PROFIBUS DP Slave to HART Multi-drop Communication Module
5507-PDPS-HART
Product Description
The ProLinx family PROFIBUS DP Slave to HART Multi-drop communications module (5507-PDPS-HART) creates a powerful connection between devices on a PROFIBUS DP network and HART field devices. The module is a stand-alone DIN rail-mounted protocol gateway that provides one PROFIBUS DP Slave configurable DB9F port and 4 configurable HART Multi-drop channels.
The PROFIBUS DP Slave (PDPS) protocol interface supports the PROFIBUS V0 Slave implementation protocol, providing powerful data transfer capability between the ProLinx module and Siemens PLCs or other hosts. User configurable data mapping and DP port operation make the interface an easy to use and powerful data transfer tool.
The HART protocol driver works as a Master on four (HART) or eight channels (HART2 – not available on certain configurations) per interface card, depending on implementation. Each channel is individually configurable.
Product Applications
The PDPS-HART modules are the ideal solution for the many applications where PROFIBUS DP connectivity can be used to integrate HART Multi-drop devices into a system.
The PROFIBUS DP Slave gateway is a powerful module designed with Slave support, enabling easy connection to PROFIBUS master devices. In combination with the HART support, the module provides a very powerful interface to the more than two million HART devices which are in use in the industrial marketplace today. Applications for the module are found in most industries, especially the Manufacturing, Oil and Gas, Electrical Power and Food Processing.
Functional Specifications
Internal Database
The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.
The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.
Application Data Area
The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.
Status Data Area
This area is used to store error codes, counters, and port status information for each port.
Configuration Data Area
This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.
PROFIBUS DP Slave Specifications
The PROFIBUS DP Slave driver gives access to the ProLinx unit's internal database via 200 bytes of Input data and 200 bytes of Output data. These Input and Output data blocks are mapped by the user within the ProLinx module's data memory allowing the user maximum flexibility and data transfer with other protocols.
|
General Parameters
|
|
GSD File
|
PRLX05A5.GSD Downloadable from ftp site
|
|
PROFIBUS Specifications
|
|
Communication parameters
|
Baud Rate: 9.6 kbit/s - 12 Mbit/s
|
|
Supported I/O length
|
200 bytes Input data 200 bytes Output data
|
|
Supported PROFIBUS DP features
|
PROFIBUS V0 Slave using Siemens SPC3 chipset
Freeze Mode
Sync Mode Auto Baud Setting
|
|
Configurable Parameters
|
- PROFIBUS Node Address: 1 to 125
- Data byte swapping
- Action on loss of PROFIBUS connection
- Comm Fail Timeout Multiplier - Status Data location in Internal Database
|
|
Status Data
|
Status data is available through the debug menu. The status information includes diagnostic data, input and output counters and module state.
|
Important Note: The slave node address is set to 126 by default in the module configuration file. The default node address must be changed to a valid address between 1-125 by the user for the slave to function on the PROFIBUS network.
HART Specifications
The HART Master Protocol exists in 4 and 8 channel configurations depending on hardware configuration for the second protocol:
- 4 or 8 HART channels if second protocol is serial
- For other protocols, 4 HART channels
This driver can be configured on an individual channel basis to operate as a HART Master Station and supports all the available HART commands including Universal, Common Practice and Device Specific Commands. Each HART channel is independently configured to interface with the internal database in the module.
The auto-poll mode allows the module to automatically collect data from each HART instrument on the channel and store the data in the module's database without the use of user commands. The module automatically generates HART commands 0, 3, 13, 14 and 15.
