DNP over Ethernet to IEC60870-5-103 Master Communication Module
5201-DNPSNET-103M
Product Description
The ProLinx family DNP over Ethernet to IEC60870-5-103 Master communications module (5201-DNPSNET-103M) creates a powerful connection between devices on a DNP over Ethernet network and an IEC 103 slave device. The module is a stand-alone DIN-rail mounted protocol gateway that provides one Ethernet port and one IEC 103 Master configurable serial port.
The ProLinx module is capable of supporting the DNP 3.0 protocol as a server using the TCP and UDP protocols using service port 20000. This port is fully configurable, providing a great deal of flexibility.
The IEC 60870-5-103 Master (103M) protocol driver works as a master to monitor and control up to 16 slaves. The serial port is user-configurable, providing a very powerful and flexible host or device interface solution.
Product Applications
The DNPSNET-103M modules are the ideal solution for the many applications where DNP over Ethernet connectivity can be used to integrate an IEC 103 slave device into a system.
The DNP over Ethernet gateway is a powerful module designed with level 2 Server support, enabling easy connection to other DNP devices. In combination with the IEC 103 Master device support, the module provides a very powerful interface to the many IEC 103 slave devices which are in use in the industrial marketplace today. Applications for the module are found in most industries, especially the Manufacturing, Oil and Gas, Electrical Power and Food Processing
.
Functional Specifications
Internal Database
The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.
The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.
Application Data Area
The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.
Status Data Area
This area is used to store error codes, counters, and port status information for each port.
Configuration File
This file contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, the module.
DNPSNET Protocol Specifications
The DNPSNET protocol driver exists as a single service port (DNPSNET port 20000) implementation that supports a single TCP port connection and multiple UDP ports on a TCP/IP Ethernet network. The DNPSNET port operates as a server, supporting the DNP 3.0 protocol in a Level 2 implementation using the DNP User Group recommended extension for use on LAN/WAN. This is published in "Transporting DNP V3.00 over Local and Wide Area Networks", December 15, 1998 by the DNP Users Group and is available on the Internet at http://www.dnp.org.
The DNPSNET driver will respond to requests from a remote DNP client (master) device. All data in the module's database configured as DNP data points is available to the remote master device for read and write requests. Additionally, the driver can send unsolicited event messages to a connected, TCP, client.
|
General Parameters
|
|
Type
|
Specifications
|
|
Internal Database
|
Binary Inputs: 8000 points (500 words)
Analog Inputs:500 points of analog input data
Counters:250 (500 words)
Binary Outputs: 2000 points (125 words)
Analog Outputs: 500 points of analog output
|
|
DNP Mode
|
DNP 3.0 Slave - Level 2
|
|
DNP Object Support
|
Reference Appendix for full Object Definition document
|
|
DNP Server
|
|
Type
|
Specifications
|
|
ServicePort
|
20000
|
|
Protocols
|
TCP (1 connection) and UDP
|
|
Node address
|
0 to 65534 - software selectable
|
|
Status Data
|
Error codes, counters and port status
|
The DNPSNET module accepts DNP commands to control and monitor the data stored in the DNP databases. These data are passed between the module and the other protocol on the ProLinx module.
IEC 60870-5-103 Master Protocol Specifications
The IEC 60870-5-103 Master driver provides extensive support for Master implementations of the protocol. The serial port on the gateway is user-configurable to support the IEC protocol (Master, Error Checking, Baud rate, etc).
The module supports:
- 16 slaves (sessions with distinct Data Link Addresses)
- Each slave (session) supports up to 3 sectors (with distinct Common ASDU Addresses)
- Configurable Time Synch and General Interrogation messages during initialization
- Supports General Interrogation, General Command and Time Synchronization Commands.
|
General Parameters - IEC 60870-5-103M Protocol
|
|
Type
|
Specifications
|
|
Communication parameters
|
Baud Rate: 110 to 115K baud
Stop Bits: 1 or 2
Data Size: 5 or 8 bits
Parity: None, Even, Odd RTS Timing delays: 0 to 65535 ms
|
|
IEC 60870-5-103 Master
|
|
Type
|
Specifications
|
|
Configurable Parameters
|
Baud Rate
Parity
RTS On
RTS Off
Minimum Delay
Receive Timeout
Data Link Address Common ASDU Address
|
|
Status Data
|
Status Data include: Command Delay, Command Queue Count, Online Status for Each Slave, Command Error, Number of Requests and Number of Responses.
|
Hardware Specifications
| Power Supply |
24 VDC nominal |
| |
18-32 VDC allowed |
| |
Positive, Negative, GND Terminals |
| |
2.5 mm screwdriver blade |
Current Load
|
500 mA max@ 32 VDC max |
| Operating Temperature |
-20 to 50 Deg C |
| |
-4 to 122 Deg F |
|
Storage Temperature |
-40 to 85 Deg C |
| |
-40 to 185 Deg F |
| Relative Humidity |
5-95% (w/o condensation) |
| Dimensions |
Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD |
|
LED Indicators |
Power and Module Status |
| |
Application Status |
| |
Serial Port Activity LED |
| |
Serial Activity and Error LED Status |
| Configuration Serial Port |
Mini-DIN |
| |
RS-232 only |
| |
No hardware handshaking |
|
Ethernet Port |
10Base-T Connector |
| |
Link and Activity LED indicators |
| |
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 |
| |
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration |
|
Application Serial Ports |
Mini-DIN |
| |
RS-232/422/485 |
| |
RS232 handshaking configurable |
| |
RS422/485 screw termination included |
|
Port Isolation |
2500V Opto-Isolators |
| |
500V Power Supply Isolation |
|
Shipped with each unit |
Mini-DIN to DB-9M cables per serial port |
| |
4 ft RS-232 configuration cable |
| |
2.5mm screwdriver |
| |
CD (docs and Configuration utility) |
| |
RS-422/485 DB9 to Screw Terminal |
| |
Adaptor (1 or 4, depending on ports) |
Click here for dimensions diagram Certifications
The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class 1, Div 2
Ordering Information
|
5201-DNPSNET-103M
|
DNP over Ethernet to IEC60870-5-103 Master
|
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.
Sales and Support:
|