Modbus TCP/IP to PROFIBUS DPV1 Master Communication Module
5204-MNET-PDPMV1
Product Description
The MNET-PDPMV1 modules are the ideal solution for the many applications where Modbus TCP/IP connectivity can be used to integrate a PROFIBUS DP slave device into a system.
The Modbus TCP/IP (MNET) driver can be used to interface many different protocols into the Schneider Electric Quantum family of processors as well other software solutions supporting the protocol. The MNET driver supports Client connections as well as Server connections.
The PROFIBUS DP Master protocol driver (PDPMV1) supports complete Master specifications according to IEC 61158 on either a Mono-Master or Multi-Master network. The module supports the DPV1 specification.
Product Applications
The MNET-PDPMV1 modules are the ideal solution for the many applications where Modbus TCP/IP connectivity can be used to integrate a PROFIBUS DP slave device into a system.
The Modbus TCP/IP gateway is a powerful module designed with both Client and Server support, enabling easy connection to other Modbus devices (Modicon processors and many others). In combination with the PROFIBUS DP V1 Master device support, the module provides a very powerful interface to the many PROFIBUS slave devices which are in use in the industrial marketplace today. Applications for the module are found in most industries, especially the Manufacturing, Oil and Gas, Electrical Power and Food Processing
.
Functional Specifications
Internal Database
The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.
The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.
Application Data Area
The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.
Status Data Area
This area is used to store error codes, counters, and port status information for each port.
Configuration File
This file contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, the module.
Modbus TCP/IP Protocol Specifications
The Ethernet driver interfaces with a common internal database in the module. This permits the sharing of data across many different protocols and networks.
Modbus TCP/IP Port Specifications
Server
The MNET module supports server functionality using the reserved Modbus TCP/IP service port 502, as well as service port 2000 to support the TCP/IP encapsulated Modbus protocol that is supported by several HMI manufacturers. Services supported in the module permit client applications (i.e., HMI software packages, Quantum processors, etc.) to read from and write to the module's database.
Data in the module's internal database is accessible for read and write operations by any node on the network supporting the MBAP (service port 502) or MNET (service ports 2000/2001) TCP/IP protocols.
There is no configuration of the MNET module required to implement Server functionality other than setting up the network and database parameters in the user configuration file.
|
Modbus TCP/IP Server
|
|
Type
|
Specification
|
|
General
|
The server driver supports connections to Modbus TCP/IP clients supporting Service Port 502 using the standard MBAP protocol, and clients supporting Modbus on Service Port 2000. - Supports up to five (5) independent server connections for Service Port 502
- Supports up to five (5) independent server connections for Service Port 2000
|
|
Configurable Parameters
|
Module IP Address Modbus address offsetting
|
|
Modbus Commands supported
|
1 : Read Output Status
2 : Read Input Status
3 : Read Multiple Data Registers
4 : Read Input Registers
5 : Write Single Bit
6 : Write Single Data Register
15 : Write Multiple Bits 16 : Write Multiple Data Register
|
Client
The module supports a client connection on the TCP/IP network to interface with processors (and other server based devices) using a user constructed command list of up to 100 entries.
|
Modbus TCP/IP Client
|
|
Type
|
Specification
|
|
General
|
The client driver supports the active reading and writing of data with Modbus TCP/IP compatible devices.
- One client connection available (connect up to 100 servers/devices with 100 commands)
|
|
Configurable parameters
|
Number of active commands (Up to 100 for client)
Min Command Delay
Response Timeout
Retry Count Command Error Pointer
|
|
Modbus Commands supported
|
1 : Read Output Status
2 : Read Input Status
3 : Read Multiple Data Registers
4 : Read Input Registers
5 : Write Single Bit
6 : Write Single Data Register
15 : Write Multiple Bits 16 : Write Multiple Data Register
|
|
Command List
|
Up to 100 commands on the Client port, each fully configurable for function, Server IP address, Service Port, register to/from addressing and word/bit count
|
|
Status Data
|
Error codes available on an individual command basis.
|
|
Polling of command list
|
User configurable polling of commands, including disabled, continuous and on change of data (write only)
|
PROFIBUS DP V1 Master Protocol Specifications
The module supports complete Master specifications according to IEC 61158. Acyclic parameter data can be transferred with Class 1 or Class 2 DPV1 services, allowing processors to easily communicate with slave devices supporting PROFIBUS DPV0/V1 protocol.
