Product Description

The ProLinx family A-B Remote I/O Adapter to DNP 3.0 Slave communications module (5601-RIO-DNPS) creates a powerful connection between devices on a Remote I/O network and DNP devices. The module is a stand-alone DIN-rail mounted protocol gateway that provides one configurable serial port and one RIO port.

The RIO interface is an adapter (slave) which can be connected to a scanner (master) that controls the data transfer. The module also supports limited high speed data transfer via the Input and Output images.

The DNP 3.0 Slave protocol driver supports Slave implementations of the protocol on one port. This port is fully configurable, providing a great deal of flexibility.

Product Applications

The RIO-DNPS modules are the ideal solution for the many applications where Remote I/O connectivity can be used to integrate DNP serial devices into a system. The RIO gateway is a powerful module designed with both Client and Server support, enabling easy connection to Rockwell Automation PLCs (CLX, SLC, PLC, CPLX, and similar devices). In combination with the DNP device support, the module provides a very powerful interface to the many DNP devices which are in use in the industrial marketplace today. Applications for the module are found in most industries, especially the Manufacturing, Oil and Gas, Electrical Power and Food Processing.

Functional Specifications

Internal Database

The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.

The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.

Application Data Area

The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.

Status Data Area

This area is used to store error codes, counters, and port status information for each port.

Configuration Data Area

This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.

A-B Remote I/O Adapter Specifications

The RIO interface is an adapter (slave) and is connected to a scanner (master) that controls the data transfer.

As an example, the master/slave relationship can be accomplished using the 460X-RIO-XXX module (adapter/slave unit) with an Allen-Bradley PLC5 (scanner/master unit). Ladder logic must be programmed into a PLC to perform BTR/BTW commands to receive and transmit data between the module and the PLC. The module also supports limited high speed data transfer via the Input and Output images.

Software Configurable Parameters

Rack Number Addressing

0 to 63

Rack Size

1/4-rack, 1/2-rack, 3/4-rack and full rack

Starting Group

0,2,4,6

Last Rack

Yes or No

Baud Rate

57.6K, 115K, 230K

Functional Specifications

Supports block-transfers of data with scanner

Supports I/O data movement. Amount determined by rack size configuration

BTW Command - up to 64 words

BTR Command - up to 63 words

Physical Connection

Remote I/O connector

Standard 3-screw termination connector.

DNP 3.0 Slave Protocol Specifications

The DNP 3.0 Slave driver provides extensive support for Slave implementations of the protocol. The serial port on the gateway is user-configurable to support the DNP 3.0 protocol (Slave, Error Checking, Baud rate, etc).

General Parameters

Internal Database

Binary Inputs: 0-100 word count
Analog Inputs:0-100 points of analog input data
Float Inputs:250 points
Double Inputs: 125 points
Counters:0-50 points of counter data
Binary Outputs: 0-100 word count
Analog Outputs: 0-100 points of analog output
Float Outputs: 250 points
Double Outputs: 125 points
Binary Input Events : 0-100 binary input event buffer
Analog Input Events: 0-100 analog input event buffer

Communication parameters

Baud Rate: 110 to 115K baud

Stop Bits : 1

Data Size: 8 bits

Parity: None

RTS Timing delays: 0 to 65535 ms

DNP Mode

DNP 3.0 Slave - Level 2

DNP Slave

Node address

0 to 65534 - software selectable

Status Data

Error codes, counters and port status available per configured slave port

Hardware Specifications

Power Supply 24 VDC nominal
  18-32 VDC allowed
  Positive, Negative, GND Terminals
  2.5 mm screwdriver blade

Current Load

500 mA max@ 32 VDC max
Operating Temperature -20 to 50°C
  -4 to 122°F
Storage Temperature -40 to 85°C
  -40 to 185°F
Relative Humidity 5% to 95% (non-condensing)
Dimensions

Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD

LED Indicators

Power and Module Status

  Application Status
  Serial Port Activity LED
  Serial Activity and Error LED Status
Configuration Serial Port DB-9M RS-232 only
  No hardware handshaking
Ethernet Port
(Ethernet protocol gateways only)
10Base-T half duplex RJ45 Connector
  Link and Activity LED indicators
  Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991
  Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
Application Serial Ports (Serial protocol gateways only) RS-232/422/485
  RS232 handshaking configurable
  RS-422/485 DB-9 to Screw Terminal Adaptor
  Note: The number of serial application ports depends on the module type, and the combination of protocols.
Serial Port Isolation 2500V RMS port signal isolation per UL 1577
  3000V DC min. isolation port to ground and port to logic
Shipped with each unit Mini-DIN to DB-9M serial cables
  4 ft RS-232 configuration cable
  2.5mm screwdriver
  CD (docs and Configuration utility)
  RS-422/485 DB-9 to Screw Terminal Adaptor for each serial application port (serial protocols only)

RIO Connector

3 pos screw-terminal adaptor(J803)

RIO LED Indicators

Active - Green

Click here for dimensions diagram

Certifications

The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class I, Div 2


Ordering Information

5601-RIO-DNPS

A-B Remote I/O Adapter to DNP 3.0 Slave

To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe/Middle East/Africa
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

Image Gallery



Home : Products : Support : Distributors : Services : News/Events : Contact : ProSoft Tested