Modbus Plus to A-B Remote I/O Adapter Communication Module
5310-MBP-RIO
Product Description
The ProLinx family Modbus Plus to A-B Remote I/O Adapter communications module (5310-MBP-RIO) creates a powerful connection between devices on a Modbus Plus network and a Remote I/O device. The module is a stand-alone DIN-rail mounted protocol gateway that provides one Modbus Plus configurable DB9F port and Remote I/P port.
The Modbus Plus protocol driver exists in dual Modbus Plus Ports (MBP). The driver can be configured on an individual port basis as either a master or a slave to interface with other Modbus Plus devices. The Modbus port is fully configurable, providing a great deal of flexibility.
The RIO interface is an adapter (slave) which can be connected to a scanner (master) that controls the data transfer. The module also supports limited high speed data transfer via the Input and Output images.
Product Applications
The MBP-RIO modules are the ideal solution for the many applications where Modbus Plus connectivity can be used to integrate a Remote I/O device into a system.
The Modbus Plus gateway is a powerful module designed with both Master and Slave support, enabling easy connection to other Modbus devices (Modicon processors and many others). In combination with the Remote I/O support, the module provides a very powerful interface to the many Remote I/O devices which are in use in the industrial marketplace today. Applications for the module are found in most industries, especially the Manufacturing, Oil and Gas, Electrical Power and Food Processing.
Functional Specifications
Internal Database
The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.
The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.
Application Data Area
The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.
Status Data Area
This area is used to store error codes, counters, and port status information for each port.
Configuration Data Area
This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.
Modbus Plus Port Specifications
The Modbus Plus protocol driver exists in dual Modbus Plus Ports (MBP). The driver can be configured on an individual port basis as either a master or a slave to interface with other Modbus Plus devices.
|
General Parameters
|
|
Modbus Function Codes
|
3 : Read Multiple Data Registers (MSTR 2)
16 : Write Multiple Data Register (MSTR 1)
Global data read (32 words max.)
Global data write (32 words max.)
|
|
Address Scope
|
1-64
|
|
Modbus Plus Functioning as a Master
|
|
Command List
|
Up to 200 commands on the master port, fully configurable for function, slave address, register to/from addressing and word count
|
|
Status Data
|
Error codes available on an individual command basis. In addition, a slave status list is maintained per active Modbus Master port.
|
|
Polling of command list
|
Configurable polling of command list, including continuous and on change of data
|
|
Modbus Plus Functioning as a Slave
|
|
Node address
|
1 to 64 - software selectable
|
|
Status Data
|
Error codes, counters and port status available on the configured slave port
|
A-B Remote I/O Adapter Specifications
The RIO interface is an adapter (slave) and is connected to a scanner (master) that controls the data transfer.
As an example, the master/slave relationship can be accomplished using the 460X-RIO-XXX module (adapter/slave unit) with an Allen-Bradley PLC5 (scanner/master unit). Ladder logic must be programmed into a PLC to perform BTR/BTW commands to receive and transmit data between the module and the PLC. The module also supports limited high speed data transfer via the Input and Output images.
|
Software Configurable Parameters
|
|
Rack Number Addressing
|
0 to 63
|
|
Rack Size
|
¼-rack, ½-rack, ¾-rack and full rack
|
|
Starting Group
|
0,2,4,6
|
|
Last Rack
|
Yes or No
|
|
Baud Rate
|
57.6K, 115K, 230K
|
|
Functional Specifications
|
|
Supports block-transfers of data with scanner
|
|
Supports I/O data movement. Amount determined by rack size configuration
|
|
BTW Command - up to 64 words
|
|
BTR Command - up to 63 words
|
|
Physical Connection
|
|
Remote I/O connector
|
Standard 3-screw termination connector.
|
Hardware Specifications
| Power Supply |
24 VDC nominal |
| |
18-32 VDC allowed |
| |
Positive, Negative, GND Terminals |
| |
2.5 mm screwdriver blade |
Current Load
|
500 mA max@ 32 VDC max |
| Operating Temperature |
-20 to 50 Deg C |
| |
-4 to 122 Deg F |
|
Storage Temperature |
-40 to 85 Deg C |
| |
-40 to 185 Deg F |
| Relative Humidity |
5-95% (w/o condensation) |
| Dimensions |
Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD |
|
LED Indicators |
Power and Module Status |
| |
Application Status |
| |
Serial Port Activity LED |
| |
Serial Activity and Error LED Status |
| Configuration Serial Port |
Mini-DIN |
| |
RS-232 only |
| |
No hardware handshaking |
|
Ethernet Port |
10Base-T Connector |
| |
Link and Activity LED indicators |
| |
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 |
| |
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration |
|
Application Serial Ports |
Mini-DIN |
| |
RS-232/422/485 |
| |
RS232 handshaking configurable |
| |
RS422/485 screw termination included |
|
Port Isolation |
2500V Opto-Isolators |
| |
500V Power Supply Isolation |
|
Shipped with each unit |
Mini-DIN to DB-9M cables per serial port |
| |
4 ft RS-232 configuration cable |
| |
2.5mm screwdriver |
| |
CD (docs and Configuration utility) |
| |
RS-422/485 DB9 to Screw Terminal |
| |
Adaptor (1 or 4, depending on ports) |
|
RIO Connector
|
3 pos screw-terminal adaptor(J803)
|
|
RIO LED Indicators
|
Active - Green
|
Click here for dimensions diagram Certifications
The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class 1, Div 2
Ordering Information
|
5310-MBP-RIO
|
Modbus Plus to A-B Remote I/O Adapter
|
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.
Distributors: