When using an MVI69-xxx or PS69-xxx module, why does a L43/L45 CompactLogix processor fault immediately after a download or after a power cycle?


A firmware anomaly has been identified in version 17 for the CompactLogix 1768-L43 and L45 processor that will not work properly when using any Prosoft MVI69 or PS69 communication modules.

FRN 18 will correct the issue.

Work around's are:
Use earlier FRN (16 or earlier)
or
Clear the major non - recoverable fault and re-download the program a second time
See also article #456 http://www.prosoft-technology.com/kb/article.php?id=456 for additional issue with PS69-DPM and PS69-DPS. 

Custom Fields

Article ID: 438
Created On: Mon, Jan 18, 2010 at 7:01 AM
Last Updated On: Wed, Jun 15, 2011 at 1:14 PM
Authored by: Administrator

Online URL: https://www.prosoft-technology.com/kb/article.php?id=438