The ProLinx PDPMV1 PROFIBUS Master module acts as a PROFIBUS network scanner, transferring Input and Output data between PROFIBUS devices and the network.
- Master Busview configuration interface via included ProSoft Configuration Builder software (see PSW-PCB)
- Project-unique GSD file import library
- Monitoring and Modification of process data and DPV1 acyclic data
- Multi-drop on a PROFIBUS DPV1 network drop with other compatible devices
- Ability to be used with a repeater as a PROFIBUS Master with PROFIBUS PA slaves on the network
- Automatic project documentation
- Automatic Bus Parameter calculation
- Online slave diagnostics
- Supports all standardized baud rates, up to 12Mbps
- Supports extended diagnostic data (DPV1)
- Auto baud detection at all valid PROFIBUS DPV1 rates
- Multiple modules can be placed in a single rack
- CRC checksum determination of slave configuration consistency to processor
- Master Status LED Indicators for Operations, Network Drop Communication, Master Token-Hold
- FDT/DTM PROFIBUS master transport communication DTM software included (see PSW-CDTM-PDPM)
PROFIBUS Master Specifications
- Up to 125 Slaves can be connected with a repeater
- Up to 1536 cyclic bytes (768 words) input and 1536 bytes (768 words) output data
- Supports Extended Diagnostic Data
- RS-485 optically isolated PROFIBUS Interface with on board DC-DC converter
- Acyclic communications (DPV1), Read and Write
- Alarm Handling (DPV1)
- Supports Sync and Freeze commands
- Supports PROFIdrive 3.1 compliant parameter read and write operations
- Supports Multicast and Broadcast telegrams (DPV1)
PROFIBUS Master Port
- DB-9F Optically Isolated RS-485
- Ready, Run, Error and Token LED Indicators
- PROFIBUS DPV1 RS-485 interface with a 9-pin D shell female connector and isolated Opto-Couplers
Hardware Specifications
| Power Supply |
24 VDC nominal |
| |
18-32 VDC allowed |
| |
Positive, Negative, GND Terminals |
| |
2.5 mm screwdriver blade |
Current Load
|
500 mA max@ 32 VDC max |
| Operating Temperature |
-20 to 50°C |
| |
-4 to 122°F |
|
Storage Temperature |
-40 to 85°C |
| |
-40 to 185°F |
| Relative Humidity |
5% to 95% (non-condensing) |
| Dimensions |
Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD |
|
LED Indicators |
Power and Module Status |
| |
Application Status |
| |
Serial Port Activity LED |
| |
Serial Activity and Error LED Status |
| Configuration Serial Port |
DB-9M RS-232 only |
| |
No hardware handshaking |
Ethernet Port (Ethernet protocol gateways only) |
10Base-T half duplex RJ45 Connector |
| |
Link and Activity LED indicators |
| |
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 |
| |
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration |
|
Application Serial Ports (Serial protocol gateways only) |
RS-232/422/485 |
| |
RS232 handshaking configurable |
| |
RS-422/485 DB-9 to Screw Terminal Adaptor |
| |
Note: The number of serial application ports depends on the module type, and the combination of protocols. |
|
Serial Port Isolation |
2500V RMS port signal isolation per UL 1577 |
| |
3000V DC min. isolation port to ground and port to logic |
|
Shipped with each unit |
Mini-DIN to DB-9M serial cables |
| |
4 ft RS-232 configuration cable |
| |
2.5mm screwdriver |
| |
CD (docs and Configuration utility) |
| |
RS-422/485 DB-9 to Screw Terminal Adaptor for each serial application port (serial protocols only) |
|
PROFIBUS Connector
|
DB-9F Standard PROFIBUS connector
|
|
PROFIBUS LED Indicators
|
Tkn - Green
|
|
|
Err - Red
|
|
|
Rdy - Green
|
|
|
Run - Green
|
Click here for dimensions diagram
Ordering Information
|
5204-MNET-PDPMV1
|
Modbus TCP/IP to PROFIBUS DP V1 Master
|