ProSoft Technology, Inc.
Home > Products > Stand-alone Gateways > Serial > ASCII > ASCII Generic Serial to PROFIBUS DP Slave Communication Module
Printable Page
 

Search | Clear


ASCII Generic Serial to PROFIBUS DP Slave Communication Module

5105-ASCII-PDPS

Product Description

The ProLinx family ASCII Generic Serial to PROFIBUS DP Slave communications module (5105-ASCII-PDPS) creates a powerful connection between a PROFIBUS DP master device and an ASCII input device. The module is a stand-alone DIN-rail mounted protocol gateway that provides one PROFIBUS DP Slave port and one ASCII configurable serial port.

The ASCII protocol driver permits the module to interface to many ASCII devices. Each ASCII port on the module is configurable to send and/or receive ASCII strings, each supporting its own individual serial network.

The PROFIBUS DP Slave (PDPS) protocol interface supports the PROFIBUS V0 Slave implementation protocol, providing powerful data transfer capability between the ProLinx module and Siemens PLCs or other hosts. User configurable data mapping and DP port operation make the interface an easy to use and powerful data transfer tool.

Product Applications

The ASCII-PDPS modules are the ideal solution for the many applications where PROFIBUS DP Slave connectivity can be used to integrate an ASCII generic serial input device into a system. The PROFIBUS DP Slave gateway is a powerful module designed with Slave support, enabling easy connection to a PROFIBUS master device. In combination with the ASCII device support, the module provides a very powerful interface to the many ASCII input devices which are in use in the industrial marketplace today. Applications for the module are found in most industries, especially the Manufacturing, Oil and Gas, Electrical Power and Food Processing .

Functional Specifications

Internal Database

The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.

The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.

Application Data Area

The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.

Status Data Area

This area is used to store error codes, counters, and port status information for each port.

Configuration Data Area

This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.

ASCII Serial Specifications

The ASCII driver provides a powerful connection between the internal application database in the ProLinx unit and devices supporting serial ASCII communications (bar code scanners, line printers, legacy terminal based computer systems, etc).

The serial port on the gateway is user-configurable to support ASCII communications (Baud rate, Data Bits, Stop Bits, etc). The ASCII port can act as a Master (Send ASCII strings) or as a Slave(Receive ASCII strings), or both.

When configured to send data strings, the transmission of characters strings is easily accomplished by the placement of string data in the module's application database, followed by toggling of a transmit control word. When the ASCII Serial driver detects a change in the transmit control word, the string is sent out the port.

When configured to receive data strings, the module buffers the data until the termination condition is satisfied (as configured by the user) and the receive string is then copied into the module's application data space, with the actual character count value leading the ASCII string data.

The following table provides specifications for the configuration and functionality available on the ASCII serial ports:

ASCII Specifications

Ports

Available in up to four port configurations to receive and/or transmit data.

Receive buffer size

255 bytes

Receive termination

Stream mode, termination characters, message timeout, inter-character delay, or packet size length.

Receive database location

-1 = disable receiver, 0 to 3896

Transmit buffer size

255 bytes

Transmit character with pacing

0 to 65535 millisecond delay between each transmitted character.

Transmit database location

-1 = disable transmitter, 0 to 3896

Communication Configuration

Baud rate

110 to 115,200

Parity

None, Odd, Even

Data bits

7 to 8

Stop bits

1 or 2

RTS On and Off Timing

0 to 65535 milliseconds

Minimum Response Delay

0 to 65535 milliseconds

Hardware or software handshaking

None, RTS/CTS, DTR/DSR, or XON/XOFF

PROFIBUS DP Slave Specifications

The PROFIBUS DP Slave driver gives access to the ProLinx unit's internal database via 200 bytes of Input data and 200 bytes of Output data. These Input and Output data blocks are mapped by the user within the ProLinx module's data memory allowing the user maximum flexibility and data transfer with other protocols.

General Parameters

GSD File

PRLX05A5.GSD
Downloadable from ftp site

PROFIBUS Specifications

Communication parameters

Baud Rate: 9.6 kbit/s - 12 Mbit/s

Supported I/O length

200 bytes Input data
200 bytes Output data

Supported PROFIBUS DP features

PROFIBUS V0 Slave using Siemens SPC3 chipset
Freeze Mode
Sync Mode
Auto Baud Setting

Configurable Parameters

- PROFIBUS Node Address: 1 to 125
- Data byte swapping
- Action on loss of PROFIBUS connection
- Comm Fail Timeout Multiplier
- Status Data location in Internal Database

Status Data

Status data is available through the debug menu. The status information includes diagnostic data, input and output counters and module state.

Important Note: The slave node address is set to 126 by default in the module configuration file. The default node address must be changed to a valid address between 1-125 by the user for the slave to function on the PROFIBUS network.

Hardware Specifications

Power Supply 24 VDC nominal
  18-32 VDC allowed
  Positive, Negative, GND Terminals
  2.5 mm screwdriver blade

Current Load

500 mA max@ 32 VDC max
Operating Temperature -20 to 50 Deg C
  -4 to 122 Deg F
Storage Temperature -40 to 85 Deg C
  -40 to 185 Deg F
Relative Humidity 5-95% (w/o condensation)
Dimensions

Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD

LED Indicators

Power and Module Status

  Application Status
  Serial Port Activity LED
  Serial Activity and Error LED Status
Configuration Serial Port Mini-DIN
  RS-232 only
  No hardware handshaking
Ethernet Port 10Base-T Connector
  Link and Activity LED indicators
  Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991
  Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
Application Serial Ports Mini-DIN
  RS-232/422/485
  RS232 handshaking configurable
  RS422/485 screw termination included
Port Isolation 2500V Opto-Isolators
  500V Power Supply Isolation
Shipped with each unit Mini-DIN to DB-9M cables per serial port
  4 ft RS-232 configuration cable
  2.5mm screwdriver
  CD (docs and Configuration utility)
  RS-422/485 DB9 to Screw Terminal
  Adaptor (1 or 4, depending on ports)

PROFIBUS Connector

DB-9F Standard PROFIBUS connector

PROFIBUS LED Indicators

Active - Green

 

Error - Red

Click here for dimensions diagram

Certifications

The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class 1, Div 2

PNO Certified - PROFIBUS Test Center


Ordering Information

5105-ASCII-PDPS

ASCII Generic Serial to PROFIBUS DP Slave

To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

Image Gallery



Home : Products : Support : Distributors : Services : News/Events : Contact Us : ProSoft Tested