| Home » Categories » Protocols » Modbus |
What are the causes of a -11 error code using a ProSoft Modbus product? |
| Article Number: 443 | Rating: Unrated | Last Updated: Thu, May 5, 2011 at 1:42 PM |
|
A -11 is a timeout error. The MCM master port is sending the command but it does not get a valid response from the slave back in time. If the port x Response Timeout setting is 1000ms, the port x LED will blink once every 1000ms. This indicates the command is being sent out of the port.
Common causes of a -11 timeout error:
- baud rate, parity, etc mismatch.
- incorrect jumper setting at bottom of module (RS232, 422, 485 setting).
- Reversed polarity
- Wiring issues, try + and - pins only, no ground/shield.
- slave is busy and ignores the master command
- noise on the line, the message is compromised by the time it gets to the destination.
Connecting with ProSoft Configuration builder and using the Data Analyzer option in the diagnostic menu will show the Modbus traffic coming in and out of the port. It will help determine if a response from the slave is received or if there is noise on the line. The User Manual shows how to connect use ProSoft Coniguration Builder for diagnostics. |
Attachments (0)
There are no attachments for this article.
|
Comments
There are no comments for this article. Be the first to post a comment.
|
Why are my PLX gateway modbus serial commands not executing despite being enabled?
Viewed 1 times since Wed, Aug 12, 2015
Defining the Slave ID when issuing Modbus Broadcast write commands
Viewed 1 times since Tue, Nov 28, 2006
What Modbus address would we need to put into the MODSIM32 simulator if we specified on the MVI56-MCM device address to 8680HEX (-31104 decimal) when the MVI56-mcm is the slave?
Viewed 1 times since Tue, Nov 28, 2006
My RX light is on solid, what might that indicate?
Viewed 1 times since Fri, Jul 17, 2015
How do you detect the individual Slave failure?
Viewed 1 times since Wed, Nov 29, 2006
I have multiple Modbus masters that need to communicate with 1 or more Modbus serial (RTU) slave devices. What product should be used??
Viewed 1 times since Tue, Jan 23, 2007
Can Modbus support redundant masters?
Viewed 1 times since Tue, Nov 28, 2006
What's the difference between Modbus ASCII and Modbus RTU?
Viewed 1 times since Wed, Mar 19, 2008
I have a ProSoft Modbus Master solution and would like to know, is the Slave Status List the best place to monitor for communications health of the network?
Viewed 1 times since Tue, Mar 18, 2008
|

Add Comment