Do you have an in-rack Ethernet I/P solution for a PLC-2 processor?


Yes, the MVI71-DFNT can work in a 1771 chassis with a PLC-2 processor.

Along with the MVI71-DFNT sample ladder, you will need to use the following settings in the PLC-2 programming software:

*The Lengths of the BTW and BTR instructions should be zero.  It will default to a 64 word block transfer size.

*2-slot addressing is needed.