How do I convert ASCII data to a Floating-Point value in a Logix based processor?


ASCII data acquired by the GSC module will be stored in the ReadString SINT (8 bit integer) array.

This data can by copied to a string type tag, and then converted to a real (floating-point) value using the RSLogix 5000 STOR function.