A-B Remote I/O Adapter to IEC60870-5-103 Master Communication Module
5601-RIO-103M
Product Description
The ProLinx family A-B Remote I/O Adapter to IEC60870-5-103 Master communications module (5601-RIO-103M) creates a powerful connection between devices on an IEC 103 network and a Remote I/O master or slave device. The module is a stand-alone DIN-rail mounted protocol gateway that provides one Remote I/O port and one IEC 103 Master configurable serial port.
The RIO interface is an adapter (slave) which can be connected to a scanner (master) that controls the data transfer. The module also supports limited high speed data transfer via the Input and Output images.
The IEC 60870-5-103 Master (103M) protocol driver works as a master to monitor and control up to 16 slaves. The serial port is user-configurable, providing a very powerful and flexible host or device interface solution.
Product Applications
The RIO-103M modules are the ideal solution for the many applications where IEC 103 Master connectivity can be used to integrate a Remote I/O master or slave device into a system.
The IEC60870-5-103 Master gateway is a powerful module designed with Master support, enabling easy connection to other IEC 103 devices. In combination with the Remote I/O device support, the module provides a very powerful interface to the many Remote I/O master or slave devices which are in use in the industrial marketplace today. Applications for the module are found in most industries, especially the Manufacturing, Oil and Gas, Electrical Power and Food Processing.
Functional Specifications
Internal Database
The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.
The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.
Application Data Area
The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.
Status Data Area
This area is used to store error codes, counters, and port status information for each port.
Configuration Data Area
This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.
A-B Remote I/O Adapter Specifications
The RIO interface is an adapter (slave) and is connected to a scanner (master) that controls the data transfer.
As an example, the master/slave relationship can be accomplished using the 460X-RIO-XXX module (adapter/slave unit) with an Allen-Bradley PLC5 (scanner/master unit). Ladder logic must be programmed into a PLC to perform BTR/BTW commands to receive and transmit data between the module and the PLC. The module also supports limited high speed data transfer via the Input and Output images.
|
Software Configurable Parameters
|
|
Rack Number Addressing
|
0 to 63
|
|
Rack Size
|
1/4-rack, 1/2-rack, 3/4-rack and full rack
|
|
Starting Group
|
0,2,4,6
|
|
Last Rack
|
Yes or No
|
|
Baud Rate
|
57.6K, 115K, 230K
|
|
Functional Specifications
|
|
Supports block-transfers of data with scanner
|
|
Supports I/O data movement. Amount determined by rack size configuration
|
|
BTW Command - up to 64 words
|
|
BTR Command - up to 63 words
|
|
Physical Connection
|
|
Remote I/O connector
|
Standard 3-screw termination connector.
|
IEC 60870-5-103 Master Protocol Specifications
The IEC 60870-5-103 Master driver provides extensive support for Master implementations of the protocol. The serial port on the gateway is user-configurable to support the IEC protocol (Master, Error Checking, Baud rate, etc).
The module supports:
- 16 slaves (sessions with distinct Data Link Addresses)
- Each slave (session) supports up to 3 sectors (with distinct Common ASDU Addresses)
- Configurable Time Synch and General Interrogation messages during initialization
- Supports General Interrogation, General Command and Time Synchronization Commands.
|
General Parameters - IEC 60870-5-103M Protocol
|
|
Type
|
Specifications
|
|
Communication parameters
|
Baud Rate: 110 to 115K baud
Stop Bits: 1 or 2
Data Size: 5 or 8 bits
Parity: None, Even, Odd RTS Timing delays: 0 to 65535 ms
|
|
IEC 60870-5-103 Master
|
|
Type
|
Specifications
|
|
Configurable Parameters
|
Baud Rate
Parity
RTS On
RTS Off
Minimum Delay
Receive Timeout
Data Link Address Common ASDU Address
|
|
Status Data
|
Status Data include: Command Delay, Command Queue Count, Online Status for Each Slave, Command Error, Number of Requests and Number of Responses.
|
Hardware Specifications
| Power Supply |
24 VDC nominal |
| |
18-32 VDC allowed |
| |
Positive, Negative, GND Terminals |
| |
2.5 mm screwdriver blade |
Current Load
|
500 mA max@ 32 VDC max |
| Operating Temperature |
-20 to 50°C |
| |
-4 to 122°F |
|
Storage Temperature |
-40 to 85°C |
| |
-40 to 185°F |
| Relative Humidity |
5% to 95% (non-condensing) |
| Dimensions |
Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD |
|
LED Indicators |
Power and Module Status |
| |
Application Status |
| |
Serial Port Activity LED |
| |
Serial Activity and Error LED Status |
| Configuration Serial Port |
DB-9M RS-232 only |
| |
No hardware handshaking |
Ethernet Port (Ethernet protocol gateways only) |
10Base-T half duplex RJ45 Connector |
| |
Link and Activity LED indicators |
| |
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 |
| |
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration |
|
Application Serial Ports (Serial protocol gateways only) |
RS-232/422/485 |
| |
RS232 handshaking configurable |
| |
RS-422/485 DB-9 to Screw Terminal Adaptor |
| |
Note: The number of serial application ports depends on the module type, and the combination of protocols. |
|
Serial Port Isolation |
2500V RMS port signal isolation per UL 1577 |
| |
3000V DC min. isolation port to ground and port to logic |
|
Shipped with each unit |
Mini-DIN to DB-9M serial cables |
| |
4 ft RS-232 configuration cable |
| |
2.5mm screwdriver |
| |
CD (docs and Configuration utility) |
| |
RS-422/485 DB-9 to Screw Terminal Adaptor for each serial application port (serial protocols only) |
|
RIO Connector
|
3 pos screw-terminal adaptor(J803)
|
|
RIO LED Indicators
|
Active - Green
|
Click here for dimensions diagram Certifications
The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class I, Div 2
Ordering Information
|
Standard Case
|
|
|
5601-RIO-103M
|
A-B Remote I/O Adapter to IEC60870-5-103 Master
|
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.