How to resolve an issue where Siemens Step 7 software displays a message indicating that the ProSoft GSD file cannot be interpreted.


PROFIBUS DP GSD file names should be limited to eight characters.
File names longer than eight characters will cause this error.
Delete the excess characters in the file name so that the file name contains no more than eight characters before the .gsd extension.

Related Keywords:

PROFIBUS DP step 7 GSD file GSE file Siemens step 7 hardware configuration applet shows the following error: 'the file 'prlx05a5_v1.gsd' cannot be interpreted.'


Custom Fields

Article ID: 264
Created On: Wed, Nov 29, 2006 at 7:54 AM
Last Updated On: Thu, Feb 26, 2015 at 5:11 PM
Authored by: Technical Support

Online URL: https://www.prosoft-technology.com/kb/article.php?id=264