RSLogix 500 sample for MVI69-xxx faults MicroLogix processor


I/O mismatch the first versions of our MVI69-XXX sample for MicroLogix processors had the wrong vendor ID code defined under the I/O configuration.

Within the RSLogix 500 program change the vendor ID code from 22 to the correct vendor ID code of 309. This will correct the issue with the I/O mismatch between RSLogix 500 and the MVI69-XXX solution.
Custom Fields

Article ID: 211
Created On: Tue, Nov 28, 2006 at 3:33 PM
Last Updated On: Tue, Jul 1, 2014 at 3:40 PM
Authored by: Technical Support

Online URL: https://www.prosoft-technology.com/kb/article.php?id=211