What are the causes of a -11 error code using a ProSoft Modbus product? |
Article Number: 443 | Rating: Unrated | Last Updated: Thu, May 5, 2011 at 1:42 PM |
A -11 is a timeout error. The MCM master port is sending the command but it does not get a valid response from the slave back in time. If the port x Response Timeout setting is 1000ms, the port x LED will blink once every 1000ms. This indicates the command is being sent out of the port.
Common causes of a -11 timeout error:
- baud rate, parity, etc mismatch.
- incorrect jumper setting at bottom of module (RS232, 422, 485 setting).
- Reversed polarity
- Wiring issues, try + and - pins only, no ground/shield.
- slave is busy and ignores the master command
- noise on the line, the message is compromised by the time it gets to the destination.
Connecting with ProSoft Configuration builder and using the Data Analyzer option in the diagnostic menu will show the Modbus traffic coming in and out of the port. It will help determine if a response from the slave is received or if there is noise on the line. The User Manual shows how to connect use ProSoft Coniguration Builder for diagnostics. |
Attachments (0)
There are no attachments for this article.
|
Comments
There are no comments for this article. Be the first to post a comment.
|
My RX light is on solid, what might that indicate?
Viewed 1 times since Fri, Jul 17, 2015
What's the difference between Modbus ASCII and Modbus RTU?
Viewed 1 times since Wed, Mar 19, 2008
How do I monitor the health of coms to my slaves when the module is a Master?
Viewed 1 times since Wed, Nov 29, 2006
Defining the Slave ID when issuing Modbus Broadcast write commands
Viewed 1 times since Tue, Nov 28, 2006
Can Modbus support redundant masters?
Viewed 1 times since Tue, Nov 28, 2006
I have a ProSoft Modbus Master solution and would like to know, is the Slave Status List the best place to monitor for communications health of the network?
Viewed 1 times since Tue, Mar 18, 2008
How can a module's Modbus port, configured as a Slave port, detect communication loss with the Master port?
Viewed 1 times since Tue, Nov 28, 2006
I am trying to use a ProSoft Modbus solution to send/receive data to a MSA Ultima X gas dectection system with Modbus interface and am having problems. How can I resolve this issue?
Viewed 1 times since Thu, Apr 24, 2008
What Modbus address would we need to put into the MODSIM32 simulator if we specified on the MVI56-MCM device address to 8680HEX (-31104 decimal) when the MVI56-mcm is the slave?
Viewed 1 times since Tue, Nov 28, 2006
I have limited or no experience with Modbus. How can I find out more about the protocol and command structure?
Viewed 1 times since Tue, Nov 28, 2006
|