5102-MCM3-101S

Product Description

The ProLinx family Modbus Master/Slave to IEC60870-5-101 Slave communications module (5102-MCM3-101S) creates a powerful connection between devices on a Modbus network and an IEC 101 master device. The module is a stand-alone DIN rail-mounted protocol gateway that provides one IEC 101 Slave configurable serial port and three Modbus Master or Slave configurable serial ports.

The Modbus (MCM) protocol driver supports Master and Slave implementations of the protocol. All Modbus serial ports are individually configurable, providing a very powerful and flexible host or device interface solution.

The IEC 60870-5-101 Slave (101S) protocol driver supports Slave implementations of the protocol. The serial port is user-configurable, providing a very powerful and flexible host or device interface solution.

Product Applications

The MCM-101S modules are the ideal solution for the many applications where Modbus connectivity can be used to integrate an IEC 101 master device into a system. The IEC60870-5-101 Slave gateway is a powerful module designed with Slave support, enabling easy connection to an IEC 101 master device. In combination with the Modbus device support, the module provides a very powerful interface to the many Modbus devices which are in use in the industrial marketplace today. Applications for the module are found in most industries, especially the Manufacturing, Oil and Gas, Electrical Power and Food Processing.

Functional Specifications

Internal Database

The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.

The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.

Application Data Area

The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.

Status Data Area

This area is used to store error codes, counters, and port status information for each port.

Configuration Data Area

This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.

Modbus Protocol Specifications

The Modbus driver provides access to an internal database of 4000 registers (words), with extensive support provided for both the Master and the Slave implementations of the protocol. The serial port(s) on the gateway can be individually configured to support the Modbus protocol (Master or Slave, RTU or ASCII, Baud Rate, etc).

General Parameters - Modbus Protocol

Type

Specifications

Communication parameters

Baud Rate: 110 to 115K baud

Stop Bits: 1 or 2

Data Size: 7 or 8 bits

Parity: None, Even, Odd

RTS Timing delays: 0 to 65535 ms

Error Checking

RTU mode (binary) with CRC-16
ASCII mode with LRC error checking

Floating Point

Floating point data movement supported, including configurable support for Enron implementation

Function Codes

1 : Read Output Status

2 : Read Input Status

3 : Read Multiple Data Registers

4 : Read Input Registers

5 : Write Single Bit

6 : Write Single Data Register

15 : Write Multiple Bits

16 : Write Multiple Data Register

Modbus Master

Type

Specifications

Command List

Up to 100 command per master port, each fully configurable for function, slave address, register to/from addressing and word/bit count

Status Data

Error codes are provided on an individual command basis, as well as a slave status list is maintained per active Modbus Master port.

Polling of command list

Configurable polling of command list, including continuous and on change of data, and dynamically user or automatic enabled.

Modbus Slave

Type

Specifications

Node address

1 to 247 - software selectable

Status Data

Error codes, counters and port status available per configured slave port. Status data is all pre-mapped in the module

IEC 60870-5-101 Slave Protocol Specifications

The 101S module acts as a gateway between the IEC-870-5-101 other protocols and networks, as well as several proprietary interfaces.

General specifications include:

  • User-definable module memory usage
  • Storage of IEC time used in module is available in the database
  • Protocol implementation conforms to the IEC-870-5-101 specification with fully configurable parameters
  • Priority Queues
  • Invalid Bit Monitoring
  • Supports Balanced and Unbalanced Mode
  • Supports CP24 and CP56 time formats for events
  • Event generation configurable per point or data type

General Parameters

Communication parameters

Baud Rate: 110 to 38,400 baud
Stop Bits: 1 or 2
Data Size: 5 or 8 bits
Parity: None, Even, Odd
RTS Timing Delays: 0 to 65535 ms

IEC 870-5-101 Slave

Configurable Parameters

Data link address length
Common Address of ASDU length
Inform. Object Address length
Select/Operate Timeout
Event Scan delay
Use Balanced Mode
Short Pulse Time
Long Pulse Time
Time DB Offset

Status Data

Status data is returned in a block of counter values allowing communications to be effectively debugged.

Supported Data Types

M_SP_NA
M_DP_NA
M_ST_NA
M_ME_NA
M_ME_NB
M_ME_NC
M_IT_NA
C_SC_NA
C_DC_NA
C_RC_NA
C_SE_NA
C_SE_NB
C_SE_NC

Hardware Specifications

Power Supply 24 VDC nominal
  18-32 VDC allowed
  Positive, Negative, GND Terminals
  2.5 mm screwdriver blade

Current Load

500 mA max@ 32 VDC max
Operating Temperature -20 to 50°C
  -4 to 122°F
Storage Temperature -40 to 85°C
  -40 to 185°F
Relative Humidity 5% to 95% (non-condensing)
Dimensions

Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD

LED Indicators

Power and Module Status

  Application Status
  Serial Port Activity LED
  Serial Activity and Error LED Status
Configuration Serial Port DB-9M RS-232 only
  No hardware handshaking
Ethernet Port
(Ethernet protocol gateways only)
10Base-T half duplex RJ45 Connector
  Link and Activity LED indicators
  Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991
  Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
Application Serial Ports (Serial protocol gateways only) RS-232/422/485
  RS232 handshaking configurable
  RS-422/485 DB-9 to Screw Terminal Adaptor
  Note: The number of serial application ports depends on the module type, and the combination of protocols.
Serial Port Isolation 2500V RMS port signal isolation per UL 1577
  3000V DC min. isolation port to ground and port to logic
Shipped with each unit Mini-DIN to DB-9M serial cables
  4 ft RS-232 configuration cable
  2.5mm screwdriver
  CD (docs and Configuration utility)
  RS-422/485 DB-9 to Screw Terminal Adaptor for each serial application port (serial protocols only)
Click here for dimensions diagram

Certifications

The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class I, Div 2


Ordering Information

5102-MCM3-101S

Modbus Master/Slave (3 port) to IEC60870-5-101 Server

To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe/Middle East/Africa
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101