PROFIBUS Master for Modicon Modbus TCP/IP
5204SE-MNET-PDPMV1
Product Description
Automating integration for Schneider Electric (SE) Modicon processors and maximizing ease-of-use are the hallmark design criteria behind the new ProLinx SE line of communication gateways. The first SE gateway, the 5204SE-MNET-PDPMV1 Modbus TCP/IP to PROFIBUS DP-V1 Master gateway, easily turns a Modicon M340 or a Quantum Programmable Automation Controller (PAC) into a PROFIBUS DPV1 Master. The new Application Communication Logic functions built into ProSoft Configuration Builder (PCB) automatically generate all the Unity Pro data types, variables, and logic required for the M340 or Quantum to perform PROFIBUS DPV1 cyclic and acyclic communication.
PCB automatically generates customized export files based on the PROFIBUS DP network configuration for the gateway. These files import into Unity Pro version 4 software without modification, eliminating the need to write additional communications message logic.
Automatically-generated Derived Function Block logic also provides advanced PROFIBUS DPV1 acyclic message pass-through capability. Acyclic messaging allows an M340 or Quantum to request extended slave data and diagnostics, as well as access slave-specific special functions.
Product Applications
|
Features
|
Benefits
|
|
New Application Communication Logic functions for use with Modicon M340 or Quantum PACs
|
-
Designed specifically to enable a Modicon M340 or QuantumPAC using Modbus TCP/IP to act as a PROFIBUS DPV1 Master
-
Generates Unity Pro version 4.0 DFB logic and variable files from gateway configuration
-
Automates the creation of application communication logic
-
Ease-of-use means faster deployment, less engineering effort, fewer programming errors
|
|
Acyclic Pass-Through Capability
|
-
Automatically generated DFBs enable advanced PROFIBUS DPV1 acyclic messaging with minimal engineering and programming effort
-
Acyclic messaging allows a M340 or Quantum PAC to communicate directly with PROFIBUS DP slaves, to access special slave features, and to get extended slave diagnostics and process data
|
|
Backed by ProSoft Technology
|
-
20-year history of delivering high-quality, reliable solutions designed with you in mind
-
Free, unlimited, worldwide Technical Support by phone for pre-sale, set-up, or troubleshooting support helps you get going sooner and stay running longer
-
Three-Year Warranty ensures reliability and protects against equipment failures
-
Free ProSoft Software tools tightly integrate with our hardware...a simple and quick, total solution to help you make our products fit your applications
|
|
Configuration
|
|
ProSoft Configuration Builder (PCB) with new Application Communication Logic functions provides a PC-based software configuration solution for managing gateway configuration files, viewing communication status, monitoring network diagnostics, and password-protecting configuration downloads. The 5204SE-MNET-PDPMV1 User Manual provides step-by-step instructions on how to move data from one network to the other. Whenever the PROFIBUS DP network configuration changes, new logic files can be automatically created, exported, and imported into an existing project, reducing engineering demands and cutting deployment time. Changes to gateway configuration can be password-protected.
|
Functional Specifications
Internal Database
The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.
The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.
Application Data Area
The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.
Status Data Area
This area is used to store error codes, counters, and port status information for each port.
Configuration File
This file contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, the module.
Hardware Specifications
| Power Supply |
24 VDC nominal |
| |
18-32 VDC allowed |
| |
Positive, Negative, GND Terminals |
| |
2.5 mm screwdriver blade |
Current Load
|
500 mA max@ 32 VDC max |
| Operating Temperature |
-20 to 50°C |
| |
-4 to 122°F |
|
Storage Temperature |
-40 to 85°C |
| |
-40 to 185°F |
| Relative Humidity |
5% to 95% (non-condensing) |
| Dimensions |
Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD |
|
LED Indicators |
Power and Module Status |
| |
Application Status |
| |
Serial Port Activity LED |
| |
Serial Activity and Error LED Status |
| Configuration Serial Port |
DB-9M RS-232 only |
| |
No hardware handshaking |
Ethernet Port (Ethernet protocol gateways only) |
10Base-T half duplex RJ45 Connector |
| |
Link and Activity LED indicators |
| |
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 |
| |
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration |
|
Application Serial Ports (Serial protocol gateways only) |
RS-232/422/485 |
| |
RS232 handshaking configurable |
| |
RS-422/485 DB-9 to Screw Terminal Adaptor |
| |
Note: The number of serial application ports depends on the module type, and the combination of protocols. |
|
Serial Port Isolation |
2500V RMS port signal isolation per UL 1577 |
| |
3000V DC min. isolation port to ground and port to logic |
|
Shipped with each unit |
Mini-DIN to DB-9M serial cables |
| |
4 ft RS-232 configuration cable |
| |
2.5mm screwdriver |
| |
CD (docs and Configuration utility) |
| |
RS-422/485 DB-9 to Screw Terminal Adaptor for each serial application port (serial protocols only) |
Click here for dimensions diagram Certifications
The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class I, Div 2
Ordering Information
|
5204SE-MNET-PDPMV1
|
Modbus TCP/IP for Schneider Electric to PROFIBUS DPV1 Master
|