<?xml version="1.0"?>

<rss version="2.0">


<channel>
<title>Home - All Categories - Rockwell In-chassis  - SLC  - MVI46 Series  </title>
<link>https://www.prosoft-technology.com/kb/category.php?id=13</link>
<description>This RSS Feed contains Articles of Category in the knowledge base. You can click on the title to view its content. Powered by PHPKB Knowledge Base Script (http://www.knowledgebase-script.com)</description>
<item>
										<guid>https://www.prosoft-technology.com/kb/article.php?id=306</guid>
										<title>How do I deal with an unsigned integer in an SLC, PLC5, or MicroLogix processor?</title>
										<link>https://www.prosoft-technology.com/kb/article.php?id=306</link>
										<description><![CDATA[Scenario: A device that uses an INT value to represent a range of 0 to 65535, but in the processor the INT tag has a range of -32768 to 32767.    Since the A/B processor does not have an unsigned Integer data type, you will need to convert this value...]]></description>

									</item>
<item>
										<guid>https://www.prosoft-technology.com/kb/article.php?id=6</guid>
										<title>Debug port connection parameters for Prosoft modules and gateways</title>
										<link>https://www.prosoft-technology.com/kb/article.php?id=6</link>
										<description><![CDATA[Connect PC to module&#039;s debug / configuration port using a null-modem cable        Start Hyperterminal, Putty or other comm program and use the following settings:                  bits per second: 57,600           data bits: 8           parity:...]]></description>

									</item>
<item>
										<guid>https://www.prosoft-technology.com/kb/article.php?id=72</guid>
										<title>When using the sample ladder I get an M0/M1 file reference error in my SLC processor if the MVI46 or 3150 is not in Slot 1.</title>
										<link>https://www.prosoft-technology.com/kb/article.php?id=72</link>
										<description><![CDATA[The M0 and M1 files are slot referenced. The second digit in the address represents the slot number.   If the MVI46 or 3150 module is in slot 1 (next to the processor), then the file reference is M0:1.XXXX and M1:1.XXXX  If the module is in slot 5,...]]></description>

									</item>
<item>
										<guid>https://www.prosoft-technology.com/kb/article.php?id=34</guid>
										<title>Is there a limit to the number of ProSoft modules I can place in my SLC chassis?</title>
										<link>https://www.prosoft-technology.com/kb/article.php?id=34</link>
										<description><![CDATA[There are limits to the number of ProSoft modules that can be placed in your system&#039;s rack:    1.&nbsp; The number of available slots in the chassis.    2.&nbsp; The size of the power supply used for the chassis; specifically, how much 5vdc...]]></description>

									</item>
<item>
										<guid>https://www.prosoft-technology.com/kb/article.php?id=42</guid>
										<title>My MVI46 module faults the processor after cycling power to the rack.</title>
										<link>https://www.prosoft-technology.com/kb/article.php?id=42</link>
										<description><![CDATA[   The bios settings have the console enabled. This will cause the MVI46 module to send a series of printf&#039;s out the debug port. This does not allow the module to boot up fast enough for the processor, and this will in turn fault the processor....]]></description>

									</item>
<item>
										<guid>https://www.prosoft-technology.com/kb/article.php?id=43</guid>
										<title>What are the advantages of the MVI46-MCM compare to the 3150-MCM?</title>
										<link>https://www.prosoft-technology.com/kb/article.php?id=43</link>
										<description><![CDATA[Here are some of the main advantages of the MVI46-MCM over the 3150-MCM:  Direct M0/M1 file access, makes it much easier to configure  You do not need to page memory as the 3150-MCM supports baud rates to 115.2 (3150 only to 38.4)  100 Modbus master...]]></description>

									</item>
<item>
										<guid>https://www.prosoft-technology.com/kb/article.php?id=57</guid>
										<title>Can the MVI46 or 3150 modules be placed in a remote rack?</title>
										<link>https://www.prosoft-technology.com/kb/article.php?id=57</link>
										<description><![CDATA[No. The MVI46 and 3150 module can only reside in the local or extended rack. Many times a ProLinx 4601-RIO-MCM can work in this type of application. The usage of M1 and M0 files prevents the module from operating in a remote rack. ]]></description>

									</item>
<item>
										<guid>https://www.prosoft-technology.com/kb/article.php?id=244</guid>
										<title>Where can I locate the User Manual for the MVI46-MCM</title>
										<link>https://www.prosoft-technology.com/kb/article.php?id=244</link>
										<description><![CDATA[All User Manuals for Prosoft Technology products can be found on the product pages of our website, or on the CD supplied with the product.]]></description>

									</item>
<item>
										<guid>https://www.prosoft-technology.com/kb/article.php?id=477</guid>
										<title>IEC-60870-5-104 Server Tutorial</title>
										<link>https://www.prosoft-technology.com/kb/article.php?id=477</link>
										<description><![CDATA[The following document outlines the ProSoft implementation of the IEC-60870-5-104 Server communication module as pertains to all -104S products.&nbsp;]]></description>

									</item>
<item>
										<guid>https://www.prosoft-technology.com/kb/article.php?id=419</guid>
										<title>How can I store my RSLogix500 program in a M13 EEPROM installed in a ProSoft 3250-L532M SLC processor?</title>
										<link>https://www.prosoft-technology.com/kb/article.php?id=419</link>
										<description><![CDATA[Before answering that question, a little history lesson will help understand the issue and the suggested solution.  The ProSoft 3250-L532M SLC 5/03 RTU processor&#039;s operating system (OS) firmware is 100% compatible only with Allen-Bradley&#039;s ...]]></description>

									</item>
<item>
										<guid>https://www.prosoft-technology.com/kb/article.php?id=416</guid>
										<title>I am using a ProSoft MVI46 solution and I am getting a Fault Message that says, &quot;Specialty I/O Module in Slot x has not responded within the time limit.&quot;  What can cause this?</title>
										<link>https://www.prosoft-technology.com/kb/article.php?id=416</link>
										<description><![CDATA[This particular fault is infrequent but common on the SLC platform.&nbsp; Without getting into a lot of boring details, it has to do with critical, sub-millisecond timing of backplane messages.&nbsp; ProSoft has worked closely with Rockwell...]]></description>

									</item>
<item>
										<guid>https://www.prosoft-technology.com/kb/article.php?id=528</guid>
										<title>How to enable Modbus commands in MVI46-MNETC</title>
										<link>https://www.prosoft-technology.com/kb/article.php?id=528</link>
										<description><![CDATA[MNETC and MBTCP products use a bit array to each command in each client. In the case of the MVI46-MNETC, each 16 bit register in N50:21 through N50-50 of our sample logic contains the bits to enable or disable the 16 available commands in the 30...]]></description>

									</item>

</channel>

</rss>