Can there be multiple Master devices on a DNP 3.0 network?


At this time, our InRAx line of DNP3 serial communications solutions offer 2 DNP serial ports. One will always be available as a DNP slave to provide data to a DNP serial master system. The other port may be used as a secondary, redundant DNP slave that has been connected to the same DNP3 master that is connected to the primary lave port; but connected on a separate physical serial network, as a way of providing redundant physical wiring paths between the our slave and the master.

This secondary port may not be used as a slave to a second DNP3 master, polling on an different network. However, it may be used as a DNP3 Master to poll other DNP3 Slave on a completely separate DNP3 physical serial network.


Related Keywords:

mvi46-dnp mvi56-dnp mvi71-dnp prolinx DNP DNP3


Custom Fields

Article ID: 133
Created On: Tue, Nov 28, 2006 at 11:06 AM
Last Updated On: Fri, Jun 27, 2014 at 5:11 PM
Authored by: Technical Support

Online URL: https://www.prosoft-technology.com/kb/article.php?id=133