockwell Automation material that support EPIC:
- PLC5/E rev C/N, D/E, E/D
- SLC5/05 series A, OS503 frn4
- 1785-ENET Series A, rev D
- Interchange V6.2
- MicroLogix 1100/1400/ANY via 1761-NET-ENI
- CompactLogix 1768-L43/L45 via 1768-ENBT
- CompactLogix 1769-L32E/L35E/ANY via 1761-NET-ENI
- RSLinx Gateway V1.7+
- ControlLogix 1756-ENET/ENBT/EN2T
Hardware Specifications
| Power Supply |
24 VDC nominal |
| |
18-32 VDC allowed |
| |
Positive, Negative, GND Terminals |
| |
2.5 mm screwdriver blade |
Current Load
|
500 mA max@ 32 VDC max |
| Operating Temperature |
-20 to 50 Deg C |
| |
-4 to 122 Deg F |
|
Storage Temperature |
-40 to 85 Deg C |
| |
-40 to 185 Deg F |
| Relative Humidity |
5-95% (w/o condensation) |
| Dimensions |
Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD |
|
LED Indicators |
Power and Module Status |
| |
Application Status |
| |
Serial Port Activity LED |
| |
Serial Activity and Error LED Status |
| Configuration Serial Port |
Mini-DIN |
| |
RS-232 only |
| |
No hardware handshaking |
|
Ethernet Port |
10Base-T Connector |
| |
Link and Activity LED indicators |
| |
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 |
| |
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration |
|
Application Serial Ports |
Mini-DIN |
| |
RS-232/422/485 |
| |
RS232 handshaking configurable |
| |
RS422/485 screw termination included |
|
Port Isolation |
2500V Opto-Isolators |
| |
500V Power Supply Isolation |
|
Shipped with each unit |
Mini-DIN to DB-9M cables per serial port |
| |
4 ft RS-232 configuration cable |
| |
2.5mm screwdriver |
| |
CD (docs and Configuration utility) |
| |
RS-422/485 DB9 to Screw Terminal |
| |
Adaptor (1 or 4, depending on ports) |
Click here for dimensions diagram Certifications
The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class 1, Div 2
Ordering Information
|
5201-DFNT-MNET
|
EtherNet/IP to Modbus TCP/IP
|
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.