|
General Parameters (Software Configurable)
|
|
Type
|
Specifications
|
|
Communication parameters
|
Number of HART Preambles: 2 to 50
Enable Handheld: Y or N Primary Master: Y or N
|
|
Configurable Parameters per Channel
|
Auto-Poll Enable
Short Address Retries
Long Address Retries
Retries After Error
Poll Time After Error
Number of Commands Slave List Error Pointer
|
|
HART Driver
|
|
Type
|
Specifications
|
|
HART Commands supported
|
Universal Command Set
00 Read Unique Identifier
01 Read Primary Variable
02 Read Current And Percent Of Range
03 Read Dynamic Variables
06 Write Polling Address
11 Read Unique Identifier Associated With Tag
12 Read Message
13 Read Tag Descriptor Date
14 Read PV Sensor Info
15 Read Output Information
16 Read Final Assembly Number
17 Write Message
18 Write Tag Descriptor Date 19 Write Final Assembly Number
Common Practice Command Set
33 Read Transmitter Variables
34 Write Damping Value
35 WriteRange Values
36 SetUpperRange Value
37 SetLowerRange Value
38 Reset Configuration Changed Flag
39 EEprom Control
40 Enter Exit Fixed Current Mode
41 Perform Transmitter Self Test
42 Perform Master Reset
43 Set Pv Zero
44 Write Pv Units
45 Trim Dac Zero
46 Trim Dac Gain
47 Write Transfer Function
48 Read Additional Transmitter Status
49 Write Pv Sensor Serial Number
50 Read Dynamic Variable Assignments
51 Write Dynamic Variable Assignments
52 Set Transmitter Variable Zero
53 Write Transmitter Variable Units
54 Read Transmitter Variable Information
55 Write Transmitter Variable Damping Value
56 Write Transmitter Variable Sensor Serial Number
57 Read Unit Tag Descriptor Date
58 Write Unit Tag Descriptor Date
59 Write Number Of Response Preambles
108 Write Burst Mode Command Number
109 Burst Mode Control 110 Read All Dynamic Variables
|
|
Command List
|
Up to 100 command per channel, each fully configurable for function, slave address, register to/from addressing and word count for Floating Point or Integer Data
|
|
Status Data
|
Error codes returned by the HART protocol available on an individual command basis. In addition, a slave status list is maintained per active channel.
|
|
Polling of command list
|
User configurable polling of commands, including disabled, continuous, on change of data (write only) and dynamically user or automatic enabled.
|
Hardware Specifications
| Power Supply |
24 VDC nominal |
| |
18-32 VDC allowed |
| |
Positive, Negative, GND Terminals |
| |
2.5 mm screwdriver blade |
Current Load
|
500 mA max@ 32 VDC max |
| Operating Temperature |
-20 to 50 Deg C |
| |
-4 to 122 Deg F |
|
Storage Temperature |
-40 to 85 Deg C |
| |
-40 to 185 Deg F |
| Relative Humidity |
5-95% (w/o condensation) |
| Dimensions |
Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD |
|
LED Indicators |
Power and Module Status |
| |
Application Status |
| |
Serial Port Activity LED |
| |
Serial Activity and Error LED Status |
| Configuration Serial Port |
Mini-DIN |
| |
RS-232 only |
| |
No hardware handshaking |
|
Ethernet Port |
10Base-T Connector |
| |
Link and Activity LED indicators |
| |
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 |
| |
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration |
|
Application Serial Ports |
Mini-DIN |
| |
RS-232/422/485 |
| |
RS232 handshaking configurable |
| |
RS422/485 screw termination included |
|
Port Isolation |
2500V Opto-Isolators |
| |
500V Power Supply Isolation |
|
Shipped with each unit |
Mini-DIN to DB-9M cables per serial port |
| |
4 ft RS-232 configuration cable |
| |
2.5mm screwdriver |
| |
CD (docs and Configuration utility) |
| |
RS-422/485 DB9 to Screw Terminal |
| |
Adaptor (1 or 4, depending on ports) |
|
PROFIBUS Connector
|
DB-9F Standard PROFIBUS connector
|
|
PROFIBUS LED Indicators
|
Active - Green
|
|
|
Error - Red
|
|
HART Connector
|
12 pos screw-terminal plug (J212)
|
|
|
Termination Resistor Packet (4 resistors)
|
|
HART LED Indicators
|
CH1-4
|
Click here for dimensions diagram Certifications
The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class 1, Div 2
PNO Certified - PROFIBUS Test Center