What is the difference between the 3150-MCM and the MVI46-MCM
The MVI46-MCM:
- Is the latest Modbus module for the Allen-Bradley ;SLC platform
- Provides a debug port which allows the user to view module configuration and status
- Provides a built-in data analyzer for troubleshooting communication problems with the attached Modbus devices
- Is field upgradable
- Is based on a 16-bit processor instead of the 3150-MCM's 8-bit processor
- Provides 5000 registers for data transfer (3150-MCM has 4000)
- Has direct M1 files access for faster data throughput (3150-MCM must page 50 words of data to the processor at a time)
- Supports baud rates of up to 115,200 on the serial port (3150-MCM supports 38,400 max)
- Supports 100 Modbus commands per port (3150-MCM supports 100 commands shared by both application ports)
Article ID: 22
Created On: Tue, Nov 28, 2006 at 8:41 AM
Last Updated On: Mon, Aug 29, 2016 at 4:47 PM
Authored by: Technical Support
Online URL: https://www.prosoft-technology.com/kb/article.php?id=22