"Invalid Input Size" when adding an Prosoft module to RSLogix 5000


Confirm that the Comm Format parameter in the modules I/O configuration is set to Data - INT. The default setting for this parameter in RSLogix5000 is Data - DINT. This setting will generate the error message mentioned above.

If the incorrect comm format is set, the only way to correct this is to delete the module from the I/O configuration and add the module using the correct Comm Format.



Custom Fields

Article ID: 225
Created On: Tue, Nov 28, 2006 at 3:58 PM
Last Updated On: Tue, Jul 1, 2014 at 6:26 PM
Authored by: Technical Support

Online URL: https://www.prosoft-technology.com/kb/article.php?id=225