Using AFC modules with corrected (net) flow as in input


The AFC is not designed to receive a corrected flow input.

However if the AFC is being used only for its accumulation and archive capabilities, then rather than the process temperature and pressure inputs, provide the meter's reference conditions as the AFC's temperature and pressure inputs.

Typically 15°C and 101.325kPa (SI) or 60°F and 14.73 PSIA (US).

Custom Fields

Article ID: 527
Created On: Fri, Sep 19, 2014 at 11:22 PM
Last Updated On: Wed, Dec 31, 2014 at 5:00 PM
Authored by: Administrator