Can an application have redundant AN-X2-GENI gateways scanning the GE Genius Bus Network(s)?

The AN-X2-GENI gateway can be used in a redundant scanner configuration with either a single GE Genius Bus network, or with a redundant network configuration.  In a redundant media configuration the GE Genius Bus I/O must be implemented with GE BSMs.

To work in a redundant scanner application the Primary gateway must be configured as Node 31 on the GE Genius Bus Network, and the secondary at Node 30.

This gateway will work with redundant ControlLogix applications, non-redundant ControlLogix applications, or CompactLogix processors.