What are the causes of a -11 error code using a ProSoft Modbus product? |
Article Number: 443 | Rating: Unrated | Last Updated: Thu, May 5, 2011 at 1:42 PM |
A -11 is a timeout error. The MCM master port is sending the command but it does not get a valid response from the slave back in time. If the port x Response Timeout setting is 1000ms, the port x LED will blink once every 1000ms. This indicates the command is being sent out of the port.
Common causes of a -11 timeout error:
- baud rate, parity, etc mismatch.
- incorrect jumper setting at bottom of module (RS232, 422, 485 setting).
- Reversed polarity
- Wiring issues, try + and - pins only, no ground/shield.
- slave is busy and ignores the master command
- noise on the line, the message is compromised by the time it gets to the destination.
Connecting with ProSoft Configuration builder and using the Data Analyzer option in the diagnostic menu will show the Modbus traffic coming in and out of the port. It will help determine if a response from the slave is received or if there is noise on the line. The User Manual shows how to connect use ProSoft Coniguration Builder for diagnostics. |
Attachments (0)
![]()
There are no attachments for this article.
|
Comments
![]()
There are no comments for this article. Be the first to post a comment.
|
I have limited or no experience with Modbus. How can I find out more about the protocol and command structure?
Viewed 1 times since Tue, Nov 28, 2006
Do any Prosoft modules support Modbus UDP?
Viewed 1 times since Mon, Aug 24, 2015
If I am reading the value from ProSoft 4x register, and it represents a digital input or digital output, how is the value stored?
Viewed 1 times since Tue, Nov 28, 2006
How do I read/write Modbus binary data?
Viewed 1 times since Wed, Nov 29, 2006
Why are my PLX gateway modbus serial commands not executing despite being enabled?
Viewed 1 times since Wed, Aug 12, 2015
I am trying to use a ProSoft Modbus solution to send/receive data to a MSA Ultima X gas dectection system with Modbus interface and am having problems. How can I resolve this issue?
Viewed 1 times since Thu, Apr 24, 2008
How can a module's Modbus port, configured as a Slave port, detect communication loss with the Master port?
Viewed 1 times since Tue, Nov 28, 2006
How do I monitor the health of coms to my slaves when the module is a Master?
Viewed 1 times since Wed, Nov 29, 2006
What's the difference between Modbus ASCII and Modbus RTU?
Viewed 1 times since Wed, Mar 19, 2008
How can I detect the feedback status of individual command successful or failed?
Viewed 1 times since Wed, Nov 29, 2006
|