'C' Programmable Ethernet, Modbus
5201-ADMNET-MCM 5202-ADMNET4-MCM4
Product Description
The ProLinx 'C' Programmable Application Development Modules with Ethernet to Modbus Master/Slave creates a powerful platform for developing and running 'C' applications to communicate with Modbus Master/Slave networks and devices. The module provides one (5201) or four (5202) serial ports, each individually configurable as a Modbus or custom Master or Slave.
ADMNET Protocol Specifications
The ADM API Suite is provided to allow software developers access to the top layer of the serial ports. The ADMNET API suite accesses the Ethernet port.
Both APIs can be easily used without having detailed knowledge of the module's hardware design. The ADMNET API Suite consists the Ethernet Port API. The Ethernet Port API provides access to the Ethernet network. Applications for the ADMNET module may be developed using industry-standard DOS programming tools and the appropriate API components.
The Modbus (MCM) protocol driver supports Master and Slave implementations of the protocol. All Modbus serial ports are individually configurable, providing a very powerful and flexible host or device interface solution.
Product Applications
The 5201 ADMNET-MCM module is the ideal solution for many applications where Ethernet and serial connectivity need to be added to a Modbus Master/Slave platform. Example applications involving the ADMNET-MCM modules include:
-
Bar code scanner interface
-
Legacy ASCII protocol connections
-
Terminal port emulation
-
Printer driver (alarm/status printer)
-
Customized protocol implementations
Functional Specifications
Internal Database
The ProLinx module contains an internal database that can be configured as needed to handle your data transfer.
The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.
General Protocol Specifications
- Allows software developers to access Serial/Ethernet ports without needing detailed knowledge of the module's hardware design
- API library functions are specified using the C programming language syntax
- Supports multi-threaded applications
- The following compiler versions are compatible with the MVI module API:
- DigitalMars C++ V8.49
- Borland C++ V5.02
- Operating System - General software DOS 6-XL
- Flash ROM program space: 896 KB
- RAM program and data space: 640 KB
- Compact Flash socket: Up to 64 MB
ADM API Libraries
Each API provides a library of function calls. This library supports any programming language that is compatible with the Pascal calling convention.
- Initialization - Open and close the API
- Debug Port - Debug port user interface
- Database - Read and write data to database
- Timer - Start and check timers
- Backplane - Transfer data over the backplane
- LED - Set user LED indicators
- Flash - Parse configuration files
- Miscellaneous - Configure the console
Modbus Protocol Specifications
The Modbus driver provides access to an internal database of 4000 registers (words), with extensive support provided for both the Master and the Slave implementations of the protocol. The serial port(s) on the gateway can be individually configured to support the Modbus protocol (Master or Slave, RTU or ASCII, Baud Rate, etc).
|
General Parameters - Modbus Protocol
|
|
Type
|
Specifications
|
|
Communication parameters
|
Baud Rate: 110 to 115K baud
Stop Bits: 1 or 2
Data Size: 7 or 8 bits
Parity: None, Even, Odd
RTS Timing delays: 0 to 65535 ms
|
|
Error Checking
|
RTU mode (binary) with CRC-16 ASCII mode with LRC error checking
|
|
Floating Point
|
Floating point data movement supported, including configurable support for Enron implementation
|
|
Function Codes
|
1 : Read Output Status
2 : Read Input Status
3 : Read Multiple Data Registers
4 : Read Input Registers
5 : Write Single Bit
6 : Write Single Data Register
15 : Write Multiple Bits
16 : Write Multiple Data Register
|
|
Modbus Master
|
|
Type
|
Specifications
|
|
Command List
|
Up to 100 command per master port, each fully configurable for function, slave address, register to/from addressing and word/bit count
|
|
Status Data
|
Error codes are provided on an individual command basis, as well as a slave status list is maintained per active Modbus Master port.
|
|
Polling of command list
|
Configurable polling of command list, including continuous and on change of data, and dynamically user or automatic enabled.
|
|
Modbus Slave
|
|
Type
|
Specifications
|
|
Node address
|
1 to 247 - software selectable
|
|
Status Data
|
Error codes, counters and port status available per configured slave port. Status data is all pre-mapped in the module
|
Hardware Specifications
| Power Supply |
24 VDC nominal |
| |
18-32 VDC allowed |
| |
Positive, Negative, GND Terminals |
| |
2.5 mm screwdriver blade |
Current Load
|
500 mA max@ 32 VDC max |
| Operating Temperature |
-20 to 50°C |
| |
-4 to 122°F |
|
Storage Temperature |
-40 to 85°C |
| |
-40 to 185°F |
| Relative Humidity |
5% to 95% (non-condensing) |
| Dimensions |
Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD |
|
LED Indicators |
Power and Module Status |
| |
Application Status |
| |
Serial Port Activity LED |
| |
Serial Activity and Error LED Status |
| Configuration Serial Port |
DB-9M RS-232 only |
| |
No hardware handshaking |
Ethernet Port (Ethernet protocol gateways only) |
10Base-T half duplex RJ45 Connector |
| |
Link and Activity LED indicators |
| |
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 |
| |
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration |
|
Application Serial Ports (Serial protocol gateways only) |
RS-232/422/485 |
| |
RS232 handshaking configurable |
| |
RS-422/485 DB-9 to Screw Terminal Adaptor |
| |
Note: The number of serial application ports depends on the module type, and the combination of protocols. |
|
Serial Port Isolation |
2500V RMS port signal isolation per UL 1577 |
| |
3000V DC min. isolation port to ground and port to logic |
|
Shipped with each unit |
Mini-DIN to DB-9M serial cables |
| |
4 ft RS-232 configuration cable |
| |
2.5mm screwdriver |
| |
CD (docs and Configuration utility) |
| |
RS-422/485 DB-9 to Screw Terminal Adaptor for each serial application port (serial protocols only) |
Click here for dimensions diagram Certifications
The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class I, Div 2
Ordering Information
|
5201-ADMNET-MCM
|
Modbus 'C' Programmable Ethernet, 1 Serial Port
|
|
5202-ADMNET4-MCM4
|
Modbus 'C' Programmable Ethernet, 4 Serial Ports
|
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.
Sales and Support:
|