Can I use 2 AN-X-MOD gateways running as scanners in a redundant application? |
Article Number: 503 | Rating: Unrated | Last Updated: Tue, Jul 1, 2014 at 6:02 PM |
The AN-X-Mod gateway can be used in a redundant scanner application with the following considerations: 1) They cannot operate on completely separate S908 networks. They need to share the same physical media so that they are able to monitor the network for the presence of a Scanner. 2) The AN-X-Mod gateways have built-in termination so they need to be connected to the Modicon splitter. 3) It can be used in a regular ControlLogix application or in conjunction with a redundant ControlLogix application. |